10/100Base-T

(RJ45)

-

+

EIA-485

BACnet MS/TP or Modbus

~

-

12-35 VDC

12-24 VAC

+

~

4 5 6

8

15 16 17

POWER

Ethernet

RS-485

Serial Terminal / M-Bus

RESET

PLC

LINK

ACT

ACT

BACnet/IP Ethernet

BBMD

POWER

STATUS

Connectors

EIA-485  4  Input GND

MS/TP 

5  Input + (B) non-inverting input

Modbus  6  Input - (A) inverting input

Ethernet  8  10/100Base-T (RJ45)

POWER  15  Power supply input EARTH GND

 

16  Power supply input MINUS

 

  Can be connected to EARTH GND

 

17  Power supply input PLUS

 

   

Must NOT be connect to

 

   

EARTH GND

SERIAL  40  EIA-232 (DB9 male)

 

  Terminal or M-Bus depending on

 

  DIP switch No. 7

Buttons

RESET 

Reset

STATUS  Send “I AM” message

Status LEDs

A OFF 

PLC not running

  Green flashing 

PLC program running

  Green 

PLC program not running

  Orange 

I/O disabled

  Red 

CPU overload

B Green flashing 

Traffic on

   

BACnet MS/TP port

C Green flashing 

Traffic on BACnet/IP port

D Green 

Ethernet link

E Green flashing 

Ethernet traffic

F Green 

LINX-210:OFF

   

LINX-211:BBMD enabled

G Green 

Power

H OFF 

Normal operation

NOTE: 

If terminal 4 is not connected make a

 

short between terminal 15 and 16,

 

and connect to EARTH GND.

40

A

B

C

F

E

D

G

H