LS Control MultiController E Скачать руководство пользователя страница 11

MultiController E 0-100% 

 

 
LS Control A/S 

 

 

Side 11  

F4: 

Allow writing from Modbus. Set configuration at 1, if configuration is to be altered from the Modbus master. 

Note:

 Cannot be altered by Modbus, must be altered manually in MultiController. 

 
3 Setpoint Overview 

Name 

Factory Setting  

Min 

Max 

Unit 

C1 Level 

50 

100 

C2 SchedulerOnOff 

OFF 

OFF 

ON 

Activated/deactivated 

C3 BoostTime (0-250sec) 

250 

Seconds 

C4 UserRights (Security Level) 

 

C5 Prolonged Operation 

10 

1  

240 

Minutes 

C6 Setpoint Source 

Internal 

Internal  External   

C8 Alarm Function 

60 

Seconds. 

C9 Optional Text 

OFF 

OFF 

ON 

 

C10 Operation Hour Counter 

12  

months 

E1 Model (ON/OFF,Percentage %, Step) 

Depending of Setting   

 

 

E2 OutputMin (0-5V) 

50 

Volt 50 = 5.0V 

E3 OutputMax (5-10V) 

100 

50 

100 

Volt 50 = 5.0V 

E4 OutputStart (Min,Max,Last) 

Last 

Min 

Max 

 

E5 Inverter output 

OFF 

OFF 

ON 

 

E6 Relay Shifting Point 

0.1 

0.0 V 

10.0 V 

Volt 

E26 Max Input2 

10,0 

0,0 

10,0 

Volt 

E27 Sensor 2 value min 

0  

0  

100 

E28 Sensor 2 value max 

0  

0  

100 

E40 Vout2 (0=10V 1= not in use 2=Offset of 
Vout1) 

 

E42 TempSensor2 selection (

NTC22 

NTC2 

Volt 

= Vin2, 

Alarm1 

= NTC2, 

Tacho 

= NTC2, 

PIR1

= NTC2, 

NTC10K 

= not in 

use, 

PIR2 

= NTC2) 

Alarm2

 = NTC2 

NTC22 

 

 

 

E44 User Text Name 

 

 

 

 

E45 User Text Counter 

 

 

 

 

E46 Alarm Level Min 

10 

50 

 

E47 Alarm Level Max 

60 

50 

100 

 

E48 PIR Time 

10 

36000  

Seconds 

E49 Out 2 Offset 

100 

200 

E52 Time before Regulation 

240 

Seconds 

E55 Step Level 1 (in percentage) 

25 

100 

E56 Step Level 2 (in percentage) 

50 

100 

E57 Step Level 3 (in percentage) 

75 

100 

E58 Step Level 4 (in percentage) 

100 

100 

F1 ModbusAddress (1-247) 

50 

247 

Address 

F2 Modbus baudrate (0=Off 1=9600 
2=19200) 

Speed 

F3 Modbus Parity1=EVEN 2=ODD 
3=NONE) 

Data 

F4 ModbusAllowWrite 

OFF 

OFF 

ON 

OFF/ON 

 

Содержание MultiController E

Страница 1: ...ervice Menu E Menu 9 3 Setpoint Overview 11 4 Technical Data 12 5 Applied Standards 12 Description MultiController E 0 100 for adjustment of output signal 0 10V from 0 to 100 4 steps or ON OFF The integrated scheduler function allows for individual adjustment of the output signal with up to 10 shifts per day The scheduler clock has an integrated battery back up RS 485 interface with MODBUS protoco...

Страница 2: ...nit is not disturbed by electromagnetic interference from e g long connection cables Terminal Connections 24V Version Terminal No Description Comment 1 and 2 Vout1 0 10V output 1 Load max 10mA 3 and 4 Vout2 0 10V output 2 Load max 10mA 5 Not in use 7 and 8 0 10V input for external setpoint 7k Ohm input impedance 13 and 14 Connection of power supply 15 30VDC or 24VAC 15 and 16 Power supply of auxil...

Страница 3: ...2 Vout1 0 10V output 1 Load max 10mA 3 and 4 Vout2 0 10V output 2 Load max 10mA 5 Not in use 7 and 8 0 10V input for external setpoint 7k Ohm input impedance 16 and 9 24V power output 24V DC max 75mA 17 and 18 RS 485 Modbus 19 Not in use 2 4 6 8 9 20 0V GND 20 and 21 Tacho PIR or alarm input 23 and 24 Voltage free contact Function depending on set up 5A AC1 250VAC ...

Страница 4: ...tep Fig 1 A By pressing arrow up the level of output signal is increased or stepped up by one B By pressing arrow down the level of output signal is decreased or stepped down by one C By pressing ON OFF output signal shifts between turned on and turned off D By pressing menu The display changes to main menu E Icon indicating that Modbus communication is enabled F Icon showing that the output signa...

Страница 5: ...e integrated scheduler function can be set to shift amongst 3 different operating levels Stop Normal Setpoint or Alternative Setpoint Relay output is closed when voltage level is higher than selected value factory setting is 0 1V i e the relay operates as an operation relay 03 0 100 PIR As set up 02 but instead of using the scheduler function a PIR motion sensor is connected to shift between Norma...

Страница 6: ...er When finished adjusting the value is saved by pressing Enter Pressing ESC will cancel the adjustment by leaving the pop up submenu without saving 2 5 Main Menu and Submenus The submenus A F are accessible from the main menu 2 6 System Information A Menu Current operating data for MultiController is displayed in this menu Data is updated every 5 seconds 01 I ntc Internal temperature 02 Ntc1 Not ...

Страница 7: ... from scheduler B2 Scheduler Reset This menu point resets the scheduler Note All settings in scheduler is deleted B3 Scheduler Copy Copy all scheduler setting from one weekday to another Previous settings are overwritten by this copying function B4 Date and Time The date weekday and time for the MultiController is set in this menu Clock is a 24 hour clock Optional choice of automatic shift between...

Страница 8: ...o 2 60 sec the alarm is activated The time indicates how long the alarm input NTC2 GND must be open before alarm occurs ALARM terminal 23 24 opens and is indicated in display with Alarm Din ALARM2 Alarm is indicated in display with Alarm Din but relay is not affected NOTE If ALARM1 is activated the normal operation relay function is not operational C9 Optional Plant Text is activated or deactivate...

Страница 9: ...This also set the boost level 100 E4 Adjustment of Start Level The manual start level may be set at 3 different start values 1 Minimum level 2 Maximum level 3 Latest level of controller when turned off Note this functionality is only available when MultiController model choice E1 is set to percentage Boost function menu point C3 overrules start level adjustment E5 Inverted output Option for invert...

Страница 10: ...ue must be increase In input is closed via a relay contact adjustment is not necessary E47 Alarm level Max Alarm is activated in C8 Upper limit of tacho signal Adjustment If tacho alarm occurs when motor is running maximum rpm value must be increased E48 PIR Time Prolonged operation time for PIR input in seconds E49 Offset of Vout2 in relation to Vout1 Only if E40 2 Formula Vout2 Vout1 x E49 100 E...

Страница 11: ...lt 50 5 0V E4 OutputStart Min Max Last Last Min Max E5 Inverter output OFF OFF ON E6 Relay Shifting Point 0 1 0 0 V 10 0 V Volt E26 Max Input2 10 0 0 0 10 0 Volt E27 Sensor 2 value min 0 0 100 E28 Sensor 2 value max 0 0 100 E40 Vout2 0 10V 1 not in use 2 Offset of Vout1 0 0 2 E42 TempSensor2 selection NTC22 NTC2 Volt Vin2 Alarm1 NTC2 Tacho NTC2 PIR1 NTC2 NTC10K not in use PIR2 NTC2 Alarm2 NTC2 NTC...

Страница 12: ... 7k Ohm input impedance 0 10VDC input2 Vin2 7k Ohm input impedance 0 10VDC output1 Vout1 0 10 0V DC Max 10mA 0 10VDC output2 Vout2 0 10 0V DC Max 10mA RS 485 Channel A and B SD Card MicroSD max 2GB with LS Control Firmware Jumper 120 Ohms termination RS 485 5 Applied Standards EN 61000 6 1 and EN 61000 6 3 Electromagnetic Compatibility EMC EN 60335 1 The Low Voltage Directive This product complies...

Отзывы: