230
Learning Advanced Features
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
14
Anti-hunting
regulation P-
Gain
AHR P-Gain
1000
0
–32767
-
15
Anti-hunting
regulation start
frequency
AHR Low
Freq
0
0
–AHR High
Freq
Hz
16
Anti-hunting
regulation end
frequency
AHR High
Freq
400.00
AHR Low
Freq
–400.00
Hz
17
Anti-hunting
regulation
compensation
voltage limit
AHR Limit
2
0
–20
%
Anti-hunting Regulation Setting Details
Code
Description
CON-13 AHR Sel
Selects the Anti-hunting regulator operation.
Setting
Function
0
No
Disable anti-hunting regulation.
1
Yes
Enable anti-hunting regulation.
CON-14 AHR P-Gain
Increasing AHR proportional gain improves responsiveness of
the anti-hunting regulation. However, current oscillation may
result if AHR proportional gain is set too high.
CON-15 AHR Low Freq
CON-16 AHR High Freq
Sets the lower limit frequency (CON-15) and the maxim limit
frequency (CON-16) for anti-hunting regulation.
5.25 Fire Mode Operation
This function is used to allow the inverter to ignore minor faults during emergency
situations, such as fire, and provides continuous operation to protect other systems, such
as ventilating fans. In Fire mode, the inverter continues to operate based on the Fire mode
run direction and frequency set at PRT-46 and PRT-47.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range Unit
PRT
44
Fire mode
password
Fire Mode
PW
3473
-
-
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...