I580
GB
I
07
19
31100419
9
G
B
TERMINAL LAYOUT
A1 A2 11 14 12
- +
C
IN1 NTC NTC
FAN
CONTROL
-
+
POWER RATINGS
Note. The rated operating voltage of the three versions according to IEC and cULus standards are respectively:
– DCTLA 400: 400VAC for IEC
– DCTLA 480: 400...480VAC for IEC and cULus
– DCTLA 690: 600...690VAC for IEC, 600VAC for cULus.
Code
DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA DCTLA
400 400 400 400 400 480 480 480 480 480 690 690 690
0075 0150 0300 0500 1000 0090 0180 0360 0600 1200 0300 0500 1000
Rated operating voltage Us 400VAC 50/60Hz 400...480VAC 50/60Hz 600…690VAC 50/60Hz
Rated current Ie 11A 22A 43A 72A 144A 11A 22A 43A 72A 144A 29A 48A 96A
Step power
400VAC 7.5kvar 15kvar 30kvar 50kvar 100kvar 7.5kvar 15kvar 30kvar 50kvar 100kvar 20kvar 33kvar 67kvar
440VAC - - - - - 8kvar 16.5kvar 33kvar 55kvar 110kvar 22kvar 37kvar 73kvar
480VAC - - - - - 9kvar 18kvar 36kvar 60kvar 120kvar 24kvar 40kvar 80kvar
525VAC - - - - - - - - - - 26kvar 44kvar 87kvar
600VAC - - - - - - - - - - 30kvar 50kvar 100kvar
690VAC - - - - - - - - - - 30kvar 50kvar 100kvar
Peak inverse voltage 1800VAC 2200VAC 3600VAC