1
Service
Service Manual
16
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User
Installer
Value
Value
Value Access
Access
H
1
HWG Night Setback Offset Temp
22
0
90
0
No
Yes
2
HWG Night Setback Mon End
22
N/A
N/A
N/A
No
Yes
3
HWG Night Setback Mon Begin
22
N/A
N/A
N/A
No
Yes
4
HWG Night Setback Tue End
22
N/A
N/A
N/A
No
Yes
5
HWG Night Setback Tue Begin
22
N/A
N/A
N/A
No
Yes
6
HWG Night Setback Wed End
22
N/A
N/A
N/A
No
Yes
7
HWG Night Setback Wed Begin
22
N/A
N/A
N/A
No
Yes
8
HWG Night Setback Thur End
22
N/A
N/A
N/A
No
Yes
9
HWG Night Setback Thur Begin
22
N/A
N/A
N/A
No
Yes
10
HWG Night Setback Fri End
22
N/A
N/A
N/A
No
Yes
11
HWG Night Setback Fri Begin
22
N/A
N/A
N/A
No
Yes
12
HWG Night Setback Sat End
22
N/A
N/A
N/A
No
Yes
13
HWG Night Setback Sat Begin
22
N/A
N/A
N/A
No
Yes
14
HWG Night Setback Sun End
22
N/A
N/A
N/A
No
Yes
15
HWG Night Setback Sun Begin
22
N/A
N/A
N/A
No
Yes
I
1
ModBus Active / Inactive
23
ACTIVE INACTIVE INACTIVE
No
Yes
2
ModBus Out of Order Timer
23
5
120
30
No
Yes
J
1
Cascade Active / Inactive
23
ACTIVE INACTIVE INACTIVE
No
Yes
2
Cascade Address
23
0
7
1
No
Yes
3
Cascade Offset
23
0
40
10
No
Yes
4
Cascade Differential
23
0
72
20
No
Yes
5
Max Boiler Setpoint for Cascade
23
32
185
185
No
Yes
6
Cascade Type
23
N/A
N/A
N/A
No
Yes
7
Block Time Switching Boiler On / Off
23
0
255
60
No
Yes
8
Minimum Next On Time
24
0
255
60
No
Yes
9
Rate % to Switch On Next Boiler
24
1
100
80
No
Yes
10
Rate % to Switch Off Last Boiler
24
1
100
10
No
Yes
11
Number of Boiler Pumps Always On
24
0
8
0
No
Yes
HW
G NIGHT SETB
A
C
K
CASCADE
MOD BU
S