Doc: I470GB10_16.docx 18/10/2016
p. 6 / 19
Setting parameters (setup) from the front panel
To access the parameter programming (setup) menu:
o
Engine must be stopped.
o
From the normal measurement display, press
▲
and
▼
simultaneously for 2 sec to enter the
Main menu
.
o
While SETUP is shown, press
START
.
The first menu is shown (P01) with its scrolling description.
Select the desired menu from the list below using
▲
and
▼
and confirm with
START
.
The first parameter of the selected menu is shown, with its scrolling description.
Select the desired parameter in the menu using
▲
and
▼
and confirm with
START
.
The present setting of the parameter is shown. Change the value using
▲
and
▼
. Confirm the value with
START
. Display goes back to parameter selection.
Press simultaneously
▲
and
▼
for a short time to go back to menu selection or for 2 sec to save settings and quit setup (in this case the unit restarts).
Code
MENU
DESCRIPTION
P01
UTILITY
Language, brightness, display pages, etc.
P02
GENERAL
System specifications
P03
PASSWORD
Access code setup
P04
CONFIGURATIONS Multiple
programmable configurations
P05
BATTERY Battery
parameters
P06
ACOUSTIC ALARMS
Control of internal buzzer and external siren
P07
ENGINE SPEED
Engine speed sensors and parameters
P08
OIL PRESSURE
Oil pressure sensors and parameters
P09
COOLANT TEMPERATURE
Engine temperature sensors and parameters
P10
FUEL LEVEL
Fuel level sensors and parameters
P11
ENGINE START
Engine start cycle parameters
P12
GENERATOR VOLTAGE CONTROL
Generator voltage parameters
P13
GENERATOR PROTECTION
Alternator protection functions
P14
DIGITAL INPUTS
Programmable digital input functions
P15
DIGITAL OUTPUTS
Programmable digital output functions
P17
MISCELLANEOUS
Miscellaneous functions, e.g. maintenance etc.
P18
USER ALARMS
User programmable alarms
ALA
ALARMS TABLE
Alarm enabling and effect
Parameter table
P01 – UTILITY
UoM
Default
Range
P01.01
Language
ENG ENG
ITA
FRA
ESP
DEU
P01.02
Display backlight brightness high
%
100 0-100
P01.03
Display backlight brightness low
%
25 0-50
P01.04
Low backlight brightness delay
sec
180 5-600
P01.05
Return to default measurements
sec
300
OFF / 10-600
P01.06
Default left indicator measurement
V sum
V sum
VL1-L2
VL2-L3
VL3-L1
VL1
VL2
VL3
P01.07
Default right indicator measurement
Hz Hz
A
kVA
%Fuel
Oil Pr
Temp
V batt
P01.08
Shutdown delay (RGK400SA only)
min
OFF OFF/1-1440
P01.01
– Display text language selection.
P01.02
– High display backlight adjustment.
P01.03
– Low display backlight adjustment.
P01.04
– Delay before switching to low display backlight.
P01.05
– Delay before returning to default page display when no button is pressed. If set to OFF, the last manually selected page remains on the display.
P01.06
– Default left measurement displayed on power up and after reset delay.
P01.07
– Default right measurement displayed on power up and after reset delay.
P01.08
– If a value in minutes is set, the controller switches off automatically after this time when in STOP mode.
P02 - GENERAL
UoM
Default
Range
P02.01
CT primary
A
5 1-10000
P02.02
CT secondary
A
5 1-5/OFF
P02.03
Use of VT
OFF OFF-ON
P02.04
VT primary
V
100 50-50000
P02.05
VT secondary
V
100 50-500
P02.06
Phase sequence check
OFF OFF