38
User Manual
- Lodam Heat Pump Controller
Ver
. 1.0 - 11.10.10
Integration time:
Integration time for the heating PI-regulator.
Range 30 – 600 s
Default 240 s
Evaporator temp. min:
Limit for limitation function.
When the evaporator temperature is below
this value, the capacity is reduced to avoid
low pressure cut-out.
Range -70.0 – 0 °C
Default -70.0 °C
Installer - Ambient / Room temperature
compensation menu
The controller will try to maintain a stable room
temperature if heating is enabled.
A heating setpoint is calculated according to the
settings on this menu.
To maintain a comfortable room temperature the
controller can compensate for ambient temperature
and/or room temperature. This is achieved using
different compensation curves where the effect
of different ambient temperatures on the heating
setpoint can be set..
Please see section for a full description.
Temp control mode
:
With or without ambient / room temperature
compensation.
Options:
Min comp: No ambient compensation,
fixed setpoint
Ambient: With ambient compensation.
Room:
Only room compensation.
Amb+room: With ambient and room
compensation.
Room on/off: No ambient compensation.
Default: Min comp
Menu system
Ambient/room comp.
31-01-2010
09:31
Temp control mode
Ambient curve
Curve -20°C
Curve -10°C
Curve 0°C
Curve +10°C
Curve +20°C
Max room comp.
Min comp
Curve 1
45.0°C
42.0°C
39.0°C
33.0°C
30.0°C
5.0°C
Содержание LMC 320
Страница 1: ...LMC 320 Lodam Heat Pump Controller User Manual Ver 1 0 11 10 10 Heat Pump Controller ...
Страница 2: ......
Страница 6: ......
Страница 67: ...67 Ver 1 0 11 10 10 21 Notes Notes ...