Solar connections 

A solar thermal system consists of several components selected to work together to convert solar energy into hot water for 
various applications. A controller is used to turn on a pump when the fluid in the solar collectors is warmer than the water in the 
Thermal-Stor tank plus the differential. The pump will transport hot fluid from the collector to the heat exchanger and replace it 
with cooler fluid returning. The collectors, pump station and heat exchanger should be connected with supply and return piping 
that is insulated to minimize heat losses (FIG. 3-1, page 10). The system should be equipped with over-temperature and over-
pressure devices that prevent unsafe operating conditions. When multiple Thermal-Stor tanks are used, they should be connected 
in reverse-return arrangement (FIG. 3-2, page 10). This will help ensure that solar heated water is distributed evenly between the 
heat exchangers. Pressure drop and maximum operating values for the Thermal-Stor spherical heat exchanger are listed in Tables 
3A - 3C. 

Installation and commissioning must be carried out by a licensed contractor. Take appropriate safety measures when carrying 
out any installation work on the roof and observe all relevant accident prevention regulations. It is the installer’s responsibility to 
comply with the building and installation codes in effect and all regulations that apply to the operation of a solar hot water system.

Table 3B

Spherical Maximum Operating 

Conditions

Copper Heat 

Exchanger

Tank

Temperature

230°F

230°F

Pressure

145 psi

125 psi

Table 3C

Spherical Heat Exchanger Pressure Drop Chart

TSU150-200 /

SHX40000

TSU257-350 /

SHX40001

TSU423-504 /

SHX40002

TSU650-940 /

SHX40003
SHX40004

0

5

10

15

20

25

30

0 gpm

2 gpm

4 gpm

6 gpm

8 gpm

10 gpm

12 gpm

14 gpm

PRESSURE DROP

, PSI

FLOW RATE, GPM

30

25

20

15

10

5

0

0

2

4

6

8

10

12

14

TSU257-350/

SHX40001

TSU150-200/

SHX40000

TSU423-504/

SHX40002

TSU650-940/

SHX40003

SHX40004

Table 3A

Spherical Heat Exchanger

Pressure Drop Values

MODEL

SPHERICAL

MODEL

PRESSURE DROP PSI)

1

GPM

2

 GPM

4

GPM

6

GPM

8

GPM

10

GPM

12

GPM

14

GPM

TSU150

SHX40000

0.20

0.68

2.29

4.66

7.71

11.39 15.67 20.52

TSU200

TSU257

SHX40001

0.24

0.81

2.71

5.52

9.13

13.49 18.56 24.31

TSU350

TSU423

SHX40002

0.07

0.23

0.78

1.59

2.64

3.90

5.36

7.02

TSU504

TSU650

SHX40003

0.03

0.09

0.30

0.61

1.01

1.50

2.06

2.70

TSU752  

TSU940

SHX40004

0.03

0.09

0.30

0.61

1.01

1.50

2.06

2.70

       

Installation & Operation Manual

Содержание TSU150

Страница 1: ...ller service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING S...

Страница 2: ...ty damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage HAZARD DEFINITIONS 2 PLEASE READ BEFOR...

Страница 3: ...plate Consider piping and installation when determining appliance location Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee...

Страница 4: ...nger equipment life for the solar thermal system and heat source If piped correctly the buffer tank can also function as a hydraulic separator effectively separating the flow in the boiler loop from t...

Страница 5: ...TSU257 30 34 2 2 240 2875 TSU350 36 40 2 2 340 3775 TSU423 36 40 2 2 420 4650 TSU504 42 46 2 2 495 5475 TSU650 48 52 2 2 645 7050 TSU752 48 52 2 2 745 8100 TSU940 48 52 2 2 920 10000 AUXILIARY HEAT OU...

Страница 6: ...g Measurements From Floor Model A in B in C in D in E in F in G in H in I in O in P in TSU150 2 1 4 10 3 4 21 1 4 28 3 4 33 50 1 4 55 1 4 71 75 3 4 3 1 2 3 1 2 TSU200 2 1 4 11 1 4 22 3 4 33 38 1 2 55...

Страница 7: ...exchanger w tank Table 1E Tank with Spherical Measurements Model Spherical Model A in B in TSU150 SHX40000 44 1 2 28 TSU200 SHX40000 48 1 4 32 TSU257 SHX40001 50 1 4 34 TSU350 SHX40001 56 1 4 40 TSU4...

Страница 8: ...sen for the tank is capable of supporting the weight This tank must be placed where leakage from the relief valve leakage from the related piping or leakage from the tank or connections will not resul...

Страница 9: ...tor Take appropriate safety measures when carrying out any installation work on the roof and observe all relevant accident prevention regulations It is the installer s responsibility to comply with th...

Страница 10: ...AR PUMP STATION CONTROLLER TEMPERATURE GAUGE TYPICAL SPHERICAL HEAT EXCHANGER SOLAR SENSOR FILL AND FLUSH VALVE PRESSURE RELIEF VALVE IMG00095 TEMPERATURE GAUGE EXPANSION TANK Figure 3 2 Solar System...

Страница 11: ...the Thermal Stor buffer tank can be used to heat domestic water The hottest water is taken from the auxiliary heat supply and piped to the indirect heater where it is used to heat domestic potable wat...

Страница 12: ...in Section VIII Division 1 paragraph UG 125 a All pressure vessels within the scope of this division irrespective of size or pressure shall be provided with pressure relief devices in accordance with...

Страница 13: ...e tank so that water at a more constant temperature exits the mixing valve Always consult the mixing valve manufacturer s instructions and guidelines for correct piping and usage WARNING An anti scald...

Страница 14: ...y local codes NOTICE BACKFLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE AIR SEPARATOR LOW TEMP ZONE ZONE 1 ZONE 2 HIGH LOW RETURN TEMPERATURE GAUGE EXPANSION TANK PRESSURE RELIEF VALVE IMG00123...

Страница 15: ...RE GAUGE EXPANSION TANK MIXING VALVE PRESSURE RELIEF VALVE IMG00125 ZONE CIRCULATORS TYPICAL UNION Y STRAINER TYPICAL BOILER CIRCULATOR T P GAUGE DRAIN PRESSURE RELIEF VALVE CHECK VALVE SHOCK ARRESTOR...

Страница 16: ...IN PRESSURE RELIEF VALVE SHOCK ARRESTOR CHECK VALVE DOMESTIC HOT WATER DOMESTIC COLD WATER MAKE UP WATER SPACE HEAT SUPPLY AUXILIARY HEAT SUPPLY Y STRAINER TYPICAL BRAISED PLATE HEAT EXCHANGER Please...

Страница 17: ...meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE Figure 4 5 DHW Priority Piping Multiple Temperature Space Heating...

Страница 18: ...ion make sure that this system is properly maintained Annual service by a qualified service technician should include the following Any procedure required by local codes Verify system pressure Air ven...

Страница 19: ...section If antifreeze is used in the heat source water check the concentration Heat source water including additives must be non toxic having a toxicity rating or class of 1 as listed in the Clinical...

Страница 20: ...Revision Notes Revision A ECO C08886 initial release TSU I O Rev A 11 11 Printed in U S A...

Отзывы: