Wall Exhauster Installation

If your fan is a wall exhauster, a mounting template is 

shipped with the fan. Use the template to locate the 
necessary lag screws or anchor bolts on the wall. The fan 
can then be lifted and attached easily. Secure with lag 
screws, anchor bolts, or other suitable fasteners.

Damper Installation

If your fan is supplied with dampers, follow the directions

below. If your fan does not include dampers, proceed to 
Belt and Pulley Installation.

1. Place the damper inside the curb or inside the duct
work. Ensure the damper will open freely for the correct
direction of the airflow.
2. Secure to curb at the damper shelf.
3. Drill hole in the curb shelf for conduit needed for motor

wiring.
4. Operate the dampers manually to ensure the blades
move freely.
5. Install fan over curb while aligning the conduit location 
with the conduit hole in the curb.

Wiring Installation

NOTICE! All wiring should be in accordance 
with local ordinances and the National Electrical 
Code, NFPA 70. Ensure the power supply 
(voltage, frequency, and current carrying 
capacity of wires) is in accordance with the 
motor nameplate.

(See page 3 for diagram)

Upblast units have two wiring conduits. The vertical 

conduit comes plugged. The horizontal conduit is directly

above the vertical conduit

For Units Without A Junction Box:

An approved metal field wiring compartment must be 

secured to the unit with two screws in order that the box 
does not rotate. All wires must be protected from abrasion 
where they enter and exit the wiring compartment. The 
green ground wire from the motor must be secured under 
the green ground screws inside the field wiring compartment 
using a closed loop connector. Complete connections in 
accordance with the wiring diagram on the motor.

For Units With A Junction Box:

Pull wires through the appropriate conduit. Protect wires 

from abrasion where they enter the field wiring compartment 
and complete connections in accordance with the diagram 
on the motor.

Leave enough slack in the wiring to allow for motor 

movement when adjusting belt tension. Some fractional 
motors have to be removed in order to make the connection 
with the terminal box at the end of the motor.

NOTICE! Follow the wiring diagram in the disconnect 

switch and the wiring diagram provided with the motor. 
Correctly label the circuit on the main power box and 
always identify a closed switch to promote safety (i.e., 
red tape over a closed switch).

1. Remove the top cap which covers the motor assembly 

by unlatching the snap clips.

2. For internal wiring, run the electrical wire and conduit 

through the opening drilled in the damper shelf (refer to 

Damper Installation

), then through the wiring conduit in 

the ventilator base to the motor compartment. For 
external wiring, run the wires through the horizontal 
conduit on upblast units, or under top cap in downblast 
units.

3. Pull the wires through and complete the wiring. 

Single Speed, Single Phase Motor

2 Speed, 2 Winding, Single Phase Motor

Single Speed, Single Phase, Dual Voltage

When ground required, attach to ground A or B with No. 6 thread forming screw. To 

reverse, interchange T-5 and J-10 leads.

To reverse, interchange any 2 line leads.

2 Speed, 2 Winding, 3 Phase

To reverse: High Speed-interchange leads T

11

 and T

12

.

Low Speed-interchange leads T

1

 and T

2

. Both Speeds-interchange any 2 line leads.

T-1

T-4

Ground B

L 2

L1

Ground A

Line

When ground required, 
attach to ground A or B 
with No. 6 thread forming 
screw. To reverse, inter-
change T-1 and T-4 
leads.

Ground A

Ground B

T-1

T-4

Low Speed

High Speed

L 1

L 2

Line

Ground B

J-10

T-5

Ground A

Link A

Link B

Low Voltage

Line

L 2

L 1

Ground A

Link A & B

L1

L 2

Line

Ground B

T-5

J-10

4 5 6

1

7

2
8

3
9

L1 L2 L3

4 5 6

7 8 9

1 2

3

L1 L2 L3

Low Voltage

208/230 Volts

High Voltage

460 Volts

3 Phase, 9 Lead Motor
Y-Connection

7

1

6

7 8 9

4 5 6

1 2

3

Low Voltage

208/230 Volts

High Voltage

460 Volts

8

2

4

9

3

5

L1

L3

L2

L1

L3

L2

3 Phase, 9 Lead Motor
Delta-Connection

When ground is required, attach to ground A or 
B with no. 6 thread forming screw. To reverse, 
interchange T-1 and T-4.

Содержание ACE-B

Страница 1: ...in order that maintenance personnel are provided complete control of the power source Grounding is required All field installed wiring must be completed by qualified personnel All field installed wir...

Страница 2: ...in accordance with the diagram on the motor Leave enough slack in the wiring to allow for motor movement when adjusting belt tension Some fractional motors have to be removed in order to make the con...

Страница 3: ...1 8 3000 5 8 5 16 1104 1200 1 1 8 7 4200 3 4 3 8 1440 1800 1 1 4 7 6000 7 Ensure fan and ductwork are clean and free of debris 8 Close and secure all access doors 9 Restore power to fan Start up Turn...

Страница 4: ...e interval by a factor of 3 For vertical shaft installations divide the interval by a factor of 2 RPM Temp F Greasing Interval Up to 1000 30 to 120 6 months 120 to 200 2 months 1000 to 3000 30 to 120...

Страница 5: ...r slowly to back wheel off the shaft Replacing Pulleys and Belts 1 Clean the motor and fan shafts 2 Loosen the motor plate mounting bolts to relieve the belt tension Remove the belt 3 Loosen the pulle...

Страница 6: ...90 1 2 540 13 16 Above Drilled hole placement Right Wheel puller Troubleshooting Problem and Potential Cause Low Capacity or Pressure Incorrect direction of rotation Make sure the fan rotates in same...

Страница 7: ...p Cap Top Cap Lid 1b Top Cap Cylinder 2 Top Cap Clip 4 3 Motor Motor 4 Motor Plate Motor Plate 5 Baffle Baffle 6 Wheel Assembly Wheel Assembly 7 Bird Screen Bird Screen 8 Base Base 9 Conduit Conduit 1...

Страница 8: ...Baffle Baffle Baffle 6 Wheel Assembly Wheel Assembly Wheel Assembly Wheel Assembly 7 Bird Screen Bird Screen Bird Screen Bird Screen 8 Base Base Base Base 9 Conduit Conduit Conduit Conduit 10 Isolato...

Страница 9: ...Top Cap Top Cap Lid 1b Top Cap Cylinder 2 Top Cap Clip 4 3 Motor Motor 4 Motor Plate Spun Motor Plate 5 Baffle Baffle 6 Wheel Assembly Wheel Assembly 7 Bird Screen Bird Screen 8 Wall Flange Wall Flan...

Страница 10: ...e Spun Motor Plate 5 Baffle Baffle Baffle 6 Wheel Assembly Wheel Assembly Wheel Assembly 7 Bird Screen Bird Screen Bird Screen 8 Wall Flange Wall Flange Wall Flange 9 Isolator 3 Isolator 4 Isolator 4...

Страница 11: ...4 Lower Post 4 Lower Post 8 13 Wind Band Wind Band Wind Band 14 Brace 4 Brace 8 15 Power Assembly Power Assembly Power Assembly 16 Shaft Shaft Shaft 17 Bearing 2 Bearing 2 Bearing 2 18 Drive Sheave D...

Страница 12: ...pringfield Missouri 65803 4637 explaining in writing in detail your complaint and referring to the specific model and serial numbers of your fan Upon receipt by Loren Cook Company of your written comp...

Отзывы: