Service

18

Service Manual

1  

Service 

SH Differential

The SH differential sets how many degrees below the turn off
temperature the temperature has to go before the boiler will
turn on.  This parameter can only be changed by the installer
by accessing parameter 

B5

.  The temperature range of this

parameter is 0°F to 86°F.  The default value is 20°F.

C: Data logging

Hours running SH

The hours running SH parameter shows the total number of
hours the boiler has been in the SH firing position.  This
parameter can be viewed by the user and the installer by
accessing parameter 

C1

.

Hours running DHW

The hours running DHW parameter shows the total number
of hours the boiler has been in the DHW firing position.  This
parameter can be viewed by the user and the installer by
accessing parameter 

C2

.

Ignition attempts

The ignition attempts parameter shows the total number of
times the boiler has attempted to fire.  This parameter can be
viewed by the user and the installer by accessing parameter

C3

.

Show last 10 errors

The control will log the 10 most current errors with the date
and time the error occurred.  This parameter can be viewed
by the user and the installer by accessing parameter 

C4

.

D: Functions

Reset last 10 errors

The reset last 10 errors parameter allows the error counter to
be reset to 0.  This parameter can only be cleared by the
installer by accessing parameter 

D1

.  Once accessed, press the

RESET key to clear the counter.

Service mode delay

By pressing the pin button on the front of the display for five
(5) seconds, the control will be placed in Service Mode.  This
will override all other heat demands.  The Service Mode
allows the installer to set the unit to either maximum firing
rate or minimum firing rate for the purpose of combustion
analysis.  The delay sets the length of time the boiler will stay
in the Service Mode if no keys have been pressed before going
back to its original state.  This parameter can only be changed
by the installer by accessing parameter 

D2

.  The time range of

this parameter is 0 to 40 minutes.  The default value is
20 minutes.

E: DHW settings

DHW boiler set point

When a DHW call for heat becomes active, the control will
use the DHW boiler set point to determine the firing rate of
the boiler based on the actual water temperature.  This
parameter can be changed by the installer by accessing
parameter 

E1

.  The temperature range of this parameter is

50°F to 190°F.  The default value is 180°F.

SH/DHW switching time

The SH/DHW switching time parameter sets the length of
time the control will stay in DHW Mode when a SH call has
been received.  After this time period has expired the control
will revert to SH Mode.  If a DHW call is still active the timer
will reset.  After the time period has expired the control will
revert back to DHW Mode.  This will continue until one of
the demands has been satisfied.  This parameter can be
changed by the installer by accessing parameter 

E2

.  The time

range of this parameter is 10 minutes to 240 minutes.  The
default value is 30 minutes.

F: Outdoor air reset  

Outdoor air reset operation

When the outdoor air sensor is installed, the control will
calculate the water temperature set point based on the
outdoor air temperature.  As the outdoor air temperature
drops the water temperature set point increases.  This feature
allows the boiler to be more efficient in periods of mild
weather, see FIG. 1-1 on page 19.

Minimum air temperature

When the outdoor air temperature drops to or below this
point, the water temperature will be at its maximum setting
(FIG. 1-1).  However, if the user set point is set lower, the
water temperature will be limited by the user set point
instead.  This parameter can be changed by the installer by
accessing parameter 

F1

.  The temperature range of this

parameter is -30°F to 90°F.  The default value is 25°F.

Maximum air temperature

When the outdoor air temperature rises to or above this
point, the water temperature will be at its minimum setting
(FIG. 1-1).  This parameter can be changed by the installer by
accessing parameter 

F2

.  The temperature range of this

parameter is -30°F to 90°F.  The default value is 70°F.

Содержание KNIGHT 210

Страница 1: ...n Read all instructions including this manual and the Knight Wall Mount Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe pe...

Страница 2: ...but not related to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing boiler 4 Boiler operation 4 Boil...

Страница 3: ...Cancer IARC has concluded Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans Group 1 Normal operating temperatures in this appliance are below...

Страница 4: ...ve sediment The high efficiency heat exchanger can be damaged by build up or corrosion due to sediment Do not use petroleum based cleaning or sealing compounds in the boiler system Gaskets and seals i...

Страница 5: ...n Knight wall mount boiler operation A General B Temperature Setting C Data Logging D Functions E DHW Settings F Outdoor Air Reset Curve G Anti cycling H Control Modes I Circulation Pumps J Service No...

Страница 6: ...ce is included to specify the Near Boiler Piping specific to the Knight wall mount boiler This piping scheme is important for proper operation of the SMART SYSTEM control See the Knight Wall Mount Ins...

Страница 7: ...1 Service Service Manual 7 1 Service continued The Knight wall mount display...

Страница 8: ...TCH SYSTEM SENSOR OUTDOOR SENSOR SEQUENCER BUILDING MANAGMENT SYSTEM LOW VOLTAGE CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE HIGH LIMIT SENSOR FLUE GAS SENSOR FLAME SENSOR LOW WATER C...

Страница 9: ...1 Service Service Manual 9 1 Service continued Control outputs...

Страница 10: ...eration can be based on boiler outlet water temperature boiler return water temperature or system supply temperature depending on the parameter setting Sequence of operation Table 1 shows control modu...

Страница 11: ...prepurge cycle is complete and the blocked drain switch and auto reset high limit are closed the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and ope...

Страница 12: ...ng set point As long as both the space heating and DHW calls for heat remain active the control will switch back and forth between the two modes until one of them is satisfied BLR SH 41 RATE OUT 123 0...

Страница 13: ...1 Service Service Manual 13 1 Service continued Display panel menu access Table 1B Use this procedure to access menus from the display panel...

Страница 14: ...1 Service 14 Service Manual 1 Service Display panel parameter access Table 1C This is a typical example of accessing a parameter shown for parameter I2 boiler pump delay...

Страница 15: ...es Yes 4 SH Offset 17 No No Yes Yes 5 SH Differential 18 No No Yes Yes C 1 Hours Running SH 18 Yes No Yes No 2 Hours Running DHW 18 Yes No Yes No 3 Ignition Attempts 18 Yes No Yes No 4 Show Last 10 Er...

Страница 16: ...turn Temperature Differential for Ending Anti Cycling 20 No No Yes Yes 3 Ramp Delay On Off 20 No No Yes Yes ANTI CYCLING H 1 SH Controlling Sensor Outlet System Inlet 21 No No Yes Yes 2 SH Source Ther...

Страница 17: ...0 F to 190 F The default value is 125 F SH minimum set point The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation The user or installer wi...

Страница 18: ...staller by accessing parameter D2 The time range of this parameter is 0 to 40 minutes The default value is 20 minutes E DHW settings DHW boiler set point When a DHW call for heat becomes active the co...

Страница 19: ...control will block all SH demands DHW demands will still be active This parameter can be changed by the user or the installer by accessing parameter F5 The temperature range of this parameter is 0 F t...

Страница 20: ...the display until the time has elapsed or the water temperature drops below parameter G2 This parameter can be changed by the installer by accessing parameter G1 The time range for this parameter is...

Страница 21: ...ether The designated Leader boiler determines the total output needed from the group based on the set point and controlling sensor reading It assigns portions of this output to itself Leader and the M...

Страница 22: ...s adjustable by the installer by accessing parameter I3 The time range for this parameter is 0 minutes to 40 minutes The default time is 30 seconds J Service Notification Service notification in month...

Страница 23: ...Installation and Operation Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger if flue temperature is more than 54 F above return water tem...

Страница 24: ...1 of the Knight Wall Mount Installation and Operation Manual If any of these are present in the boiler intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lin...

Страница 25: ...night Wall Mount Installation and Operation Manual before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized...

Страница 26: ...edures 2 Check settings of external limit controls if any and adjust if necessary Perform start up and checks 1 Start boiler and perform checks and tests specified in Section 10 Start up of the Knight...

Страница 27: ...hanger Cleaning Kits Model Kit Number Part Number Component Description 50 105 KIT30062 CTN20005 Rear Refractory Cover MSC20083 Nylon 4 Wheel Brush MSC20085 1 4 x 12 Drill Extension 150 210 KIT30063 C...

Страница 28: ...ith boiler on Minimum 4 inches w c natural 8 inches w c LP with gas flowing verify during boiler startup Check control module fuses ALWAYS check control module fuses before replacing control module or...

Страница 29: ...ote thermostat satisfied Review remote thermostat setting Outside air temperature above Warm Weather Shutdown WWSD set point for main control board Check location of outside air sensor Check resistanc...

Страница 30: ...ble 3D Outdoor Air Sensor Resistance vs Temperature Temperature Resistance Temperature Resistance 50 490 813 20 46 218 40 336 606 30 34 558 30 234 196 40 26 099 20 165 180 50 19 900 10 118 018 60 15 3...

Страница 31: ...Clean or replace the burner as necessary Low water flow through the heat exchanger Refer to Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for minimum flow rates...

Страница 32: ...ected excessive condensate build up inside the unit Check condensate tube from unit to floor drain for proper installation and obstructions Inspect condensate trap for blockage Clean if necessary Chec...

Страница 33: ...rify that the plastic hose from the gas valve to the air inlet is connected and is not damaged Verify that the vent air intake pipes are installed correctly and that there are no obstructions Check fo...

Страница 34: ...installed correctly and there are no obstructions Check for 24 vac to the gas valve at the 2 pin connection on the side of the main control board during the ignition attempt If no voltage is present r...

Страница 35: ...operating replace the pump If the system pump is a variable speed pump ensure that the system flow is not less than the boiler flow If operating on something other than an outlet sensor check temperat...

Страница 36: ...EM display to reset Either the inlet water or outlet water temperature sensor has been disconnected Check the sensors and their associated wiring Repair or replace the sensor or wiring if damaged Meas...

Страница 37: ...ation Manual for the proper piping methods for the Knight wall mount boiler Check for 120 vac to the boiler pump motor on a call for heat If voltage is not present check the wiring back to the main co...

Страница 38: ...en corrected Press the RESET button on the SMART SYSTEM display to reset After downloading parameters from a laptop the main control board must be reset Press the ENTER RESET button on the SMART SYSTE...

Страница 39: ...ce the main control board if necessary If 120 vac is present on a call for heat and the boiler pump is not operating replace the pump Verify that the boiler pump is set to the proper speed or that the...

Страница 40: ...Troubleshooting Chart Combustion Levels POSSIBLE CAUSE CORRECTIVE ACTION Vent Air Intake Length or Obstruction Refer to Section 3 General Venting of the Knight Wall Mount Installation and Operation Ma...

Страница 41: ...1 4 turn counterclockwise to decrease CO2 levels After performing one adjustment on the valve follow the Combustion Analysis Procedure on page 40 of this manual to measure the combustion If combustion...