Lochinvar SOLUTION 260000 Скачать руководство пользователя страница 16

Installation & Service Manual

16

Masonry Chimney Installation

A masonry chimney must be properly sized for the
installation of a gas fired appliance.  Venting of an appliance
into a cold or oversized masonry chimney can result in
op 

er 

tion 

al and safety problems.  Exterior masonry

chim neys, with one or more sides exposed to cold out door
tem per a tures, are more likely to have venting problems. The
temperature of the flue gases from an appliance may not be
able to suf fi cient ly heat the ma son ry structure of the chim ney
to generate proper draft.  This will result in condensing of flue
gases, damage the masonry flue/tile, insufficient draft and
possible spill age of flue gases into an occupied living space.
Care ful ly in spect all chimney systems before installation.  If
there is any doubt about the sizing or condition of a masonry
chimney, it must be relined with a prop 

er 

ly sized and

approved chimney liner system.

Inspection of a  Masonry Chimney

A masonry chimney must be carefully inspected to determine
its suitability for the venting of flue gas es.  A clay tile lined
chimney must be structurally sound, straight and free of
misaligned tile, gaps between liner sections, missing sections
of liner or any signs of con den sate drainage at the breaching
or clean out.  If there is any doubt about the condition of a
masonry chimney, it must be relined.  An unlined masonry
chimney must not be used to vent flue gases from this appliance.
An unlined chimney must be relined with an approved
chimney liner system when a new appliance is be ing attached to
it. Metallic liner systems (Type “B” double wall or flexible or
rigid metallic liners) are recommended.  Consult with local
code officials to determine code requirements or the
advisability of using or relining a masonry chimney.

Sidewall Venting - Negative Draft

Figure 2-6_

Unit with Fan Assisted Venting

The in duced draft fan MUST also be equipped with a prov ing
switch, properly interlocked into the ap pli ance’s con trol circuit
to prove fan operation before the main burn ers are allowed to
fire. A vertical or sidewall vent termination for an induced draft
fan MUST be in stalled per the recommendations of the fan
manufacturer and provide proper clearances from any
combustion or  ventilation openings, win dows, doors or other
open ings into the building. All induced draft fan in stal la tions
must comply with local code requirements.

Fan Assisted Venting

A Power Venter Kit is available on Models 45,000 - 135,000
Btu/hr only (see Table 2B).

TABLE - 2B

VENT MATERIALS

Kit 

Number

Input

Btu/hr

Material

KIT3103

45,000

PVC Rated (CPVC Optional)

75,000

PVC Rated (CPVC Optional)

KIT3104

90,000

CPVC Rated 

135,000

CPVC Rated 

Minimum Vent Length = 12 Equivalent Feet* 

(ALL UNITS)

Maximum Vent Length = 25 Equivalent Feet* 

(ALL UNITS)

* Equivalent Feet:  90° Elbow = 5 Feet

45° Elbow = 3 Feet

2  

Venting

This appliance is NOT approved for sidewall venting with
the negative draft venting system as shipped from the
factory.   An induced draft fan MUST be used if the
installation requires that the flue gases be vented out a
sidewall unless a power venter is used, see 

Fan Assisted

Venting

.  A properly sized and in stalled induced draft fan

may also be used to vent the flue gases ver ti cal ly if required
by jobsite re stric tions.  The induced draft fan must be listed
by a nationally recognized test agency, be properly sized and
installed per the rec om men da tions of the   in duced draft fan
manufacturer and meet local code requirements. Use care to
ensure that the me chan i cal ly supplied draft does not exceed
the range of a negative 0.02 to 0.05 inches water column to
ensure proper operation. If draft exceeds the spec i fied range,
the fan must be adjusted or the installation of  a baro met ric
damper in the flue may be required to prop er ly control draft.
An induced draft fan MUST be interlocked into the
appliance’s control circuit to start when the appliance calls
for heat.

Содержание SOLUTION 260000

Страница 1: ...nd servicing of the appliance It is strongly recommended that this manual be reviewed completely before proceeding with an installation Perform steps in the order given Failure to comply could result...

Страница 2: ...arances 15 Masonry Chimney Installation 16 Inspection of a Masonry Chimney 16 Automatic Vent Damper 17 3 GAS CONNECTIONS Gas Supply 18 Gas Pressure Test 18 Gas Connection 18 Gas Piping 19 Gas Manifold...

Страница 3: ...ed by too much water velocity through the tubes and is not covered by the manufacturer s warranty see Boiler Flow Rates and Temperature Rise for flow requirements Checking equipment Upon receiving equ...

Страница 4: ...ll be installed in accordance with those installation regulations in force in the local area where the installation is to be made These regulations shall be carefully followed in all cases Authorities...

Страница 5: ...tions above 2000 feet elevation 5 Ratings have been confirmed by the Hydronics Institute Section of AHRI Maximum allowed working pressure is located on the rating plate NOTICE Installation Service Man...

Страница 6: ...es adequate flow to operate the unit 13 Pilot not shown The pilot is a spark ignition device used to light a pilot flame which in turn is used to light the main burners 14 Pump relay The pump relay en...

Страница 7: ...els 45 000 90 000 Left Side inside unit Models 45 000 90 000 Right Side inside unit Models 45 000 90 000 Rear View The Solution How it works continued 11 22 14 23 21 25 9 16 7 18 12 6 24 1 10 19 8 3 1...

Страница 8: ...rks Models 135 000 260 000 Btu hr Left Side inside unit Models 135 000 260 000 Btu hr Right Side inside unit Models 135 000 260 000 Btu hr Rear View Models 135 000 260 000 Btu hr Front View 10 1 19 3...

Страница 9: ...d in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have...

Страница 10: ...s see FIG 1 3 a Combustion air opening with a minimum free area of one square inch per 4000 Btu hr input 5 5 cm2 per kW This opening must be located within 12 30 cm of the floor b Ventilation air open...

Страница 11: ...e Particular care should be taken where exhaust fans attic fans clothes dryers compressors air handling units etc may take away air from the appliance The combustion air supply must be completely free...

Страница 12: ...feet per 1 000 Btu hr input Buildings MUST NOT be of Tight Construction For buildings of Tight Construction provide air openings into the building from outside No combustion air openings are needed wh...

Страница 13: ...ntional Negative Draft Vertical Venting TABLE 2A VENT PIPE SIZES Input Btu hr Flue Size 45 000 4 75 000 5 90 000 5 135 000 6 180 000 7 215 000 7 260 000 8 On a conventionally vented negative draft app...

Страница 14: ...and other deficiencies which could cause an unsafe condition c Insofar as is practical close all building doors and windows and all doors between the space in which the appliances remaining connected...

Страница 15: ...from or 1 foot 30cm above any door window or gravity air inlet into any building Do not terminate the vent in a window well stairwell alcove courtyard or other recessed area The vent can not terminat...

Страница 16: ...enting The induced draft fan MUST also be equipped with a proving switch properly interlocked into the appliance s control circuit to prove fan operation before the main burners are allowed to fire A...

Страница 17: ...s condition such as an explosion or carbon monoxide poisoning could result The damper position indicator must be in a visible location with access for service following installation The damper must be...

Страница 18: ...l Gas LP Gas 45 000 3 5 10 0 9 2 5 75 000 2 4 7 0 9 2 5 90 000 180 000 3 5 10 0 9 2 5 215 000 260 000 3 5 10 0 9 2 5 Gas Pressure Test 1 The appliance must be disconnected from the gas supply piping s...

Страница 19: ...ons must be made with pipe joint compound resistant to the action of liquefied petroleum and natural gas All piping must comply with local codes Tubing installations must comply with approved standard...

Страница 20: ...c for Natural gas models and 10 w c for L P gas models 4 Remove the pressure regulator adjustment cap screw on the gas valve See FIG 3 3 for location 5 Turn the power ON at the main disconnect switch...

Страница 21: ...de proper gas pressure to the control 11 If the gas supply pressure is within the specified range proceed with the following steps to return the appliance to service 12 Turn the power OFF at the main...

Страница 22: ...ter complies with the safety code requirements of CSD 1 CF 190 a as shipped from the manufacturer without the installation of additional vent lines Two Stage Burner Control System The 45 000 thru 260...

Страница 23: ...ter Flow Switch Top Connections A water flow switch is available as a factory supplied option on all heating boilers see FIG 4 2 The flow switch should be wired between terminals X and B Remove the ju...

Страница 24: ...boiler and on the suction side of the pump 6 Support all water piping Placing the Boiler in Operation Filling the System All air must be purged from the system for proper operation An air scoop and a...

Страница 25: ...t hd 45 000 36 900 7 4 0 6 3 7 0 2 2 5 0 2 1 9 0 2 75 000 61 500 12 3 1 3 6 2 0 4 4 1 0 3 3 1 0 2 90 000 73 800 14 9 1 4 7 4 0 5 5 0 0 3 3 7 0 2 135 000 110 700 22 3 3 2 11 1 1 2 7 4 0 6 5 6 0 3 180 0...

Страница 26: ...his is a low mass high efficiency hot water boiler which must have adequate flow for quiet efficient operation The boiler circulating pump must be field supplied The boiler circulator pump must operat...

Страница 27: ...ance loop is dedicated to the unit and does not affect the building s system or primary secondary flow characteristics and will not circulate the building It is acceptable to remove the performance lo...

Страница 28: ...f combustion from condensing in most installations The bypass should be fully sized with a balancing valve to allow for proper adjustment A valve must also be provided on the boiler discharge after th...

Страница 29: ...SION TANK BALL VALVE TYPICAL UNION TYPICAL PRESSURE RELIEF VALVE DRAIN POINT TYPICAL MAKE UP WATER FROM SYSTEM 12 NOT TO EXCEED APART BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR...

Страница 30: ...SSURE GAUGE AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL UNION TYPICAL PRESSURE RELIEF VALVE DRAIN POINT TYPICAL MAKE UP WATER FROM SYSTEM 12 NOT TO EXCEED APART BOILER CIRCULATOR SYSTEM CIRCULATOR...

Страница 31: ...SURE RELIEF VALVE DRAIN POINT TYPICAL MAKEUP WATER HOT WATER OUT BOILER CIRCULATOR BACKFLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE EXPANSION TANK ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE CIRCULATORS...

Страница 32: ...E AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL UNION TYPICAL PRESSURE RELIEF VALVE MAKE UP WATER FROM SYSTEM SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN Y STRAINER RECOMMENDED Figure 4 7...

Страница 33: ...RATOR EXPANSION TANK BALL VALVE TYPICAL UNION TYPICAL PRESSURE RELIEF VALVE MAKE UP WATER FROM SYSTEM BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN Y STRAINER RECOMMENDED 3...

Страница 34: ...re after each set point adjustment to ensure proper operation Room Thermostat or Remote Thermostat Connection to Terminal Strip A room thermostat or remote temperature control may be connected to the...

Страница 35: ...E The temperature controller is pre set at the factory with test settings You may need to adjust the settings to meet your specific needs WARNING Return water temperatures must not be less than 140 F...

Страница 36: ...the temperature control shuts the unit off If the High Fire Offset knob is set to 0 or 1 the delay will be 10 seconds if set to 2 or above the delay will be 120 seconds Boiler Application Standard boi...

Страница 37: ...e temperature sensor wiring near welding equipment 5 Make sure good mechanical connections are made to the sensor any interconnecting wiring and the controller 6 Do not mount sensor with leadwire end...

Страница 38: ...s control over the reset ratio to be used during Outdoor Air Reset The allowable ratios are as low as 0 5 1 or as high as 1 5 1 Selecting the 0 5 1 ratio will increase the set point 0 5 for every 1 0...

Страница 39: ...es are located in the controls compartment and in the relief opening of the boiler s built in draft hood Each switch has a red reset button In the event the system has actuated to shut off the main bu...

Страница 40: ...nnections are tight and the appliance and piping system have been properly filled 5 Ensure that discharge from the relief valve has been piped to a floor drain 6 Verify that properly sized combustion...

Страница 41: ...sired setting 11 Re install the control panel door 12 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier To Turn Of...

Страница 42: ...the front header and one from the outlet side of the front header on the heat exchanger Blow all water out of the heat exchanger e Drain pump and piping Freeze Protection for a Heating Boiler System...

Страница 43: ...s Perform start up checkout and performance verification per Section 6 Start up If combustion or performance indicate need Clean heat exchanger Remove and wash burners ANNUAL START UP Owner maintenanc...

Страница 44: ...water may also cause severe property damage 1 Inspect all water and gas piping and verify to be leak free 2 Look for signs of leaking lines and correct any problems found 3 Check gas line using the p...

Страница 45: ...unless the valve and its components are physically removed and inspected This inspection must only be conducted by a plumbing contractor or authorized inspection agency not by the owner Failure to re...

Страница 46: ...injection pressure into the venturi of the burners The burners do not have an adjustable air shutter Adequate combustion air must be supplied to the room where the appliance is installed to ensure pro...

Страница 47: ...ht black smudge is normal with some types of gases If abnormal soot deposits are present the heat exchanger must be cleaned and the cause of the soot problem corrected Proceed as follows k Remove soot...

Страница 48: ...o be sure that no sediment or scale accumulates on the heat transfer surfaces Inspection plugs are located at both ends of the heat exchanger Inspection plugs should be removed and tubes inspected at...

Страница 49: ...ess the reset button Yes Is there 24 VAC tan wire on the 4 pin connector plug on the temperature controller Yes Check each of the following for an open X and B on the terminal strip purple and gray wi...

Страница 50: ...50 Installation Service Manual Schematic Diagram M9 Unit 45 000 260 000 Btu hr Models Wiring Diagram M9 Unit 45 000 260 000 Btu hr Models 9 Diagrams...

Страница 51: ...51 Notes...

Страница 52: ...elease Revision B ECO C06868 update the pressure drop chart Table 4C to reflect the correct models and change out the reference to the two blues wires to SYS TANK contacts under System Sensor on page...

Отзывы: