Preparing the Installation
14
1.5 Cable Selection
When you install power and signal cables in the terminal blocks, only use cables that meet
the required specification for the safe and reliable operation of the product. Refer to the
following information to assist you with cable selection.
•
Wherever possible use cables with the largest cross-sectional area for mains power wiring,
to ensure that voltage drop does not exceed 2%.
•
Use copper cables rated for 600 V, 75
℃
for power terminal wiring.
•
Use copper cables rated for 300 V, 75
℃
for control terminal wiring.
•
The inverters in the range between 15 and 90 kW must be grounded conveniently with
fixed connections.
•
The inverters in the range between 5,5kW and 11kW must be grounded with and
industrial connector according to IEC 60309.
•
The minimum size of the protective earthing conductor shall comply with the local
safety regulations for high protective earthing conductor current equipment.
•
Only one conductor per terminal should be simultaneously connected
Ground Cable and Power Cable Specifications
Load (kW)
Ground Wire
Input/Output Power Wire
mm
2
AWG
mm
2
AWG
R/S/T
U/V/W
R/S/T
U/V/W
3-Phase
200 V
0.75
3.5
12
1.5
1.5
16
16
1.5
2.2
3.7
2.5
2.5
14
14
5.5
10
10
4
4
12
12
7.5
6
6
10
10
11
10
10
8
8
15
14
6
16
16
6
6
18.5
25
22
4
4
3-Phase
400 V
0.75
2
14
1.5
1.5
16
16
1.5
2.2
Содержание H100 0008-2(PLUS)
Страница 26: ......
Страница 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Страница 48: ...Installing the Inverter 22 ...
Страница 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Страница 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Страница 238: ...212 ...
Страница 239: ...213 목차 ...