Loreme CAL4/100ig Скачать руководство пользователя страница 7

 

SOMMAIRE

 

 E 7 

5.2 proof interval 

 
According table 2 from CEI 61508-1 the PFDavg ,for systems operating in low demand mode, 
must be between  ≥ 10

-3

 and <10

-2

 

for SIL2 safety functions and between  ≥ 10

-4

 and <10

-3

 for SIL3 safety functions . 

T

[Proof]

 = 1 year

 

T

[Proof]

 = 5 years

 

T

[Proof]

 = 10 years

 

T

[Proof]

 = 20 years

 

PFD

avg=7.88E

-06

 

PFD

avg=3.94E

-05

 

PFD

avg=7.88E

-05

 

PFD

avg=1.57E

-04

 

 temperature conditions 45°C  
 

 PFD

avg

 value depending proof interval 

λ

safe

 

λdangerous = PFH 

SFF 

305 FIT 

1.8 FIT 

99.4% 

 
approximation : PFDavg = 

λdangerous x T[Proof] /2  (error caused by approximation < 3%)  

 
Fields marked in green means that the calculated values of PFDavg are within the limits allowed for SIL 3 
 
Summary:  
 
Fault probability  PFD = 7.88 E

-6

 x Tproof [year]  

 
either for : Tproof = 10 years 8 % from SIF and for  Tproof = 20 years 16 % from  SIF in SIL3 
 
Remarks :  
 
- Test intervals should be determined according to the PFDavg required . 
 
- The SFF , PFDavg and PFH must be determined for the entire safety instrumented function (SIF) 
ensuring that the " out of range current values" are detected at system level and they actually lead to the safety position. 

5 Commissioning and periodic proof

 

 
The periodic test procedure is defined by LOREME and must be followed by the end user to ensure and guarantee the SIL level over 
time. 
Periodic testing should be performed following the procedure defined below and at the intervals defined  
under paragraph 

" proof interval "

 

 

5.1  control steps 

 
Periodic proof allows detection of possible product internal failure and loop calibration. 
environmental conditions and a minimum heating time of 5 minutes must be respected. 
 
 Isolator test and complete output Loop control (

the system is unavailable during the test

 
1. If necessary, bypass the security system and / or take appropriate provision to ensure safety during the test. 
2. Disconnect the current input transmitter.  
3. Using a current simulation device (note 1), set the input current to high alarm value (≥ 21.0 mA). 
4. Raise the front cover of device. With the TEST terminals and a milliammeter, check if each output current have this value /- 
1%. (the green LED of each output is light off when the milliammeter is connected) 
5. Set the input current to the low alarm value  (≤ 3.6 mA) 
6. Check if the signal from each output reaches this value /-1% 
7. Set the output current to a median value (= 12 mA) 
8. Check if the signal from each output reaches this value at +/-1% (linearity and transfer function check) 
9. Remove the input simulator, close the front panel and connect the transmitter input . 
10. Remove the bypass on the safety controller system or return to a normal operating condition

 

11. After testing, the results should be documented and archived. 
 
Any device that does not satisfy the control needs to be replaced. 

Note 1: The current generator must be calibrated (according to the state of the art and practice) 

 

4-20mA signal isolator, signal splitter with 2,3,4 outputs 
SIL2 / SIL3   

 

 

 

 CAL4/100ig     CAL4/100igM 

Содержание CAL4/100ig

Страница 1: ...fety manual LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ Phone 03 87 76 32 51 Fax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual on www loreme...

Страница 2: ...tate E4 2 1 Safety function E4 2 2 Safety fallback position E4 3 Safety Recommendation E4 3 1 Interfaces E4 3 2 Configuration Calibration E4 3 3 Useful lifetime E4 4 Installation commissioning and rep...

Страница 3: ...urity features and damage to property environment or people 1 2 Functions and intended uses The transducer CAL4 100ig provides isolation and duplication of analog current loop 4 20mA an auxiliary powe...

Страница 4: ...ssumed by the probabilistic estimation that it applies only to the useful lifetime of components Beyond this lifetime the probability of failure is increasing significantly with time The useful lifeti...

Страница 5: ...uts SIL2 SIL3 CAL4 100ig CAL4 100igM Green LED Power indicates that the device is cor rectly power on Blink if power is on protected mode under voltage supply overload or thermal protection mode Green...

Страница 6: ...ode the output load resistance must be between 0 ohms and 600 ohms Input wiring In 4 20mA passive current input between terminal in and GND for active transmitter In 4 20mA loop with transmitter suppl...

Страница 7: ...efined under paragraph proof interval 5 1 control steps Periodic proof allows detection of possible product internal failure and loop calibration environmental conditions and a minimum heating time of...

Страница 8: ...ls 4 20mA image of input Generally a transducer is taking place between a sensor and a protective equipment designated as Logic Safety Equipment Sensor transmitter CAL4 100ig PLC Logic Safety Equipmen...

Страница 9: ...reby in the FMEA analysis this state is considered as a not dangerous state Study hypotheses The failure rate of component are considered as constant for the all system life time The evaluation of the...

Страница 10: ...ion up to SIL3 according to standard IEC61508 2 2000 respecting the safety instructions specified in the safety manual The assessment of the safety critical and dangerous random failure give the follo...

Страница 11: ...of a device with a walkie talkie 5 W output power because it creates a electromagnetic field with an intensity greater than 10 V M for a distance of less than 50 cm 2 2 Power supply Observe the charac...

Страница 12: ...failure occurs if the measuring system doesn t switch into a define safe state or into an alarm signaling mode on process demand Appendix term and definitions SIL stands for Security Integrity Level w...

Отзывы: