MultiController E 0-100%
LS Control A/S
Side 11
F4:
Allow writing from Modbus. Set configuration at 1, if configuration is to be altered from the Modbus master.
Note:
Cannot be altered by Modbus, must be altered manually in MultiController.
3 Setpoint Overview
Name
Factory Setting
Min
Max
Unit
C1 Level
50
0
100
%
C2 SchedulerOnOff
OFF
OFF
ON
Activated/deactivated
C3 BoostTime (0-250sec)
5
0
250
Seconds
C4 UserRights (Security Level)
0
0
3
C5 Prolonged Operation
10
1
240
Minutes
C6 Setpoint Source
Internal
Internal External
C8 Alarm Function
0
0
60
Seconds.
C9 Optional Text
OFF
OFF
ON
C10 Operation Hour Counter
0
0
12
months
E1 Model (ON/OFF,Percentage %, Step)
Depending of Setting
E2 OutputMin (0-5V)
0
0
50
Volt 50 = 5.0V
E3 OutputMax (5-10V)
100
50
100
Volt 50 = 5.0V
E4 OutputStart (Min,Max,Last)
Last
Min
Max
E5 Inverter output
OFF
OFF
ON
E6 Relay Shifting Point
0.1
0.0 V
10.0 V
Volt
E26 Max Input2
10,0
0,0
10,0
Volt
E27 Sensor 2 value min
0
0
100
%
E28 Sensor 2 value max
0
0
100
%
E40 Vout2 (0=10V 1= not in use 2=Offset of
Vout1)
0
0
2
E42 TempSensor2 selection (
NTC22
=
NTC2
Volt
= Vin2,
Alarm1
= NTC2,
Tacho
= NTC2,
PIR1
= NTC2,
NTC10K
= not in
use,
PIR2
= NTC2)
Alarm2
= NTC2
NTC22
E44 User Text Name
E45 User Text Counter
E46 Alarm Level Min
10
0
50
E47 Alarm Level Max
60
50
100
E48 PIR Time
10
1
36000
Seconds
E49 Out 2 Offset
100
0
200
%
E52 Time before Regulation
0
0
240
Seconds
E55 Step Level 1 (in percentage)
25
0
100
%
E56 Step Level 2 (in percentage)
50
0
100
%
E57 Step Level 3 (in percentage)
75
0
100
%
E58 Step Level 4 (in percentage)
100
0
100
%
F1 ModbusAddress (1-247)
50
1
247
Address
F2 Modbus baudrate (0=Off 1=9600
2=19200)
0
0
2
Speed
F3 Modbus Parity1=EVEN 2=ODD
3=NONE)
1
1
3
Data
F4 ModbusAllowWrite
OFF
OFF
ON
OFF/ON