Designer’s Guide / Power-fin Water Heater
Chapter 3 – Gas Supply
Lochinvar products are designed with the concept of flame control. We develop combustion
systems that tightly control the flow of air and gas to deliver a clean and efficient burn. In
Chapters 1 and 2, we showed the various methods to deliver an ample quantity of air to the
appliance. In Chapter 3, we discuss delivering a steady and reliable supply of gas to the
appliance.
The key to the gas supply is sizing the gas line properly. The Power-fin will require less than a
half a pound of pressure. The following Sizing Chart is based on less than ½ pound of pressure
or less than 14 inches of pressure. The table is derived from the ANSI Z223.1, the National Fuel
Gas Code.
Simply calculate the total linear feet of straight gas pipe. Figure each elbow as equal to five
straight feet of pipe. Working down the column that matches your pipe length, find the value
GREATER THAN the total Btu/hr input of the water heater or water heaters. This will identify the
minimum nominal iron pipe size.
GAS PIPE SIZING CHART
Nominal
Iron
Length of Pipe in Straight Feet
Pipe
Size
10
20
30
40
50
60
70
80
90
100
125
150
175
200
3/4"
369
256
205
174
155
141
128
121
113
106
95
86
79
74
1"
697
477
384
328
292
267
246
256
210
200
179
164
149
138
1 1/4"
1,400
974
789
677
595
543
502
472
441
410
369
333
308
287
1 1/2"
2,150
1,500
1,210
1,020
923
830
769
707
666
636
564
513
472
441
2"
4,100
2,820
2,260
1,950
1,720
1,560 1,440 1,330 1,250 1,180 1,100
974
871
820
2 1/2"
6,460
4,460
3,610
3,100
2,720
2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
3"
11,200
7,900
6,400
5,400
4,870
4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
4"
23,500
16,100 13,100
11,100 10,000
9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
The Power-fin features a Negative-Regulation or Neg-Reg gas
combustion system. The gas is introduced upstream of the
combustion blower. As the blower draws air in, the negative
pressure on the inlet of the blower pulls the gas from the gas
valve. The gas/air mixture is pushed through the blower into the
burner. The gas/air mixture filters through the ceramic burner
mesh and is ignited by the Hot Surface Igniter.
On full fire, a crisp blue flame rises off the surface of the burner.
As demand decreases, the operating control reduces the blower
speed. The flame is reduced and touches the burner surface.
The ceramic burner material is designed to burn infra-red safely without being damaged by direct
contact of the flame. Even at this reduced Btu/hr input, the gas/air mixture is balanced to provide
clean, efficient combustion.