21
Error signals:
The pump is equipped with self-diagnostics and malfunction detection. Defects
detected by the pumpsystem are signalled to the user with alternating short and
long LED light flashes.
1) No error, pump is running:
LED on
2) Low voltage failure:
SHORT, LONG
3) Speed feedback failure:
SHORT, SHORT, SHORT, SHORT, LONG
4) Overtemperature failure:
SHORT, SHORT, SHORT, LONG
5) Blocked rotor:
SHORT, SHORT, SHORT, SHORT,
SHORT,LONG
6) Airpurge:
200 msec ON – 200 msec OFF – 200 msec
ON
7) Standby:
50 msec ON – 1.5 sec OFF – 50 msec ON
Troubleshooting
Problem
Cause
Solution
Pump
not
running
Not connected or
connected incorrectly
Connect correctly
Pump too hot, dry
operation- or
overheating protection
active
Allow to cool, pump restarts
automatically
Pump blocked
See section 8
“Maintenance/Disassembly”
Pump is
noisy
Not thoroughly air
purged
See section 7.2 “Getting started”
Foreign objects in pump
See section 8
“Maintenance/Disassembly”
Worn bearing
Replace pump
Malfunctioning pumps can be returned to the manufacturer‘s address. The
manufacturer will refuse to accept packages with unpaid shipping or invoices for
repair. The manufacturer grants a two-year guarantee under the condition of
correct installation and proper use.