5
2.0
USER GUIDE
2.1
GENERAL REQUIREMENTS
This equipment must be installed by a competent person, registered with a H.S.E. approved
body. All installations must conform to the relevant Gas Safety and Building regulations. Health
& safety requirements must also be taken into account when installing any equipment.
A competent person must also undertake any alterations that require the gas train or flue system
to be broken.
Any interference with a sealed component is forbidden.
Failure to comply with the above may lead to prosecution.
Incorrect use may result in injury and will also invalidate the warranty
2.2
PROCEDURE FOR LIGHTING
1.
Ensure that the gas inlet appliance isolating valve is in the “off” position.
2.
Press the power rocker switch, positioned on the front of the appliance next to the control thermostat, to
bring the equipment on.
3.
The combustion fans should ramp up to full speed to purge the combustion chamber and then drop back
to half rate in order to light. As the gas inlet appliance isolating valve is closed, the controls should go to
a flame failure condition after four ignition attempts.
4.
If the above occurs correctly, open the gas inlet appliance isolating valve and reset the unit by
depressing the button on both upper and lower control panels.
5.
The combustion fans will repeat the pre-purge procedure and attempt to light. Once a flame is
established, the green ‘Burner On’ lamp, located below the digital display on the control panel, will
illuminate for each burner.
2.3
PROCEDURE FOR SHUTTING DOWN
To take the appliance out of service, the control thumbwheel on the upper display should be set to its minimum
value. If the appliance is operating when the thumbwheel is turned, wait for a period of 60 seconds to allow the
appliance to complete its combustion cycle. Once the appliance is in its standby mode, the main power rocker
switch can be turned to the off position. If the appliance in to be shut down for a long period of time, the gas
supply should be isolated at the gas inlet appliance isolating valve.
2.4
TEMPERATURE ADJUSTMENT PROCEDURE
The operating temperature of the boiler can be adjusted using the thumbwheel on the upper display of the
appliance control panel. The LED display on the panel will change to show the selected set point temperature.
2.5
MAINTENANCE
Service intervals should be determined during the first months of operation. Details of this procedure can be found
in the Installation Commissioning and Maintenance Instructions for the appliance. If these instructions are not
available, a copy should be obtained from Lochinvar’s website
www.lochinvar.ltd.uk
.
Even if the maintenance schedule for the storage vessel is determined to be less than annually, it is
important that all controls and safety features are checked for correct operation on an annual basis.
A competent person should check and ensure that the flue system, ventilation to the plant room, safety valve,
drain, pressure gauge etc. are in a serviceable and working condition and still comply with the relevant standards
and codes of practice, as detailed in the Installation, Commissioning and Maintenance Instructions.