MultiController E 0-100%
Side 2
LS Control A/S
1 Mounting
MultiController E must be mounted according to the general applicable installation rules in the ’Low Voltage
Directive’. The unit is to be carefully fixed on a plane and stable surface with screws in the 2 oval holes. The unit
may not be fixed on moving or vibrating surfaces. Avoid that unit get exposed to high temperature and direct
sunlight.
Ensure that the unit is not disturbed by electromagnetic interference from e.g. long connection cables.
Terminal Connections 24V Version
Terminal No.
Description
Comment
1 and 2 (Vout1)
0-10V output 1
Load max 10mA
3 and 4 (Vout2)
0-10V output 2
Load max 10mA
5
Not in use
7 and 8
0-10V input (for external setpoint)
7k Ohm input impedance
13 and 14
Connection of power supply
15-30VDC or 24VAC
15 and 16
Power supply of auxiliary outlet
As terminals 13 and 14
15, 17 and 18
RS 485 Modbus
2,4,6,8,9,14,15,20,22 0V / GND
19
Not in use
20 and 21
Tacho, PIR or alarm input
23 and 24
Voltage free contact. Function depending on set-up
24VDC NO, 3A AC1