40
T OFF
ROx
T
t
T ON
Temperature thermostat ›Cooling‹:
T ON > T OFF The output is activated once the
›T ON‹ temperature is reached, and deactivated
once the ›T off‹ temperature is reached.
T ON
ROx
T
t
T OFF
Temperature thermostat ›Heating‹:
T OFF > T ON The output is deactivated once the
›T OFF‹ temperature is reached, and activated
once the ›T ON‹ temperature is reached.
Thermostat functions
ROx
8:00
9:00
t
T OFF
ROx
T
t
T ON
8:00
9:00
The controller’s free outputs can be used as thermostats for various applications.
Settings must be made to this effect in professional mode under ›1.3.1 Thermostat‹.
Control signals can be de
¿
ned as temperature thermostat, timer,
timer thermostat or temperature comparator.
Timer-Thermostat
Combination of timer and thermostat.
Once at least one of these criteria is met,
the output is activated.
Temperature comparator
Any temperature difference to a reference
sensor will trigger a control signal:
The output is activated once ›dT ON‹ is reached,
and deactivated once ›dT OFF‹ is reached.
Timer function:
The output is activated
within a selected time frame.
dT OFF
dT ON
ROx
TSx
T
t
Reference sensor
GB
ENGLISH