SMART SYSTEM control module 

(continued)

Set space heating operation

Determine controlling sensor

For space heating systems, the temperature control can be 
based on one of three sensors; the inlet, outlet, or system  
supply sensor.  The SMART SYSTEM control is programmed 
at the factory to control the temperature of the outlet 
sensor.  The control will automatically switch to the system 
supply sensor once it is connected.  If it is desired to base 
the temperature control on the inlet sensor, the appropriate 
parameter must be changed in the control.  See the Knight 
Fire Tube Boiler Service Manual for a detailed explanation of 
this procedure.

Verify space heat circulator mode

The Space Heating Mode controls both the system pump 
(if connected), and the boiler pump.  When the SMART 
SYSTEM control receives a space heating call for heat, it 
turns on the system pump.  If the boiler is not heating an 
indirect DHW (Domestic Hot Water) tank, and the set 
point is not met, it also turns on the boiler pump.  After the 
space heating call for heat ends, the system pump continues 
to run for a short period of time.  The system pump can be 
programmed to run continuously, except during outdoor 
shutdown.  If the boiler pump was running, it continues to 
run for a short period of time as well.  These pump delays 
are factory set to 30 seconds.  If different delays are desired, 
the appropriate parameters in the control must be changed.  
See the Knight Fire Tube Boiler Service Manual for a detailed 
explanation of this procedure. 

Adjust set point temperature(s)

Please note that the brackets ([]) denote 
screen status.

 NOTICE

The NAVIGATION dial may be used during normal 
operation to adjust the space heating and tank set point 
temperatures.  

1.  From the Status Screen press the NAVIGATION dial.
2.  Turn the NAVIGATION dial counterclockwise to select 
 

the appropriate set point.

3.  Press the NAVIGATION dial to adjust the temperature.
4.  Once the desired temperature is displayed, press the 
 

RIGHT SELECT [SAVE] key.

5.  If necessary repeat Steps 3 and 4 to make adjustments to 
 

additional set points.

6.  Press the RIGHT SELECT [HOME[ key to upload the 
 changes.
7.  If the RIGHT SELECT [SAVE] key is not pressed, the 
 

new settings will be discarded.

Set domestic hot water (DHW) operation

Verify DHW mode

There are two (2) modes of operation for DHW.  In Normal 
Mode, when a DHW demand begins, the control will start 
the DHW pump, turn off the boiler pump (if running), and 
modulate to bring the outlet temperature to the DHW boiler 
set point.  The maximum firing rate may be limited in this 
mode if desired.

In Zone Mode it is assumed that the indirect DHW tank is 
piped as a zone on the primary loop.  When a DHW demand 
begins, the control will turn on the DHW pump output, and 
raise the system temperature set point to the DHW boiler set 
point (if higher).  The boiler pump will be turned on.  The 
system pump may be forced on, forced off, or not changed, 
depending on the System Pump Mode selected (reference the 
Knight Fire Tube Service Manual for details).  In this mode, 
any low temperature zones (such as radiant heating) may 
need additional controls to limit the water temperature sent 
to those zones.

Set DHW boiler target temperature

When in the DHW Mode, the control will modulate to 
maintain the boiler outlet temperature or system supply 
temperature to a set point.  This set point is set at the factory 
to 180°F.  If a different set point is desired, the appropriate 
parameter in the control must be changed.  See the Knight 
Fire Tube Boiler Service Manual for a detailed explanation of 
this procedure.

Set maximum DHW fan speed

If the rated input of the indirect tank is less than the 
maximum output of the boiler, change the maximum DHW 
fan speed setting to limit the boiler output accordingly, see 
the Knight Fire Tube Boiler Service Manual for a detailed 
explanation of this procedure.

The SMART SYSTEM control has a built-in clock that it 
uses for its night setback feature and for logging events.  This 
clock must be set when the boiler is installed, and anytime 
the boiler has been powered off for more than 4 hours.  Use 
the following procedure to set the clock:

1.  Press and hold the LEFT SELECT [MENU] key for at 
 

least 5 seconds.

2. The display changes to read [PASSWORD], 
 

with four (4) zeros below it.

3.  Press the RIGHT SELECT [SAVE] key.
4.  The display will then show a menu with the time and 
 

date and temperature unit.

5.  Press the NAVIGATION dial twice.
6.  Turn the NAVIGATION dial to adjust the hours.  Press 
 

the NAVIGATION dial.

Please note that the brackets ([]) denote 
screen status.

 NOTICE

Set clock

        

          User’s Information Manual

Содержание Knight 285

Страница 1: ...flammable vapors are likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your ga...

Страница 2: ...avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage Contents...

Страница 3: ...ler if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has been under water must be replaced Boiler wat...

Страница 4: ...abrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction...

Страница 5: ...rn water temperature If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheel Owner maintenance see pages 6 8 for detail...

Страница 6: ...Products containing chlorine or fluorine if allowed to contaminate the boiler intake air will cause acidic condensate in the boiler This will cause significant damage to the boiler if allowed to conti...

Страница 7: ...CTION FROM CONDENSATE VENT ON BOILER FROM CONDENSATE DRAIN ON BOILER DIR 2000507910 00 1 2 PVC UNION FIELD PROVIDED 1 2 PVC TEE RECOMMENDED FIELD SUPPLIED NEUTRALIZER KIT FLOOR DRAIN OR DRAIN PAN User...

Страница 8: ...e technician to inspect the valve and system 4 If water does not flow from the valve when you lift the lever completely the valve or discharge line may be blocked Immediately shut down the boiler foll...

Страница 9: ...9 3 Operating instructions User s Information Manual...

Страница 10: ...ture units can also be changed see page 11 Installer Most parameters are available only to the installer accessible by entering the installer password see the Knight Fire Tube Boiler Service Manual Sa...

Страница 11: ...ngs will be discarded Set domestic hot water DHW operation Verify DHW mode There are two 2 modes of operation for DHW In Normal Mode when a DHW demand begins the control will start the DHW pump turn o...

Страница 12: ...the minutes Press the NAVIGATION dial 8 TurntheNAVIGATIONdialtoadjustthemonth Pressthe NAVIGATION dial 9 Turn the NAVIGATION dial to adjust the date Press the NAVIGATION dial 10 Turn the NAVIGATION d...

Страница 13: ...The call for heat has been satisfied and the unit runs the fan for an additional postpurge period to clear the combustion chamber and vent system of residual flue products SHUTDOWN The unit has been p...

Страница 14: ...mperature of Loop 3 reported by the MTLC control I O SCREEN a GAS PRESS SW The state of the gas pressure switch b FLOW SW The state of the flow switch c LOUVER RELAY The state of the louver relay outp...

Страница 15: ...the Home Status Screen and upload any changes EXIT Press the LEFT SELECT key to go back to the previous Menu Screen YES Press the LEFT SELECT key to accept current operation SKIP Press the LEFT SELECT...

Страница 16: ...Revision Notes Revision A Change 500001290 initial release MM 100267830_DIR 2000508772 Rev A 10 15...