Setting parameters (setup) from the front panel 

 

To access the parameter programming (setup) menu: 

o

 

Engine must be stopped. 

o

 

From the normal measurement display, press 

and 

simultaneously for 2 sec to enter the 

Main menu

o

 

While SETUP is shown, press 

START

 

 

The first menu is shown (P01) with its scrolling description. 

 

Select the desired menu from the list below using  

and 

and confirm with 

START

 

The first parameter of the selected menu is shown, with its scrolling description. 

 

Select the desired parameter in the menu  using  

and 

and confirm with 

START

 

The present setting of the parameter is shown. Change the value using 

and 

. Confirm the value with 

START

. Display goes back to parameter selection. 

 

Press simultaneously 

and 

for a short time to go back to menu selection or for 2 sec to save settings and quit setup (in this case the unit restarts). 

 

 

Code 

MENU 

DESCRIPTION 

P01 

UTILITY 

Language, brightness, display pages, etc.  

P02 

GENERAL 

System specifications   

P03 

PASSWORD 

Access code setup 

P04 

CONFIGURATIONS Multiple 

programmable configurations 

P05 

BATTERY Battery 

parameters 

 

P06 

ACOUSTIC ALARMS   

Control of internal buzzer and external siren 

P07 

ENGINE SPEED 

Engine speed sensors and parameters 

P08 

OIL PRESSURE 

Oil pressure sensors and parameters 

P09 

COOLANT TEMPERATURE 

Engine temperature sensors and parameters 

P10 

FUEL LEVEL 

Fuel level sensors and parameters 

P11 

ENGINE START 

Engine start cycle parameters 

P12 

GENERATOR VOLTAGE CONTROL 

Generator voltage parameters 

P13 

GENERATOR PROTECTION 

Alternator protection functions 

P14 

DIGITAL INPUTS 

Programmable digital input functions 

P15 

DIGITAL OUTPUTS 

Programmable digital output functions 

P17 

MISCELLANEOUS 

Miscellaneous functions, e.g. maintenance etc. 

P18 

USER ALARMS 

User programmable alarms 

ALA 

ALARMS TABLE 

Alarm enabling and effect 

 

Parameter table 

 

P01 – UTILITY 

UoM 

Default 

Range

 

P01.01 

Language  

 

ENG ENG 

ITA 

FRA 
ESP 

DEU 

P01.02 

Display backlight brightness high 

100 0-100 

P01.03 

Display backlight brightness low 

25 0-50 

P01.04 

Low backlight brightness delay  

sec 

180 5-600 

P01.05 

Return to default measurements 

sec 

300 

OFF / 10-600 

P01.06 

Default left indicator measurement 

 

V sum 

V sum  

VL1-L2 
VL2-L3 
VL3-L1 

VL1 
VL2 
VL3 

P01.07 

Default right indicator measurement 

 

Hz Hz 

kVA 

%Fuel 

Oil Pr 
Temp 

V batt 

P01.08 

Shutdown delay (RGK400SA only) 

min 

OFF OFF/1-1440 

P01.01

 – Display text language selection. 

P01.02

 – High display backlight adjustment. 

P01.03

 – Low display backlight adjustment. 

P01.04

 – Delay before switching to low display backlight. 

P01.05

 – Delay before returning to default page display when no button is pressed. If set to OFF, the last manually selected page remains on the display. 

P01.06

 – Default left measurement displayed on power up and after reset delay. 

P01.07

 – Default right measurement displayed on power up and after reset delay. 

P01.08

 – If a value in minutes is set, the controller switches off automatically after this time when in STOP mode.

 

 

P02 - GENERAL 

UoM 

Default 

Range

 

P02.01 

CT primary    

5 1-10000 

P02.02 

CT secondary   

5 1-5/OFF 

P02.03 

Use of VT 

 

OFF OFF-ON 

P02.04 

VT primary 

100 50-50000 

P02.05 

VT secondary 

100 50-500 

P02.06 

Phase sequence check 

 

OFF OFF 

Содержание RGK400SA

Страница 1: ...s 3 Navigating between the display pages 3 Switching on and starting up RGK400SA 3 Switching on and starting up RGK420SA 3 Expandability 4 Inputs and outputs 4 User alarms UAx 4 IR programming port 4...

Страница 2: ...eter and alarm messages in 5 languages ENG ITA FRA SPA DEU 3 Ph N 480 VAC rated generator voltage measuring input 1 ph current input 6 digital inputs including o 4 standard digital inputs o 1 digital...

Страница 3: ...er only switches off at the end of this after the engine has stopped During the cooling cycle the display reads out a countdown of the time to engine shutdown If you wish to stop the engine immediatel...

Страница 4: ...occurs o the properties of the alarm as for standard alarms i e how it interacts with the genset controller If the alarm is displayed following activation of an external digital input then the source...

Страница 5: ...f the RGK4 SA controller more or less in the position shown alongside Hold it in position for a few seconds until you hear a beep The app runs automatically and the parameters are loaded and displayed...

Страница 6: ...or voltage parameters P13 GENERATOR PROTECTION Alternator protection functions P14 DIGITAL INPUTS Programmable digital input functions P15 DIGITAL OUTPUTS Programmable digital output functions P17 MIS...

Страница 7: ...ment P04 n 01 Rated generator voltage Always set phase to phase voltage for polyphase systems P04 n 02 Choice of connection type three phase with without neutral two phase or single phase P04 n 03 Vol...

Страница 8: ...asurements while performing calibration P08 04 Selection of unit of measure for oil pressure P08 05 P08 06 The minimum oil pressure pre alarm and alarm thresholds respectively See the corresponding al...

Страница 9: ...C P11 03 Generator frequency threshold for determining motor running P11 04 W speed or pick up signal threshold or AC from permanent magnet alternator threshold for determining motor running P11 05 Gl...

Страница 10: ...ed current for alarm A31 Maximum generator current P13 02 Delay for alarm in previous parameter P13 03 Percentage threshold referred to rated current for alarm A32 Generator short circuit P13 04 Delay...

Страница 11: ...of the signal the engine begins its stop cycle Start without stop Starts the engine remotely and does not stop it in the event of an alarm The signal must be maintained for as long as the engine needs...

Страница 12: ...time set in P05 04 A16 Battery voltage low Occurs if battery voltage remains below the threshold set in P05 03 for longer than the time set in P05 04 A17 Battery discharged Occurs if engine start atte...

Страница 13: ...Manual circuit breaker open A46 Cannot change configuration A47 Water in fuel UA1 UA1 UA2 UA2 A38 System error 5V Occurs if an internal error occurs in the RGK4 SA controller Contact Technical Support...

Страница 14: ...e sensor offset Advanced Calibrates resistive sensors by adding subtracting a value in Ohms to the resistance measured by them to compensate for cable length or resistance offsets Calibration is made...

Страница 15: ...K ALIMENTATO 18 12 11 13 14 L3 L1 L2 L3 24 L1 25 L2 23 S1 21 20 S2 RGK420SA 3 4 5 17 6 N N 22 19 10 9 8 F F4A ELETTROV CARBURANTE FUEL SOLENOID VALVE START AVVIAMENTO F F6A LIVELLO CARBURANTE AN MASSA...

Страница 16: ...OIL PRESSURE T1A 15 16 3 4 5 17 6 LIBERO 1 2 FREE F INP5 INP6 INP4 INP3 INP2 INP1 ARRESTO DI EMERGENZA ALTERNATORI TIPO BOSCH MARELLI LUCAS PICK UP PICK UP BATTERY ALTERNATOR TYPE BOSCH MARELLI LUCAS...

Страница 17: ...4 23 22 21 19 16 18 15 BATTERY 20 17 8 10 12 14 7 9 11 13 2 4 6 1 3 5 L1 L2 L3 N S1 S2 COM1 OUT2 OUT4 COM2 D OUT1 OUT3 OUT5 INP1 AN INP3 INP5 S GND INP2 INP4 100 500VLL 50 60Hz CAT III I 0 025 5A SSR...

Страница 18: ...impedance 100 K Pre excited battery charging alternator 500 rpm input terminal 7 Operating range 0 33 V Max input current 1 mA Max voltage at D terminal 12 or 24 VDC battery voltage Excitation curren...

Страница 19: ...max 0 2 2 5 mmq 24 12 AWG UL use data Cable cross section min max 0 75 2 5 mm 18 12 AWG Tightening torque 0 56 Nm 5 Lbin Enclosure Version Flat panel mounted Material Polycarbonate Front protection ra...

Отзывы: