L-DALI User Manual
42
LOYTEC
Version 5.2
LOYTEC electronics GmbH
3.
If possible dim artificial light in room until luxmeter show desired lux setpoint. To dim
the light select the rooms DALI group in the
Dim lights
drop down box, enter a desired
dim value in the field
Level
and press the
Set
button.
4.
Enter the measured lux level in the input field and select index 0.
5.
Press the
Calibrate
button.
3.5.5 Parameterize the DALI button
1.
On the DALI Installation page click on the
Configure
button next to the button device
that is to be configured. The dialog shown in Figure 33 appears.
Figure 33: Configure DALI button functions.
2.
Use the drop-down boxes to determine which function is executed and which group is
controlled by which button input. In our example we use button T1 for “On/Up” and T2
for “Off/Down”, both controlling group 2. This will allow us to control all lights in the
room together.
3.
Click on
Save
to write the configuration to the button device.
3.5.6 Parameterize the Constant Light Controller
1.
Go to the
Data Points
page and select the data point path of constant light controller
application instance 0.
Figure 34: DALI Installation Web Interface: Parameters.
BACnet
L-DALI:
/BACnet
Port/Datapoints/Channel
1/Constant
Light
Controllers/Constant Light Controller 0/