Lowell Model UPS9C-1000 Manual
Pg. 6
Step 4:
Disable/Enable ROO/RPO function .
•
ROO:
Contact open:
UPS shuts down .
Contact closed:
UPS start-up (UPS is connected to AC power and AC power is available) .
Note:
The local ON/OFF control by pressing On/Off button overrides the remote-control function .
•
RPO:
Contact open:
UPS shuts down and Fault LED (3) will be ON .
To return to normal operation, de-activate external remote contact (Fault LED [3] will be OFF) and restart .
Step 5:
Turn on/off the UPS .
Press the ON/OFF button on the front panel for two seconds to power on the UPS .
Step 6:
Install software .
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown . You may insert
provided CD into CD-ROM to install the monitoring software . If not, please follow steps below to download and install monitoring
software from the internet:
1 . Go to the website http://www .power-software-download .com
2 . Click ViewPower software icon and then choose your required OS to download the software .
3 . Follow the on-screen instructions to install the software .
4 . When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near
the clock .