User Manual
LogicSP-2-1 / LogicSP-2-2
Page 20 of 29
1.
Press the DOWN key for less than 2 seconds to move to the currently calibrated lower
end position.
Alternatively, you can keep holding the DOWN key until the carrier stops in the current
lower end position.
2.
After the carrier stops, press DOWN again and keep holding the key for at least 5
seconds.
The carrier starts moving again at half speed. Keep holding the DOWN key until it
stops in the actual lower end position.
3.
The lower end position is now calibrated properly to the absolute lower end position.
Note:
This calibration procedure can be performed at any time while the box is in
normal (i.e. not SETUP or BYPASS) mode.
If the carrier already is in the absolute lower end position, the control box will not
attempt to move it any further downwards. In that case, the calibration procedure is
complete after you press the DOWN key for at least 5 seconds in step
2
.
4.3. Software-Dependent Functions
Note:
Prior to delivery, the LogicSP control box is programmed with a set of parameters
appropriate for the intended application.
The functions described in this section are available only if the parameter-set of your
control box activates them.
4.3.1.
Reset after Power On
After each power-on (e.g. connecting the power cord or after a power-outage), the control box
must be reset to make it fit for operation.
1.
After power-on, the UP key is locked (i.e. has no function).
2.
Press the DOWN key and hold it (i.e. perform the reset). The carrier will move
downwards at half speed until it stops in the absolute lower end position.
3.
The box is now reset properly and ready for normal operation.
4.3.2.
Low-Speed Area
This function performs a soft-stop before reaching the target position when the target is one
of:
•
The absolute upper end position.
•
The absolute lower end position.
•
The viewing position.
•
The heat-protection level.
4.3.3.
Plug Detection
The LogicSP motor control box is able to detect whether a motor is connected to a motor
interface or not.