HP+SP
SP+EH
HP+EH+SP: All sources are used according
to best energy efficiency
SP+HP-DUAL
Default: HP
Hot water set point:
Desired hot water temperature
Range 5 ° to 55 °C
Default 45 °C
Hot water neutral zone:
Neutral band from hot water setpoint.
Range 0.1 to 15.0 °C
Default 4.0 °C
Hot water capacity:
Use a specific capacity / speed when
producing hot water
(only for modulating control).
A frequency inverter controlled heatpump
may have a better energy efficiency at lower
speed than at max speed.
Range 10 – 100 %
Default 80 %
Hot water minimum:
If hot tap water temperature is below hot
water minimum for more then “Electrical
heat delay”, the electrical heater is turned
on.
If hot tap water temperature is above hot
water minimum, the heater is turned off.
Range 5 – 55 °C
Default 35 °C
Legionella interval:
Intervals between anti-Legionella operations.
Range 0 – 21 d
0 d = Off.
Default 7d