To programme the transmission code from remote proceed as 
follows: send the radio control code continuously for more than

 

10  seconds  and  the  control  unit  will  enter  the  programming 
mode  as    described  above  for  the  CODE  LED  in  the  main 
menu.

 

The  control  unit  is  supplied  by  the  manufacturer  with  remote 
programming of the  transmission code not  enabled; to  enable 
the function proceed as follows: check that the extended menu

 

1  is  enabled  (the  T.  MOT.  and  T.  PAUSA  LEDs  start  flashing 
alternatively), use the SEL key to navigate to the CODE when 
the corresponding LED is flashing and press the SET key: the 
CODE  is  enabled  and  programming  is  complete.  Repeat  the 
operation to restore the previous configuration.

 

 

B) PED. CODE. 

(Step-by-Step / Automatic Operation):

 

The  control  unit  is  supplied  by  the  manufacturer  with  the 
Automatic  operation  function  disabled. To  enable  the  function 
proceed  as  follows:  check   that  the  extended  menu  1  is 
enabled  (the  T.  MOT.  and  T.  PAUSA  LEDs  start  flashing 
alternatively),  use  the  SEL  key  to  navigate  to  PED.  CODE 
when  the  corresponding  LED  is  flashing  and  press  the  SET 
key:  the  PED.  CODE  LED  lights  up  and  programming  is 
complete.

 

By  using  both  the  radio  control  and  the  low  voltage  push- 
button  station  to  control  the  shutter,  the  following  operation 
may  be  obtained:  the  first  press  opens  the  shutter  until  the 
programmed  motor  time  elapses  while  the  second  press 
closes it; if a button is pressed before the programmed motor

 

time has elapsed, the control unit 

inverts 

the motion, whether 

during the opening or closing process. Repeat the operation to 
restore the previous configuration.

 

 

C) INB. CMD. AP (

Maintaining Hydraulic Motor Pressure

):

 

The  control  unit  is  supplied  by  the  manufacturer  with  the 
hydraulic motor pressure maintenance disabled. To enable the 
function  proceed  as  follows:  check  that  the  extended  menu  1 
is  enabled  (the  T.  MOT.  and  T.  PAUSA  LEDs  start  flashing 
alternatively),  use  the  SEL  key  to  navigate  to  INB.  CMD.  AP. 
when  the  corresponding  LED  is  flashing  and  press  the  SET 
key:  the  INB.  CMD.  AP.  LED  lights  up  and  programming  is 
complete.  In  this  way  the  control  unit  will  send  a  closing 
command  to  the  motor  every  2  hours  for  2  seconds.  Repeat 
the operation to restore the previous configuration.

 

 

 

D) LAMP/CORT (Electronic Brake):

 

The  control  unit  is  supplied  by  the  manufacturer  with  the 
electronic  brake  function  disabled.  To  enable  the  function 
proceed  as  follows:  check   that  the  extended  menu  1  is 
enabled  (the  T.  MOT.  and  T.  PAUSA  LEDs  start  flashing 
alternatively),  use  the  SEL  key  to  navigate  to  LAMP/CORT. 
when  the  corresponding  LED  is  flashing  and  press  the  SET 
key:  the  LAMP/CORT.  switches  on  and  programming  is 
complete.  The  control  unit  reduces  the  forward  motion  of  the 
gate   due  to  inertia  in  the  presence  of  a   stop  or  inversion 
command.  Repeat  the  operation  to  restore  the  previous 
configuration.

 

 

EXTENDED MENU 2

 

The  control  unit is  supplied  by the manufacturer with  only the 
option  of  directly  selecting  the  functions  listed  in    the  main 
menu.

 

To enable the functions listed in extended menu 2, proceed as 
follows: access extended menu 1 (as described in the relevant 
paragraph),  then  press  the  SET  button  again  and  hold  for  5 
seconds;  the  T.  MOT.  and  T.  PAUSA  LEDs  will  flash 
simultaneously  and  the  user  has  30  seconds  within  which  to 
select  the  functions  of  extended  menu  2  using  the  SEL  and 
SET    buttons.  When  this  time  has  elapsed  the  control  unit 
returns to the main menu.

 

 

EXTENDED MENU 2

 

 

LED status                              LED off                LED on

 

A) CODE                  1 sec. inversion time                0.5 sec. inversion time

 

3) PED. CODE         Soft Start = OFF                      Soft Start = ON

 

C) INB.CMD.AP       User present CH = OFF          User present CH = ON

 

D) LAMP/CORT       Input PUL = PUL                     Input PUL = D.S.

 

E) T. MOT.                          Simultaneous flashing beacon ON/OFF

 

F) T. PAUSA.                      Simultaneous flashing beacon ON/OFF

 

 

A) CODE (Inversion Time Selection 1 s /  0.5 s ):

 

The  control  unit is  supplied  by the manufacturer  with the  time 
taken to invert the rotation movement of the motor set at about

 

1   second;  to   increase  the  inversion  speed   to  about  0.5 
second,  proceed  as  follows:  check  that  extended  menu  2  is 
enabled  (T.  MOT.  and  T.  PAUSA  LEDs  start  flashing 
simultaneously), use the 

“SEL” button to navigate to the CODE 

LED  when  flashing  and  press  the 

“SET”  button:  the  CODE 

LED  remains  permanently  lit  and  programming  is  complete. 
Repeat the operation to restore the previous configuration.

 

 

B) PED. CODE ( Soft Start ) :

 

The  control  unit  is  supplied  by the  manufacturer  with  the  Soft 
Start operation mode disabled. To enable the function proceed 
as  follows:  check  that  extended  menu  2  is  enabled  (T.  MOT. 
and  T.  PAUSA  LEDs  flash  simultaneously),  use  the 

“SEL” 

button  to  navigate  to  the  CODE  PED  LED  when  flashing  and 
press  the 

“SET”  button:  the  CODE  PED  LED  remains 

permanently lit and programming is complete. This means that 
at every start of movement, the control unit will govern the way 
the    motor    starts,    bringing    the    power    in    gradually,    from 
minimum  to  maximum  in  the  first  2  seconds  of  operation. 
Repeat the operation to restore the previous configuration.

 

 

C) INB. CMD. AP (

User present during closure operation

) :

 

The  control unit is  supplied  by the manufacturer  with the user 
present    during    closure    function    disabled.   To    enable    the 
function  proceed as follows: make sure that extended menu 2 
is  enabled  (the  T.  MOT.  and  T.  PAUSA  LEDs  flash 
simultaneously), use the SEL button to navigate  to INB. CMD. 
AP.  when  the  corresponding  LED  is  flashing  and  press  the 
SET button: the INB. CMD. AP. switches on and programming 
is  complete. The control unit will now operate in User  Present 
mode  during  the  closure  phase.  Repeat  the  operation  to 
restore the previous configuration.

 

 

D) LAMP/CORT (Selecting Input PUL = PUL / D.S. ):

 

The  control  unit  is  supplied  by  the  manufacturer  with  Input 
PUL  =  PUL,  i.e.  with  the  operation  mode  for  the  normal 
connection of the command button (NO). If you  wish to define 
Input  PUL  =  D.S.,  i.e.  with  the  operating  mode  for  the 
connection  of  a  safety  device  (NC)  (intervention  during  the 
opening  stage  causes  the  opening  gate  to  stop  immediately, 
followed  directly by a  brief inversion of the direction of travel), 
proceed as follows: check that extended menu 2 is enabled (T. 
MOT.  and  T.  PAUSA  LEDs  start  flashing  simultaneously), 
press  the  SEL  button  until  the  LAMP/CORT  LED  flashes  and 
press  the  SET  button:  the  LAMP/CORT  LED  remains 
permanently lit and programming is complete.

 

Warning:     connect     any     safety     device     only     after

 

programming Input  PUL  =  D.S.  If necessary, it is  possible 
to  restore  the  previous  configuration,  taking  care  to 
disconnect the safety device first.

 

 

RESET:

 

To  restore  the  default  configuration,  press  the  SEL  and  SET 
keys  simultaneously,  all  

RED  

LEDs  will  light  up  and  then 

switch off. 

 
 
 

 

DIAGNOSTICS: 

Command input test:

 

Содержание LRX2102

Страница 1: ...l alimentazione ed il collegamento di Fotocellule Coste pneumatiche NC L intervento nella fase di apertura non viene considerato nella fase di chiusura provoca l inversione del moto Questo ingresso se non utilizzato deve essere ponticellato Spunto iniziale e Regolazione Forza Motore La centrale elettronica è dotata delle funzioni di spunto iniziale e regolazione della forza motore completamente ge...

Страница 2: ...cortesia ripetere l operazione sopra descritta premendo il tasto SEL due volte ottenendo il lampeggio veloce del LED LAMP CORT anziché una volta Ripetere l operazione se si desidera ripristinare la configurazione di fabbrica Funzionamento Lampeggiatore L uscita 230Vac si attiverà ogni volta che l automazione è in movimento per la durata del tempo motore Funzionamento Lampeggiatore anche in pausa L...

Страница 3: ... Led T PAUSA posizionarsi con il tasto SEL sul lampeggio del LED LAMP CORT poi premere il tasto SET nello stesso istante il LED LAMP CORT si accenderà permanentemente e la programmazione sarà conclusa In questo modo la centrale riduce l avanzamento del cancello dovuto all inerzia in corrispondenza di un arresto o di un comando d inversione Ripetere l operazione se si desidera ripristinare la confi...

Страница 4: ...la pulsantiera in modo che l utente non venga a trovarsi in posizione pericolosa in accordo al punto 5 2 8 della EN 12453 La centrale non presenta nessun tipo di dispositivo di sezionamento della linea elettrica 230 Vac sarà quindi cura dell installatore prevedere nell impianto un dispositivo di sezionamento E necessario installare un interruttore omnipolare di con categoria III di sovratensione E...

Страница 5: ...ai bambini di giocare con il dispositivo e tenere lontano dalla loro portata i radiocomandi ATTENZIONE conservare questo manuale d istruzioni e rispettare le importanti prescrizioni di sicurezza in esso contenute Il non rispetto delle prescrizioni potrebbe provocare danni e gravi incidenti Esaminare frequentemente l impianto per rilevare eventuali segni di danneggiamento Non utilizzare il disposit...

Страница 6: ...sitif de sécurité La centrale autorise l alimentation et le raccordement de cellules photoélectriques barres palpeuses pneumatiques NC L intervention en phase d ouverture n est pas prise en compte en phase de fermeture par contre elle provoque une inversion du mouvement En cas de non utilisation cette entrée doit être pontée Accélération initiale et réglage de la Force Moteur La centrale électroni...

Страница 7: ...er la fonction Clignotant procéder comme suit se positionner à l aide de la touche SEL sur la LED LAMP CORT appuyer ensuite sur la touche SET à partir de ce moment là la LED LAMP CORT reste allumée en permanence Pour retourner à la configuration d usine refaire la même opération Pour activer la lumière de courtoisie refaire l opération décrite ci dessus en appuyant deux fois sur la touche SEL au l...

Страница 8: ...enverra ainsi toutes les 2 heures une commande de fermeture au moteur pendant 2 secondes Pour retourner à la configuration précédente refaire la même opération D LAMP CORT Frein électronique Le fabricant fournit la centrale avec fonction frein électronique désactivée Pour activer cette fonction procéder comme suit s assurer d avoir bien activé le menu étendu 1 signalé par le clignotement alterné d...

Страница 9: ...ent sur la touche SEL et sur la touche SET il y aura allumage en même temps de toutes les leds ROUGES de signalisation et leur extinction tout de suite après DIAGNOSTIC Test input commandes En face de chaque entrée de commande en basse tension la centrale dispose d une LED de signalisation pour pouvoir contrôler rapidement l état Logique de fonctionnement LED allumée entrée fermée LED éteinte entr...

Страница 10: ...ition de danger en application du point 5 2 8 de la norme EN 12453 La centrale ne présente aucun dispositif de sectionnement de la ligne électrique 230 Vac il appartiendra donc à l installateur de prévoir un dispositif de sectionnement sur l installation Il faut installer un interrupteur à coupure omnipolaire en catégorie III de surtension Il faut que ce dernier soit positionné de façon à être pro...

Страница 11: ...enables power supply and connection for photoelectric cells and pneumatic buffers NC No action is taken into account during the opening stage and causes inverted motor action during the closing stage If not used this input must be bridged Initial pick up and Motor Power Adjustment The electronic control unit is equipped with initial pick up and motor power adjustment functions that are fully manag...

Страница 12: ...uration Flashing beacon function while the unit is paused The 230 V a c output will activate every time automation takes place for the duration of the motor timer If the Pause Time is stored the 230 V a c output will also be active during the Pause Flashing Beacon Operation The 230 V a c output will activate every time automation takes place for the duration of the motor timer Courtesy Light Opera...

Страница 13: ... flash simultaneously and the user has 30 seconds within which to select the functions of extended menu 2 using the SEL and SET buttons When this time has elapsed the control unit returns to the main menu EXTENDED MENU 2 LED status LED off LED on A CODE 1 sec inversion time 0 5 sec inversion time 3 PED CODE Soft Start OFF Soft Start ON C INB CMD AP User present CH OFF User present CH ON D LAMP COR...

Страница 14: ...mmended that motor reducers fitted with an electromechanical unlocking device are used so that the shutter can be moved manually if necessary In compliance with section 5 4 3 of EN 12453 electromechanical unlocking systems or similar devices should be used as these enable the shutter to stop safely at its stop limit Power supply and motor connection cables which are suitable for use in conjunction...

Страница 15: ...Electronic Control Unit LRX 2102 comply with the requirements of Directives R TTE 99 5 EC EMC 2004 108 EC LVD 2006 95 EC ...

Отзывы: