3
Troubleshooting
(continued)
39
Table 3A Troubleshooting Chart - No Display
FAULT
CAUSE
CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.
• Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON
position.
• Check 120 VAC through the ON/OFF switch.
• Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- No voltage through the switch.
• Replace switch.
- Bad display board.
• Replace board.
- Bad main control board.
• Replace the main control board.
- Blown fuse.
• Replace fuse F3 on the main control board, see
page 38 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat satisfied.
• Review remote thermostat setting.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on page 42 of this manual for corrective
actions.
Unit Does
Not Modulate
Above 50%
- Water heater controlled by BMS.
• Check BMS parameter settings.
- Flue sensor open.
• Verify that the flue sensor is located in the flue outlet.
• Check wiring connections at the flue sensor.
• Check the resistance of the flue sensor and compare
to Table 3C on page 40 of this manual.
Service Manual
Содержание ArmorX2 1.0
Страница 5: ...1 Service The Armor X2 display 5 Service Manual...
Страница 51: ...Notes 51...
Страница 52: ...Revision Notes Revision A ECO C09645 initial release AWX2 SER Rev A 1 12...