1.0

 

 DISPLAY CODES 

 

The Lochinvar TTB has two three digit LED display on the front panel; these displays are used for setting the 

desired stored water temperature and for aiding diagnosis if the unit is not firing. 

 

1.1

 

DOUBLE NUMBERS 

 

If two numbers (e.g. 80) are displayed on the upper display, the water heater is operating normally and the value 

displayed is the setpoint of the water heater.  If two numbers (e.g. 80) are displayed on the lower display, the lower 

burner has a demand present and the value displayed is the setpoint for the burner. If the green LED below either 

display is illuminated, this signifies that the relevant burner is active. 

 

1.2

 

DIAGNOSTIC CODES 

 

When a code is permanently displayed (i.e. not flashing), on the upper or lower display, the relevant burner is 

waiting for a specific condition before beginning the firing sequence.  The following table gives a list of diagnostic 

codes, descriptions of the fault and solutions. 

 

Code  Fault

 

Solution 

A1 

System pressure too low 

Check system pressure 

A2 

Outlet temperature too high 

Wait for outlet temperature to drop 

A3 

External sensor temperature too high 

Wait for temperature to drop 

A5 

Anti-cycling time 

Wait for time period to expire 

A6 

Fan speed too high 

Wait for fan speed to drop 

A7 

Fan speed too low 

Wait for fan speed to increase 

A8 

Water flow through heater too low 

Wait for water flow to increase 

C1 

Flame simulation 

Wait for burner to extinguish 

C3 

High limit thermostat activated 

Wait for water temperature to drop 

E6 

Heater running in safe operation mode 

Contact qualified service personnel 

TABLE 1.1 

DIAGNOSTIC CODES 

 

1.3

 

ERROR CODES 

 

When a code is flashing in the upper or lower LED display, the relevant burner has locked out and will need to be 

reset by depressing the button on the water heater control panel.  The following table gives a list of error codes, 

descriptions of the causes.  If an error code does not reset or occurs again immediately, a competent person 

should be called to investigate and rectify the fault. 

 

Code  Fault

 

F0 

Short circuit in ionisation circuit 

F1 

Blocked condensate drain 

F2 

High temperature limit exceeded 

F4 

Wrong fan speed 

F5 

No flame after 5 ignition attempts 

F6 

Flame lost (4 times) during running 

E0

 

Outlet temperature sensor shorted or interrupted 

E2 

Inlet temperature sensor shorted or interrupted 

E5 

Flow temperature sensor shorted or interrupted 

E6 

Low water flow (A8) has occurred 4 times 

PP 

Parameters programmed into controller 

PE 

Incorrect parameters programmed into controller 

nc 

Heater control has failed 

NC 

Cascade communication has failed 

H1 

Gas valve wiring interrupted 

TABLE 1.2 

ERROR CODES 

 

 

 