42
Figure 7-3
Pressure Drop vs. Flow
Table 7A
Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F
0
10
20
30
40
50
60
0
10
20
30
40
50
60
70
80
90
100
PR
ES
SU
RE
DR
OP
(F
T.
HD
)
FLOW RATE (GPM)
PRESSURE DROP VS FLOW
(HEAT EXCHANGER ONLY)
400
500
650
800
1000
TEMPERATURE RISE APPLICATIONS
Model
MINIMUM
PIPE
SIZE
20°F
25°F
30°F
35°F
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
400
2"
38
10
30
7
25
5
22
4
500
2"
48
14
38
12
32
9
27
8
650
2"
62
16
50
11
41
9
36
7
800
2"
76
17
61
13
51
10
44
9
1000
2 1/2"
96
18
76
11
64
8
54
6
7
Hydronic piping
Installation & Operation Manual