background image

(800) 665-3760 

|

 www.logiquip.com 

|

 

[email protected]

USE & INSTALLATION GUIDE

 CAUTION

Read and understand all of the instructions and safety information  

in this document before assembling and installing this product.

Surgical Scrub Sinks

USE & INSTALLATION GUIDE

 

 

Содержание SS32

Страница 1: ...customersupport logiquip net USE INSTALLATION GUIDE CAUTION Read and understand all of the instructions and safety information in this document before assembling and installing this product Surgical Scrub Sinks USE INSTALLATION GUIDE ...

Страница 2: ...9 RECOMMENDED MOUNTING SPECIFICATIONS 10 12 CONNECTING THE DRAINPIPE 13 PLUMBING INSTALL INSTRUCTIONS 13 PREVENTATIVE MAINTENANCE 14 TROUBLESHOOTING 14 REPLACEMENT PARTS FOR SINK PLUMBING MANUAL AND INFRARED 15 PLUMBING ACCESS MANUAL SINKS 16 INFRARED IR CONTROLS 16 CLEANING INSTRUCTIONS 17 OPTIONAL IR TIMER ASSEMBLY 18 INSTALLING OPTIONAL ELECTRONIC SINK TIMER DISPLAY 18 TIMER OPERATION DISPLAY P...

Страница 3: ...f Activated Surgical Scrub Sink models SS32 1 Station Scrub Sink SS64 2 Station Scrub Sink SS96 3 Station Scrub Sink PURPOSE OF THIS GUIDE This user guide details the installation operation maintenance and cleaning of LogiQuip Surgical Scrub Sinks It also contains general specifications warnings and cautions PLEASE KEEP THIS GUIDE ...

Страница 4: ...r to attempting any repairs or servicing I Ic co on n D De es sc cr ri ip pt ti io on n Red triangle with an exclamation point indicate the potential for minor to severe injuries up to and including death to personnel Yellow triangle with an exclamation point indicate the potential for minor injury to personnel and damage to equipment Note The exclamation point will not be visible where only equip...

Страница 5: ... piping 4 Power Requirements For Sinks With Optional Infrared Sensor Operations 120 Volt 60 Hz single phase 3 0 amp GFIC protected electrical outlet by others 220 VAC 60 Hz single phase 1 5 amp To be installed per local building codes 5 Sink Weight 1 Station 130 lbs 2 Station 230 lbs 3 Station 320 lbs 6 Sink Certifications UL and cUL Certified California OSHPD pre approved when mounted on a struct...

Страница 6: ... Orientation Any position Set points shown are based on vertical inlet down position Required Filtration 50 microns or better Weight 0 66 lb 301 g Agency Approval CE Switch Ratings Max Resistive Load VA Volts Amps AC Amps DC 20 0 30 4 3 120 17 13 240 08 06 A A C C B B Pin Connections for Units with MS Receptacle T Ty yp pi ic ca al l W Wi ir ri in ng g D Di ia ag gr ra am m Piston Housing Spring S...

Страница 7: ...SCRUB SINKS USE INSTALLATION GUIDE www logiquip com 7 Fig 2 SS32 Single Basin Fig 3 SS64 Double Basin Fig 4 SS96 Triple Basin SINK DIMENSIONS SS32 SS64 SS96 MODELS ...

Страница 8: ... an exclamation point indicate the potential for minor injury to personnel and damage to equipment Note The exclamation point will not be visible where only equipment damage is present B Bu ur rn n H Ha az za ar rd d W Wa ar rn ni in ng gs s Yellow triangle with radiating lines indicate a potential burn injury to personnel E El le ec ct tr ri ic ca al l W Wa ar rn ni in ng gs s Yellow triangle wit...

Страница 9: ...ink Basin Soap Dispenser tubing is also included The dispenser spout should be installed before hanging the Sink 1 To install remove the bushing Fig 8 Item 3 shown in green 2 Feed the spout item 1 through the small hole at the top of the sink Fig 9 The nut item 2 should rest on top of the sink 3 Re install the bushing onto the spout from inside the cabinet Fig 10 4 Attach the soap tubing to the sp...

Страница 10: ...ED MOUNTING SPECIFICATIONS FOR SS32 1 STATION SCRUB SINK For the assembly drawing of In Line wall Carrier Mount S0001 see page 21 Fig 13 Z Bracket Mounting Locations SS32 Fig 14 In Line Wall Carrier Mount S0001 Fig 15 In Line Wall Carrier Mounting Locations SS32 ...

Страница 11: ...D MOUNTING SPECIFICATIONS FOR SS64 2 STATION SCRUB SINK For the assembly drawing for the In Line Wall Carrier Mount S0002 see page 22 Fig 17 In Line Wall Carrier Mount S0002 Fig 16 Z Bracket Mounting Locations SS64 Fig 18 In Line Wall Carrier Mounting Locations SS64 ...

Страница 12: ...MOUNTING SPECIFICATIONS FOR SS96 3 STATION SCRUB SINK For the assembly drawing for the In Line Wall Carrier Mount S0003 see page 23 Fig 20 In Line Wall Carrier Mount S0003 Fig 19 Z Bracket Mounting Locations SS96 Fig 21 In Line Wall Carrier Mounting Locations SS96 ...

Страница 13: ...ystem must be of materials with a construction capable of withstanding the high limit output temperatures of the water heating source I Ic co on n D De es sc cr ri ip pt ti io on n Red triangle with an exclamation point indicate the potential for minor to severe injuries up to and including death to personnel Yellow triangle with an exclamation point indicate the potential for minor injury to pers...

Страница 14: ...s Clogged cartridge 2 Flow of water is completely cut off Valves upstream from supply completely closed Failure of cold water supply pressure mixing value is designed to shut off on a cold water supply failure Checkstops completely closed 3 Flow low is untempered hot or cold water Valves Accumulation of time deposits in hot water pipes restricting the flow of hot water Thermostatic actuator failur...

Страница 15: ... MANUAL KNEE OPERATED AND INFRARED SELF ACTIVATED SINK PLUMBING Both plumbing configurations shown below indicate which parts are replaceable See the table below for replacement part numbers Fig 23 Infrared Self Activated Sink Plumbing Fig 22 Manual Knee Operated Sink Plumbing 8 I It te em m D De es sc cr ri ip pt ti io on n K Kn ne ee e O Op pe er ra at te ed d P Pa ar rt t I In nf fr ra ar re ed...

Страница 16: ...within the sensors range The sensors are equipped with a 2 second on off delay and no time out feature This prevents the sink from turning on when walking past at a normal pace and no timeout allows for an uninterrupted scrub SOAP I I PLUMBING ACCESS MANUAL KNEE OPERATED SINKS ONLY 1 Open the knee panel door by depressing the latch at the bottom of the panel door Fig 24 2 Swing the door fully open...

Страница 17: ...oved cleaner wipe down the entire exterior surface of the stainless steel sinks Using a damp lint free cloth with distilled water and a mild detergent wipe down the entire exterior surface of the stainless steel sinks 2 Let cleaned sinks air dry CLEANING DECALS OR PRINTED LABELS Use only distilled water and a mild detergent applied with a clean dry lint free cloth to clean decals or printed labels...

Страница 18: ...ter are provided on the housing Secure to sink top with the provided hex nuts 4 Thread the three 3 flow switch timer wires through the drilled hole on top of the sink Fig 32 circled in red 5 Connect the three 3 timer wires black red and orange to the timer read out terminal connections as shown in Fig 33 6 Program the timer as shown on page 19 Fig 30 IR Timer Assembly For IR Scrub Sinks Fig 31 Dri...

Страница 19: ...esired parameter appears on the screen Pressing the Next Key key will cause the leftmost digit of that value to begin to flash Use the Next and Down Key in combination to choose individual digits and change their value FRONT PANEL RESET ENABLE When active ON the time value when being displayed can be reset by pressing the Next Reset Key If set to OFF the time value can only be reset through the re...

Страница 20: ...itive Power Source Single or dual 3V Lithium battery typical 5 years life w single battery 10 years w dual batteries Ranges Resolution Seconds minutes to 1 10 hours to 1 10 hours minutes seconds Display 12mm high Supertwist LCD 7 digits Low Bat indicator Backlighting Green Illumination over whole viewable area Requires 10 to 28 VDC power source Dimensions Mounting See dimensions picture below Pane...

Страница 21: ...nds that the In line Wall Carrier Mount Assembly be tied into the existing wall support structure All applicable local and state building codes should be adhered to when mounting this unit 3 8 U BOLTS HDW0003 01 QTY 6 3 8 FLAT WASHER HDW0001 01 QTY 12 3 8 HEX NUT HDW0002 01 QTY 12 1 4 HEX NUT HDW0002 02 QTY 33 1 4 ALL THREAD ROD HDW0004 01 QTY 11 BOTTOM CARRIER PLATE SMS0052 01 QTY 1 TOP CARRIER P...

Страница 22: ...nds that the In line Wall Carrier Mount Assembly be tied into the existing wall support structure All applicable local and state building codes should be adhered to when mounting this unit SINK POST SMS0050 QTY 3 TOP CARRIER PLATE SMS0051 02 QTY 2 BOTTOM CARRIER PLATE SMS0052 02 QTY 1 1 4 ALL THREAD ROD HDW0004 01 QTY 12 1 4 HEX NUT HDW0002 02 QTY 36 3 8 HEX NUT HDW0002 01 QTY 18 3 8 FLAT WASHER H...

Страница 23: ...ends that the In line Wall Carrier Mount Assembly be tied into the existing wall support structure All applicable local and state building codes should be adhered to when mounting this unit SINK POST SMS0050 QTY 4 TOP CARRIER PLATE SMS0051 03 QTY 1 BOTTOM CARRIER PLATE SMS0052 03 QTY 1 1 4 ALL THREAD ROD HDW0004 01 QTY 14 1 4 HEX NUT HDW0002 02 QTY 42 3 8 HEX NUT HDW0002 01 QTY 24 3 8 FLAT WASHER ...

Страница 24: ... product Visit LogiQuip com Warranty for more details CUSTOMER SERVICE If you have any problems measuring for your Surgical Scrub Sink please contact our Customer Service Department at PHONE 800 665 3760 EMAIL CustomerSupport LogiQuip net ABOUT US Healthcare exclusive since 1992 LogiQuip s Inventory Management Solutions are designed for Healthcare Professionals looking for a better way to manage s...

Отзывы: