41
12.0
AIR SUPPLY
The following information is based on single boiler installations only. If more than one boiler is being used, BS5440-2
or BS6644 (as appropriate) should be consulted to calculate the necessary requirements.
12.1
COMBUSTION VENTILATION
When used as a Type C (room sealed) appliance, provided sufficient clearance is provided, ventilation for combustion
is not necessary as the combustion air is ducted directly from outside.
When used as a Type B (open flue) appliance, the combustion air requirements are as follows:
Model
Gross
Input
(kW)
Net
Input
(kW)
Ventilation
(Room)
(cm
2
)
Compartment
Compartment
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
HCB46CE
43.9
39.6
165
200
400
400
800
HCB61CE
58.6
52.8
230
265
530
530
1060
12.1.1
COMBUSTION
VENTILATION
REQUIREMENTS
HCB46CE
–
HCB61CE
Model
Input
(Gross)
kW
Input
(Net)
kW
Plant Room
Enclosure
Low
Summer Use
Medium
Summer Use
High
Summer Use
Low
Summer Use
Medium
Summer Use
High
Summer Use
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
HCB86CE
83.5
75.3
152
304
228
380
304
456
380
760
456
836
532
912
12.1.2
COMBUSTION
VENTILATION
REQUIREMENTS
HCB86CE
12.2
COOLING VENTILATION
When used as a type C (room sealed) appliance, installed in a compartment or an enclosure, cooling ventilation should
be provided as follows:
Model
Input
(Gross)
kW
Input
(Net)
kW
Enclosure/Compartment
Enclosure/Compartment
Boiler Room
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
HCB46CE
43.9
39.6
200
200
400
400
N/A
N/A
HCB61CE
58.6
52.8
265
265
530
530
N/A
N/A
HCB86CE
83.5
75.3
380
380
760
760
152
152
12.2.1
COOLING
VENTILATION
REQUIREMENTS
When used as a type B (open flue) appliance, provision for cooling ventilation is included in the combustion ventilation
allowance.
Содержание HERALD HCB116CE
Страница 8: ...8 3 1 2 PRINCIPLE PARTS TO BE USED IN CONJUNCTION WITH TABLE 3 1 1...
Страница 11: ...11 5 2 CLEARANCES 5 2 1 ENCLOSURE INSTALLATION CLEARANCES MM 5 2 2 PLANT ROOM INSTALLATION CLEARANCES MM...
Страница 31: ...31 Max distance between brackets...
Страница 32: ...32...
Страница 33: ...33...
Страница 37: ...37...
Страница 53: ...53 15 8 WIRING DIAGRAM 15 8 1 WIRING DIAGRAM...
Страница 54: ...54 15 9 LADDER DIAGRAM 15 9 1 LADDER DIAGRAM...
Страница 92: ...92...