3) Analogs outputs configuration
In standard, the device has no output. It can, by /S1,/S2 options, provide 1 or 2 outputs. These outputs, insulated be-
tween themselves, are independently configurable. Analog outputs configuration is presented through 2 rubrics:
- Output type:
- current output (mA),
- voltage output (V).
And for each output type, the low and high scale.
- Output parameters:
- security value,
- limitation,
- response time.
The security value
allows to set the output to a known state when there is a sensor breaking or a measure range over-
flow. This value will be transferred to output.
The limitation
allows to bound the output signal swing to the configured output scales for all input signal values.
Only security value goes beyond this function.
The response time
allows a smoothing of the output. It is adjustable from 0 to 60 s.
Default factory setup is:
- 4 to 20 mA current output,
- Security value = 22 mA,
- No limitation,
-Response time = 0 s.
Switched off
Switched on
Inactive
Event
Alarm
Relay in +
security
Relay in -
security
Delay
Delay before
activation
Delay before
de-activation
active
Switched off
Switched on
Event time measure is reseted
after event disappearing