background image

For this type of installation, it is best to use a
draft control for each water heater located
on the riser between the vent outlet and the
breeching - Location “A”. When this riser is
too short to permit the installation of a draft
control, locate a separate control for each
water heater on the main breeching as
illustrated in Location “B”. If, because of
general crowding or other reasons, neither
of these locations are possible, use a single
large control in the breeching between the
water heater nearest the chimney and the
chimney, as shown in Location “C”.

All draft readings are made while unit is in
stable operation (approximately 5 minutes
running time).

Masonry Chimney

A masonry chimney 

must

be properly sized

for the installation of a high efficiency gas
fired appliance. Exterior masonry chimneys,
with one or more sides exposed to cold
outdoor temperatures, are more likely to
have venting problems. The temperature of
the flue products from a high efficiency
appliance may not be able to sufficiently
heat the masonry structure of the chimney to
generate proper draft. This will result in

condensing of flue products, damage of the
masonry flue/tile, insufficient draft and
possible spillage of flue products into an
occupied living space.  

Carefully inspect all chimney systems during
the project design phase. If there is any doubt
about the sizing or condition of a masonry
chimney, it is prudent to reline the chimney
with a properly sized and approved chimney
liner system. Metallic liner systems (Type “B”
doublewall or flexible or rigid metallic liners)
are recommended. Consult with local code
officials to determine code requirements or the
advisability of using or relining a masonry
chimney.

OUTDOOR INSTALLATION

Units are self venting and can be used
outdoors when installed with the optional
Outdoor Cap. This cap mounts directly to
the top of the water heater and covers the
flue outlet and combustion air inlet openings
on the jacket. No additional vent piping is
required. Maintain a minimum clearance of
3

(76 mm) to combustible surfaces and a

minimum of 3

(76 mm) clearance to the air

inlet. 

L o c h i n v a r

D E S I G N E R

S

G U I D E

C O P P E R

-

F I N

W A T E R

H E A T E R

6 1 5 - 8 8 9 - 8 9 0 0                      

9

NOTE:

Common venting

systems may be too

large when an existing

unit is removed. Be

careful to resize any

common venting system

when new appliances

are installed or existing

appliances are replaced.

NOTE:

Flue gases will form a

white plume in winter.

Plume could obstruct

window view. Flue gas

condensate can freeze

on exterior surfaces or

on the vent cap. Flue

gas condensate can

cause discoloration of

exterior building

surfaces. Adjacent brick

or masonry surfaces

should be protected with

a rust resistant sheet

metal plate.

(FIG. 8) MULTIPLE UNIT BAROMETRIC

DAMPER INSTALLATION

(FIG. 9) OUTDOOR VENTING

NOTE:

Venting of a high

efficiency appliance into

a cold or oversized

masonry chimney can

result in operational and

safety problems.

Содержание Copper-Fin CW 495

Страница 1: ...DESIGNER S GUIDE COPPER FIN WATER HEATER 4 9 5 0 0 0 2 0 6 5 0 0 0 B t u h r...

Страница 2: ...d in a succinct easy to use manner so you can use and share information confidently and with minimal effort However it is important to remember that this guide is not intended to replace our installat...

Страница 3: ...FIG 2 Water Heater Equipment Control Orientation 4 FIG 3 6 Combustion Ventilation Air 5 6 FIG 7 Barometric Damper Installation 8 FIG 8 Multiple Unit Barometric Damper Installation 9 FIG 9 Outdoor Ven...

Страница 4: ...connections should leak water damage will not occur When such locations cannot be avoided it is recommended that a suitable drain pan adequately drained be installed under the unit The pan must not re...

Страница 5: ...istribution piping runs through the floor and beneath the appliance Ensure that combustible floor base meets local fire code requirements Outdoor models require the installation of an optional vent ca...

Страница 6: ...RMINAL STRIP HOT WATER OUTLET COLD WATER INLET BURNER INSPECTION PORT FRONT GAS CONNECTION HOT WATER OUTLET COLD WATER INLET BURNER INSPECTION PORT FRONT AIR INLET FRESH AIR INLET RIGHT SIDE FLUE PROD...

Страница 7: ...re If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room each of the two openings should be sized based on a minimum free area of one squa...

Страница 8: ...ry I listed vent pipe Additionally it is recommended that this vent material be double wall construction or insulated in the field A Category I appliance operates with a non positive static vent press...

Страница 9: ...The vent terminal should be vertical and exhaust outside the building at least 2 feet 0 6 m above the highest point of the roof when within a 10 foot 3 05 m radius Additionally vertical terminations...

Страница 10: ...terial using the FAN category of vent sizing tables in the latest edition of the National Fuel Gas Code FAN applies to fan assisted combustion appliances in Category I Barometric Dampers A barometric...

Страница 11: ...a masonry chimney it is prudent to reline the chimney with a properly sized and approved chimney liner system Metallic liner systems Type B doublewall or flexible or rigid metallic liners are recomme...

Страница 12: ...onto the water heater Lochinvar must furnish an outdoor vent kit in accordance with CSA international requirements Each kit includes the flue outlet combustion air inlet assembly gasket and pump cove...

Страница 13: ...R H E AT E R 6 1 5 8 8 9 8 9 0 0 1 1 4 5 TABLE D GAS SUPPLY PIPE SIZING Length of Pipe In Straight Feet Nominal Iron Pipe Size Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200 369 256 205 174 155...

Страница 14: ...TANT To ensure proper velocity through the heat exchanger it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet This must be done on initial installation and...

Страница 15: ...ory installed as a low water cutoff device on models CW495 thru CW2066 The flow switch is installed in the outlet piping from the water heater and wired in series with the ignition system safety contr...

Страница 16: ...nvar NOTE When the unit is installed in Canada it must conform to the CAE C22 1 Canadian Electrical Code Part 1 and or local Electrical Codes NOTE Incorrect piping of the cold water supply to the syst...

Страница 17: ...RELIEF VALVE LOCK TEMP STORAGE TANK DRAIN FULL PORT BALL VALVE SYSTEM PUMP SYSTEM RELIEF VALVE TEE ELBOW UNION EXPANSION TANK CHECK VALVE THERMOMETER COLD WATER SUPPLY BUILDING RETURN INLET OUTLET LO...

Страница 18: ...OW UNION EXPANSION TANK CHECK VALVE THERMOMETER L E G E N D BUILDING HOT WATER SUPPLY LOCHINVAR WATER HEATER COLD WATER SUPPLY BUILDING RETURN LOCK TEMP STORAGE TANK RELIEF VALVE DRAIN OUTLET INLET LI...

Страница 19: ...LET RELIEF VALVE OUTLET COLD WATER SUPPLY 1400 F HOT WATER SUPPLY 1800 F HOT WATER SUPPLY LOCK TEMP STORAGE TANK LOCHINVAR WATER HEATER MIXING VALVE CHECK VALVE LIT0136 This illustration is for concep...

Страница 20: ...PPLY BUILDING HOT WATER SUPPLY LIT0138 This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer All nec...

Страница 21: ...SUPPLY LIT0451 THERMOMETER This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer All necessary equi...

Страница 22: ...S G U I D E C O P P E R F I N W A T E R H E AT E R 6 1 5 8 8 9 8 9 0 0 PIPING DIAGRAM MULTI STACK FRAME W WATER HEATERS AND STORAGE TANK LIT0396 Heater Heater Inlet Manifold Model Outlet Size Pipe Si...

Страница 23: ......

Страница 24: ...Lochinvar Corporation Lebanon TN 615 889 8900 Fax 615 547 1000 www Lochinvar com CW DG 05 Revised CW DG 05 1 07 4 09 Printed in U S A...

Отзывы: