background image

 

 

13 

 

LIFTING  

 

 

Always exercise extreme caution when lifting to avoid damage, lift from underneath on a pallet or base if 

fitted 

Avoid lifting from any of the pipework, controller, or valves 

 

 

WATER CONNECTIONS 

 

 

Do not weld near to or on the heat exchanger or associated components. 

 

Use two wrenches when attaching unions to the domestic water circuit threaded stub connections. One wrench to be used to tighten 

the union & the other to prevent the stub end from rotating 

 this avoids damage to the gasket inside the unit that seals against the 

back on the stub connection. Use a none hardening thread sealant for best results. Threads are BS21 

 taper, male. It is necessary 

to support the secondary pump and the pipe work as the heat exchanger connections are not designed to accept any weight being 

imposed upon them. 

To avoid damage to the unit, to prevent failure and to ease maintenance, we recommend the following: 

 

Pipe-work - fully support to avoid weight/forces acting upon the unit / connections. 

 

The fitting of flexible couplings if the pipe work is subject to vibration. 

 

The pipe work is completely flushed before attaching to exchanger. The exchanger acts as an effective filter and will 

become blocked if pipe-work debris can enter the plate pack. 

 

The fitting of suitable vents, isolation valves & drains. To allow servicing of the package without complete system draining 

appropriate isolation valves should be fitted. 

 

The fitting of non-return valves where appropriate 

 

The fitting of suitable sized pressure relief valves in the pipe work on both circuits (essential safety requirement). 

 

 

 

The LOKE must be installed as per the schematics 

here,

 failure to include all  necessary valves etc. Will 

invalidate the warranty and could lead to a dangerous situation on site. 

 

 

UN-VENTED SYSTEM ARRANGEMENT 

 

If the LOKE is to be used in an unvented arrangement, the system should follow the guidance given in 

BS6700

 and must comply 

with 

The Building Regulations: Part G3 in England and Wales, P5 in Northern Ireland and P3 in Scotland.

  A kit of components 

that have been suitably sized for the unvented or boosted operation of the appliance is available from Lochinvar Limited.  For further 

information, see below. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание LOKE8-100

Страница 1: ...75 LOKE8 100 LOKE8 125 LOKE8 150 LOKE8 175 LOKE8 200 LOKE8 225 LOKE8 250 LOKE Instantaneous packaged plate heat exchanger Installation Commissioning Maintenance and User instructions installation man...

Страница 2: ...2 BLANK PAGE...

Страница 3: ...TY 12 LOCATION 12 LIFTING 13 WATER CONNECTIONS 13 UN VENTED SYSTEM ARRANGEMENT 13 STANDARD UN VENTEDKITS 14 CIRCULATING PUMPS 14 CONTROL 14 OVERHEAT PROTECTION 14 9 0 SCHEMATICS 15 KEY FOR SCHEMATICS...

Страница 4: ...with Models LOKE8 50 to LOKE8 150 o COLK3503 for use with Models LOKE 175 to LOKE8 250 Direct storage vessels with matched primary circulation pumps For units being installed with a storage vessel con...

Страница 5: ...damage caused by inaccurately following these installation instructions Only original parts may be used when carrying out any repair or service work This appliance is not intended for use by persons i...

Страница 6: ...230V 1Ph 50hz Protection class II Torque 6Nm Power consumption 230v AC 10VA Connection mounting set External thread Running time at maximum speed 30seconds Supplied parts Actuator with pre assembled s...

Страница 7: ...Secondary Side Inlet Temperature C Varies Depending on Demand 10 At Full Demand Outlet Temperature C 65 65 65 65 65 Fluid Flow Rate litres second 0 22 0 33 0 43 0 54 0 65 Fluid type Water Water Water...

Страница 8: ...y Side Inlet Temperature C Varies Depending on Demand 10 At Full Demand Outlet Temperature C 65 65 65 65 Fluid Flow Rate litres second 0 76 0 87 0 98 1 09 Fluid type Water Water Water Water pressure d...

Страница 9: ...9 7 0 DIMENSIONS AND CLEARANCE Unit Dimension A Total Height mm 835 B Depth mm 710 C Width mm 196 DIMENSIONS OF UNIT WITHOUT OPTIONAL BASE...

Страница 10: ...10 Unit Dimension A Total Height mm 965 B Depth mm 800 C Width mm 620 D Base Depth mm 130 DIMENSIONS OF UNIT WITH OPTIONAL BASE FITTED...

Страница 11: ...h optional base fitted if unit does not have optional base clearances are from side of plate pack Side clearances can be reduced but the unit may need to be removed in the future if the plate pack req...

Страница 12: ...G01Guidance on safe operation of Water Heaters Manufacturer s notes must not be taken in any way as overriding statutory obligations WATER QUALITY Water supply quality may adversely affect the efficie...

Страница 13: ...tting of flexible couplings if the pipe work is subject to vibration The pipe work is completely flushed before attaching to exchanger The exchanger acts as an effective filter and will become blocked...

Страница 14: ...d overcome the plate pressure drop details can be found in the technical data table CONTROL The controller is factory fitted to the three port valve OVERHEAT PROTECTION Due to its simple design the LO...

Страница 15: ...5 In all cases where information is provided the customer must assess and manage risks associated with the technical information and advice provided SYMBOL DESCRIPTION IV ISOLATION VALVE LSV LOCKSHIEL...

Страница 16: ...16 Schematic LOKE instantaneous installation...

Страница 17: ...17 Schematic LOKE with storage vessel schematic...

Страница 18: ...n of at least 3mm in all poles should be sited close to the equipment and must only serve that equipment The double pole switch must be readily accessible under all conditions The controller fitted to...

Страница 19: ...t The actuator should slowly rotate until the valve is at the fully diverting position and then stop Now lower the temperature below ambient and the actuator should rotate anti clockwise and stop at a...

Страница 20: ...r will not cause any damage or injury 4 Close the cold water inlet valve from the header tank or unvented kit unit to water heater system 5 Open the drain valve 6 Working systematically from the highe...

Страница 21: ...o assemble the plate you will require the plate sequencing sheet this should be in the paperwork supplied with the Plate heat exchanger If this cannot be found contact Lochinvar Technical support befo...

Страница 22: ...skewing the frame plates by more than 10mm 4 Tightening is complete when the distance between the inside faces of the two frame plates is within the compression length maximum and minimum dimensions...

Страница 23: ...23 12 7 1 EXAMPLES OF GASKET AND PLATE TYPES...

Страница 24: ...the manual 2 Flange gaskets leaking check replace 3 Crack in weld at joint Dye Pen Check and repair remove plates out of heat exchanger before welding 4 Cross contamination Check all plates for crack...