8
- STAND-BY TIME
is a function responsible for an interruption of the
boiler operation when there is no fuel or the fuel feeder is blocked.
Set time measured by the controller when the central heating temperature
does not increase and remains within the range 0
º
C to 5
º
C below the
temperature in the central heating
- SUPPORT PAUSE
- SUPPORT OPERATION
both parameters concerns an operation in
the summer mode. They are responsible for dispensing an appropriate
amount of fuel in order to maintain a fire in the combustion chamber after
heating up the domestic water. There are two parameters that are inex-
tricably linked together. The pause is responsible for a break that is
determined in minutes and the operation is determined as a time of ope-
ration of the feeder and fan. It is determined in seconds. These two para-
meters should be set so that the boiler does not go dead while on support.
- FAN START-UP
the device automatically adjusts an adequate rotational
speed of the fan, the function of airflow start-up is responsible for a start
of the fan alone, it is based on adjusting an adequate start time determi-
ned in seconds. The time should be set so that the fan reaches the ma-
l.
0
0
CH 20
C z 55 C
0
0
HSV 20
C z 45 C
6. Installation menu
ENTERING THE INSTALLATION MENU
– Simultaneously press and
hold the keys ( )( ).The keys ( ) ( ) are intended for scrolling
through the menu. Entering next sub-menu and confirming a selected
parameter, press the key (ENTER). Exiting the menu, press the key
(EXIT)
STAND-BY TIME
STAND-BY TIME
60 min
STAND-BY TIME
40 min
SP
18L
Manual