Installation & Operation Manual
3
General
venting
22
The installer must use a specific vent starter
adapter at the flue collar connection.
This adapter is supplied by the vent
manufacturer to adapt to its vent system.
See Table 3F for approved vent adapters.
Discard CPVC starter piece.
NOTICE
All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 3-10).
NOTICE
IMG00129
JOINT CONNECTOR REQUIRED AT ALL
COMPONENT CONNECTIONS OF VENT SYSTEM
POLYPROPYLENE ADAPTER
Figure 3-10 Near Water Heater Polypropylene Venting
Polypropylene
This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3E.
All terminations must comply with listed options in this manual
and be a single-wall vent offering.
For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
Use only the adapters and vent system
listed in Tables 3E and 3F. DO NOT
mix vent systems of different types or
manufacturers. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
WARNING
Installations must comply with applicable
national, state, and local codes. For
Canadian installation, polypropylene vent
must be listed as a ULC-S636 approved
system.
NOTICE
Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.
NOTICE
Approved Polypropylene Vent Manufacturers
Make
Model
Centrotherm Eco Systems
InnoFlue SW/Flex
Duravent (M & G Group)
PolyPro Single-Wall / PolyPro Flex
Table 3E Polypropylene Vent Pipe and Fittings
WARNING
Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.
Model
Centrotherm InnoFlue SW
Duravent Polypro
Polypropylene
Adapter
Joint
Connector
Sidewall Retaining
Bracket*
Sidewall
Adapter*
Polypropylene
Adapter
Joint
Connector
Sidewall Kit*
151-200
ISAAL0303
IANS03
IATP0303
ISTAGL0303
3PPS-AD
3PPS-LB
3PPS-HLK
400-601
ISAAL0404 IANS04
IATP0404
ISTAGL0404
4PPS-AD
4PPS-LB
4PPS-HLK
701-801
ISAAL0606
Not
Required
IATP0606
ISTAGL0606 FSA-6PVCM-6PPS Not Required
6PPK-HLK
* These parts are only needed if the sidewall termination assembly is used (see FIG. 4-5B on page 26).
Table 3F Approved PolypropyleneTerminations