Chapter 5 High-speed Link Setting
5-6
2) Parameter of High-speed link block setting
High-speed link block setting parameter is as shown below.
(1) High-speed link editing window.
Classification
High-speed link block setting window
Block
editing
Each entry of speed link setting windows is as follows.
Classification
Contents
Index
Number of high-speed link block
Module type
Select module type of slave
Mode
Select communication mode (transmit or receive) with slave
Station No.
Communication station No. of slave.
Read area
Starting address of the device to be transmitted from the slave module to the master
module.
Read area
Word size
Indicate the size of a send data
Save area
Starting address of the device to be received by the master module.
Save area
Word size
Indicate the size of a receive data
Rnet communicates by byte unit, even though address of High-speed link block in XG5000 is set by
Word unit.
Therefore, when the slave address set less than 1byte or 2xN bytes + 1byte, module point less than 8 bit
is dealt with 1 Word.
Note