E 25
2.2) Characteristic :
The device follow the PROFIBUS EN 50710 volume 2 specification
supported baud rate:
9.6K, 19.2K, 93.75K, 187.5K, 0.5M, 1.5Mbauds
transmission type:
RS485, 8bits of data, 1 stop, even parity
Connector:
sub D 9 pins
3) Using:
The address, the baud rate of bus and data format are to be setting on device via the RS232 link. All needing informa-
tion for communication on network are include in the GSD file provide on our web site : www.loreme.fr
This information are in 3 groups:
- operating information (baud rate supported, available functions, … ),
- data configuration (format of input data and output data),
- alarm list and operating default, parameters.
3.1) Detail of input and output data:
We call input data, the data transferred from slave to master, and output data the transfer from master to slave.
There is 73 bytes of input data and 1 byte of output data. The input data are composed of 36 words of measure and 1
byte for the relays alarm status. The output byte is use for reset the energy counters.
3.2) Details of diagnosis data:
The diagnosis data are composed of 6 bytes of standard diagnosis and 2 bytes of device specific diagnosis.
3.3) Exchange data frame:
b7 b6 b5 b4 b3 b2 b1 b0
0 0 0 0 0 0 0 0/1
Star voltage
Byte 1
Word 1
phase 1
Byte 2
(V)
Byte 3
Word 2
Byte 4
Star voltage
Byte 1
Word 1
phase 2
Byte 2
(V)
Byte 3
Word 2
Byte 4
Star voltage
Byte 1
Word 1
phase 3
Byte 2
(V)
Byte 3
Word 2
Byte 4
Interlinked voltage
Byte 1
Word 1
Phase 1-2
Byte 2
(V)
Byte 3
Word 2
Byte 4
Interlinked voltage
Byte 1
Word 1
Phase 2-3
Byte 2
(V)
Byte 3
Word 2
Byte 4
Interlinked voltage
Byte 1
Word 1
Phase 3-1
Byte 2
(V)
Byte 3
Word 2
Byte 4
Reset energy output
Measure input
bit 0 = 1 => Reset energy