User’s Information Manual

17

4  

SMART SYSTEM control module 

(continued)

Status Display Screens 

(cont’d)

By using the Previous/Next (

,

) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8)

display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and
what they can display:

Screen

Display shows:

Description

#3

SYS: ***.*F

If the system sensor has not been selected as the control sensor,
only the system temperature will be displayed.

***.*F (***)

When the system sensor has been selected as the control sensor, the
control will display the system temperature as well as the set point in
parenthesis.

Open

The control does not detect the system sensor.

Shorted

The system sensor wires or the sensor itself has become grounded.

OUTDOOR: ***.*F

The control will display the outdoor air temperature as sensed by
the outdoor air sensor.

Open

The control does not detect the outdoor air sensor.

Shorted

The outdoor air sensor wires or the sensor itself has become
grounded.

Press the Next 

arrow key on the SMART SYSTEM display to access Screen #4.

#4

FLUE: ***.*F

The control will display the flue temperature.

Open

The control does not detect the flue sensor.

Shorted

The flue sensor wires or the sensor itself has become grounded.

AUX: ***.*F

The control will display the temperature.

Open

The control does not detect the auxiliary sensor.

Shorted

The auxiliary sensor wires or the sensor itself has become
grounded.

Press the Next 

arrow key on the SMART SYSTEM display to access Screen #5.

#5

FAN SPD: ****RPM

The control will display the actual fan motor RPM.

FLAME SIG: **.*uA

The control will display the flame signal in dc microamps.

Press the Next 

arrow key on the SMART SYSTEM display to access Screen #6.

#6

SH CFH: OFF

The control has not received a call for heat from a remote
thermostat.

ON

The control has received a call for heat from a remote thermostat.

DHW CFH: OFF

The control has not received a call for heat from a SH remote
thermostat.

ON

The control has received a call for heat from a DHW thermostat.

Press the Next 

arrow key on the SMART SYSTEM display to access Screen #7.

Содержание 80 - 500

Страница 1: ...flammable vapors are likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas...

Страница 2: ...life of the product DANGER WARNING CAUTION CAUTION NOTICE DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentiall...

Страница 3: ...al supply to the circulator Instead shut off the gas supply at a location external to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance c...

Страница 4: ...hments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishmen...

Страница 5: ...re than 54 F above return water temperature If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheel Owner maintenance s...

Страница 6: ...or fluorine if allowed to contaminate the boiler intake air will cause acidic condensate in the boiler This will cause significant damage to the boiler if allowed to continue Read the list of potentia...

Страница 7: ...Call your qualified service technician to inspect the boiler and system 5 Leave the top of the 1 2 inch tee OPEN This is needed as a vacuum break 6 Do not expose condensate line to freezing temperatu...

Страница 8: ...s on pages 9 and 10 of this manual Call your qualified service technician to inspect the boiler and system Shut boiler down unless boiler is used for Domestic Water 1 Follow To Turn Off Gas to Applian...

Страница 9: ...User s Information Manual 9 3 Operating instructions Models 80 285...

Страница 10: ...User s Information Manual 10 3 Operating instructions 3 Operating instructions Models 399 500...

Страница 11: ...s Information Manual 11 4 SMART SYSTEM control module Figure 4 Control Panel Knight boiler control module Use the control panel FIG 4 to set temperatures operating conditions and monitor boiler opera...

Страница 12: ...the installer access code Have your qualified service technician reference the Knight Boiler Service Manual Saving parameters reference parameter table on page 13 of this manual To save parameters an...

Страница 13: ...es Yes Yes 7 Night Setback Times 14 Yes Yes Yes Yes B 1 SH Set Point User 14 Yes Yes Yes Yes E 1 DHW Boiler Set Point 15 Yes Yes Yes Yes 2 SH DHW Switching Time 15 Yes Yes Yes Yes F 5 Outdoor Air Shut...

Страница 14: ...an be changed by the user or the installer by accessing parameter A6 The temperature range for this parameter is 32 F to 140 F The feature is turned off with a setting of 32 F The default value is 32...

Страница 15: ...F to 120 F The default value is 80 F Outdoor air shutdown differential The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go...

Страница 16: ...an additional 10 seconds to clear the combustion chamber and vent system of residual flue products Service The unit has been placed in a temporary mode that will allow the unit to fire at 100 of rate...

Страница 17: ...e outdoor air sensor wires or the sensor itself has become grounded Press the Next arrow key on the SMART SYSTEM display to access Screen 4 4 FLUE F The control will display the flue temperature Open...

Страница 18: ...mote thermostat and has not powered the system pump ON The control has received a call for heat from a remote thermostat and has powered the system pump Delay The system call for heat has been satisfi...

Страница 19: ...User s Information Manual 19 5 Notes...

Страница 20: ...KB USER 01 09 05...

Отзывы: