LK Systems Cq 1 NC Скачать руководство пользователя страница 2

2

EN.33.C.74(NC).

Assembly instructions | LK Receiver Unit Cq 1 (NC)

Programming / commissioning

1. Activate the receiver unit

Always begin programming by erasing all even-

tual previous programming according to the be-

low:

• 

Press the ”Reset” button simultaneously as 

the

!

button.

• 

Then release the ”Reset” button first, follo-

wed by 

!

• 

Press reset again.

• 

Activate receiver unit Cq 1 by pressing once 

on

!

.

A weak signal sounds and an indicating light 

turns on.

2. Activate the thermostat

A

B

C

D

• 

Open the lid of the room thermostat and 

remove the transport protection from the 

batteries. 

• 

Check that the current switch (A) is set to the 

bottom position facing the heat symbol, ac-

cording to image 3 

• 

Activate the room thermostat by holding the 

lower button (B) down, press briefly on the 

upper black button (C). 

• 

When the green LED on the thermostat 

lights, the lower black button (B) may be 

released. 

• 

The thermostat is now activated for pro-

gramming. 

The unit is complemented with a LK Transformer 

230/24V AC (article order separately)

The controlling device moves once a day in order 

to prevent valves from sticking in a closed posi-

tion. If no valve movement is wanted, the function 

can be disconnected by removing jumper 1 on the 

thermostat. Remove the dial of the thermostat, 

loosen the screws and remove the cover. Remove 

jumper 1, marked BR1 on the circuit board.

Installation

A 230 Volt wall outlet should be available nearby 

the receiver unit. The receiver unit may only be 

installed by a suitably qualified professional ac-

cording to the wiring diagram and in accordance 

with valid safety regulations. In order to achieve 

protective level 2, the necessary installation mea-

surements must be taken.

Connect 230 V to terminals N and →

Coupling of controlling devices

Controlling devices are coupled between termi-

nal 9 on Cq 1 and one of the 24 Volt cables of the 

LK Transformer.

If many controlling devices are to be connected, 

they are coupled parallel to each other and in 

series with the transformer, see wiring diagram. 

Then connect the second 24 Volt cable of the trans-

former to terminal 2 on the Cq 1.

N

9

Mains AC 230V

2

LK Actuator

LK Transformer

230 / 24 V AC

Mains AC 230V

24 V AC

LK Cq 1

Electric wiring diagram for Cq 1

Содержание Cq 1 NC

Страница 1: ... termi nal a total of eight devices can be connected Models LK Wireless Room Temperature Controller Cq NC 1 consists of a LK Room Thermostat Cq transmitter and a LK Receiver Unit Cq 1 a re ceiver device for one channel Also included in the wireless assortment is a re ceiving device for eight channels for more infor mation see separate instructions for LK Receiver Unit Cq 8 The LK Repeater Cq HW si...

Страница 2: ...ly The controlling device moves once a day in order to prevent valves from sticking in a closed posi tion If no valve movement is wanted the function can be disconnected by removing jumper 1 on the thermostat Remove the dial of the thermostat loosen the screws and remove the cover Remove jumper 1 marked BR1 on the circuit board Installation A 230 Volt wall outlet should be available nearby the rec...

Страница 3: ...Confirm by pres sing once on the upper black button of the ther mostat C The LED on the thermostat shuts off and the diode on the receiver unit will flash a few times The programming is now complete Functional control Test the connection by turning the knob of the thermostat up down When the thermostat is at the maximum position the indication light on Cq1 should be on and when the thermostat is a...

Страница 4: ... mm Weight 0 144 kg Capping class IP 40 Max no controlling devices Max 8 pcs Article name LK Room Thermostat Cq n Article no 241 88 50 Polar white 241 88 51 Silver grey Setting area 5 30 C Power supply 2 x 1 5 V 3 V alkaline bat teries LR03 Battery life Approx 2 years Control function PBM optional 2 point Cycle period Approx 10 minutes total on off time Measurement interval Approx 10 minutes Type ...

Отзывы: