To install the flue connection to the EKB175CE boiler the following procedure should be followed:
1.
Insert the exhaust transition (Item 6 in
Figure 8.6
) into the exhaust port on the boiler.
2.
Insert the flue temperature sensor (supplied with the boiler) into the location hole on the exhaust transition.
NOTE: IF THE FLUE TEMPERATURE SENSOR IS NOT FITTED, THE FLUE GAS MAY EXCEED THE
MAXIMUM TEMPERATURE RATING OF THE FLUE AND CAN LEAD TO SEVERE PERSONAL INJURY, DEATH
OR SUBSTANTIAL PROPERTY DAMAGE.
3.
Insert the 90° elbow (Item 5 in
Figure 8.6
) in to the exhaust transition ensuring the socket is pointing
upwards.
4.
Insert the 100mm to 130mm expander (Item 4 in
Figure 8.6
) in to the 90° elbow.
5.
Insert the 130mm to 150mm expander (Item 3 in
Figure 8.6
) in to the 100mm to 130mm expander.
6.
Insert the air intake transition (Item 2 in
Figure 8.6
) into the intake connection (Item 1) and tighten the worm
drive clip.
8.7.4
EKB205CE – EKB235CE
FIGURE 8.7
FLUE CONNECTION DETAILS EKB205CE – EKB235CE
ITEM
DESCRIPTION
1
Intake Connection
2
Air Intake Transition
3
Exhaust Transition
4
Flue Collar
TABLE 8.5
FLUE CONNECTION DETAILS EKB205CE – EKB235CE
To install the flue connection to the EKB205CE – EKB235CE boilers the following procedure should be followed:
1.
Ensure that the flue collar (Item 4 in
Figure 8.7
) is correctly located in the appliance and that the flue
temperature sensor (supplied with the boiler) is located in the grommet in the collar.
NOTE: IF THE FLUE TEMPERATURE SENSOR IS NOT FITTED, THE FLUE GAS MAY EXCEED THE
MAXIMUM TEMPERATURE RATING OF THE FLUE AND CAN LEAD TO SEVERE PERSONAL INJURY, DEATH
OR SUBSTANTIAL PROPERTY DAMAGE.
2.
Insert the air intake transition (Item 2 in
Figure 8.7
) into the intake connection (Item 1) and tighten the worm
drive clip.
3.
Insert the exhaust transition (Item 3 in
Figure 8.7
) into the flue collar (Item 4) and secure with the worm
drive clip.
2
3
4
1