Logic SP-18L Скачать руководство пользователя страница 8

8

- STAND-BY TIME

 is a function responsible for an interruption of the 

boiler operation when there is no fuel or the fuel feeder is blocked. 
Set time measured by the controller when the central heating temperature 
does not increase and remains within the range 0

º

C to 5

 º

C below the 

temperature in the central heating 

- SUPPORT PAUSE

- SUPPORT OPERATION

  both parameters concerns an operation in 

the summer mode. They are responsible for dispensing an appropriate 
amount of fuel in order to maintain a fire in the combustion chamber after 
heating up the domestic water.  There are two parameters that are inex-
tricably linked together. The pause is responsible for a break that is 
determined in minutes and the operation is determined as a time of ope-
ration of the feeder and fan. It is determined in seconds. These two para-
meters should be set so that the boiler does not go dead while on support. 

- FAN START-UP

 the device automatically adjusts an adequate rotational 

speed  of the fan, the function of airflow start-up is responsible for a start 
of the fan alone, it is based on adjusting an adequate start time determi-
ned in seconds.  The time should be set so that the fan reaches the ma-
l. 

0

0

CH    20

C z 55 C

0

0

HSV  20

C z 45 C

6. Installation menu

ENTERING THE INSTALLATION MENU 

– Simultaneously press and 

hold the keys (     )(     ).The keys (     ) (     ) are intended for scrolling 
through the menu. Entering next sub-menu and confirming a selected 
parameter, press the key (ENTER). Exiting the menu, press the key 
(EXIT)

 STAND-BY TIME

 STAND-BY TIME
                60 min

 STAND-BY TIME
                40 min

SP 

18L

 Manual                                                               

Содержание SP-18L

Страница 1: ...MICROPROCESSOR TEMPERATURE CONTROLLER SERVICE MANUAL 1 8 l ...

Страница 2: ...on hold ENTER button for 2 sec 2 LCD display 3 Indicator lights 4 Device control buttons 5 Airflow start up indicator 6 Central heating pump start up indicator 7 Hot service water pump start up indicator 8 Loader start up indicator 9 7A fuse 2 SP 18L Manual 4 3 5 6 7 8 9 1 2 ...

Страница 3: ...s The device has four keys intended for its operation The key ENTER switching on the device entering the menu saving a parameter The key EXIT monitoring the boiler exit without saving changes The key scrolling through the menu changing parameters adjusting the temperature of the central heating switching on off the summer mode The key scrolling through the menu changing parameters adjusting the te...

Страница 4: ...ng and domestic hot water temperature is screened on the LCD display the device starts to operate CHANGE OF MONITORING THE BOILER Change of reading after pressing the key ENTER Monitoring the central heating and domestic hot water temperature Current power in the boiler monitoring the valve operation CHANGE OF THE CENTRAL HEATING TEMPERATURE Press the key the central heating temperature is flashin...

Страница 5: ...mperature is flashing on the display Select the appropriate temperature confirm by pressing the key ENTER SUMMER MODE Press the key the central heating temperature is flashing on the display Press and hold the key release it when two horizontal lines appear on the display instead of the temperature Confirm by pressing the key ENTER SWITCHING ON THE DOMESTIC HOT WATER PUMP Press the key the domesti...

Страница 6: ...g domestic hot water DOMESTIC HOT WATER HYSTERESIS enables to adjust a delay of starting up the domestic hot water pump by a set number of degrees e g while 2ºC hysteresis and 50ºC set temperature the pump starts up when the domestic water temperature drops to 48ºC CENTRAL HEATING DOMESTIC HOT WATER PRIORITY the device controls two pumps central heating domestic hot water The function lets determi...

Страница 7: ... heating priority there is no possibility to adjust a domestic hot water temperature higher than the central heating temperature The central heating priority function is equipped with the following safety function lack of starting up the domestic hot water pump when the temperature of hot water storage container is higher than the temperature of the water jacket in the boiler FUEL TYPE switching t...

Страница 8: ...etermined in minutes and the operation is determined as a time of ope ration of the feeder and fan It is determined in seconds These two para meters should be set so that the boiler does not go dead while on support FAN START UP the device automatically adjusts an adequate rotational speed of the fan the function of airflow start up is responsible for a start of the fan alone it is based on adjust...

Страница 9: ...s on or switches off the pump depending on the temperature When the thermostat is connected to the adjuster yes should be pressed in the function An arrow will appear in the upper right corner on the display CAUTION the function should not be enabled when no indoor thermo stat connected WORM TEMPERATURE the function together with the sensor placed on the pipe of the feeder allows to protect the bo...

Страница 10: ...timal way The fuel amount should be determined on the basis of an observation if the fuel runs through as not fully burnt its amount is decreased but when the fuel runs out and the flame moves back to the feeder s pipe the amount is increased Changes should be made every hour since the last modi fication Every time it is determined if the fuel amount is adequate After finding a correct setting the...

Страница 11: ...hamber If the result of this modi fication is satisfying the test is finished by confirming with the key ENTER Caution While modifying the amount of the fuel transported changes should not be confirmed with the key Enter The amount of the transport ed fuel is modified when the parameter is modified on the display While testing there is also the parameter of the boiler temperature on the display ex...

Страница 12: ...elative air humidity 95 7 I insulation class 8 7 A fuse 9 Controller has got function preventing from premature freezing of o installation in case oftemperature decrease below 6 C circulation pump starts up automatically 10 Controller is equipped with secondary protection emergenc MAX POWER TEST 0 40 C 35 85 Central heating temperature Break time s Feeding time s 8 Use 1 Connect feeder of CH and H...

Страница 13: ...40 C 3 Perform installation in accordance with par 5 Use 4 Device should be installed and operated in accordance with rules of operating electrical devices Controller must not be exposed to water or to conditions causing steam condensation i e rapid changes of ambient temperature 5 In cases of controller misoperation first check a the fuse b connections stability and technical condition of coopera...

Страница 14: ...14 12 Electric parameters 1 Supply voltage 230 V 50 Hz 2 Power consumption no ratings 2 W 3 Output ratings blower 100 W loader 100 W pumps CH 100 W HSW 100 W SP 18L Manual ...

Страница 15: ...ul Moczydło 10a 30 698 Kraków tel 012 650 47 90 fax 012 650 47 91 e mail biuro electronics net pl Producent Electronics s c Paweł Wilgocki Piotr Wilgocki ...