E 19
6.3) Data format:
Data are given in integer 32 bits format.
NORMAL format : Data transmitted Most significant word first, compound of 4 bytes i.e 2 words.
SPECIAL format : Data transmitted least significant word first, compound of 4 bytes i.e 2 words.
The data write for the energy reset is a hexadecimal code. This code is compound of 2 bytes, i.e.1 word.
Code $55AA: reset of all energies.
7) Data Table:
Decimal word address
(Hexadecimal)
b7 b6 b5 b4 b3 b2 b1 b0
Total
Words
Bytes
40960 ($A000)
Reserve
Byte 1
Word 1
1
1
Byte 2
2
40961 ($A001)
Reserve
Byte 3
Word 2
2
3
Byte 4
4
40962 ($A002)
Star voltage
Byte 1
Word 1
3
5
phase 1
Byte 2
6
40963 ($A003)
(V)
Byte 3
Word 2
4
7
Byte 4
8
40964 ($A004)
Star voltage
Byte 1
Word 1
5
9
phase 2
Byte 2
10
40965 ($A0005)
(V)
Byte 3
Word 2
6
11
Byte 4
12
40966 ($A006)
Star voltage
Byte 1
Word 1
7
13
phase 3
Byte 2
14
40967 ($A007)
(V)
Byte 3
Word 2
8
15
Byte 4
16
40968 ($A008)
Interlinked voltage
Byte 1
Word 1
9
17
Phase 1-2
Byte 2
18
40969 ($A009)
(V)
Byte 3
Word 2
10
19
Byte 4
20
40970 ($A00A)
Interlinked voltage
Byte 1
Word 1
11
21
Phase 2-3
Byte 2
22
40971 ($A00B)
(V)
Byte 3
Word 2
12
23
Byte 4
24
40972 ($A00C)
Interlinked voltage
Byte 1
Word 1
13
25
Phase 3-1
Byte 2
26
40973 ($A00D)
(V)
Byte 3
Word 2
14
27
Byte 4
28
40974 ($A00E)
Current
Byte 1
Word 1
15
29
Phase 1
Byte 2
30
40975 ($A00F)
(A)
Byte 3
Word 2
16
31
Byte 4
32