LK Systems Cq 1 NC Скачать руководство пользователя страница 1

1

controlling devices. The control signal, which is 

calculated from the difference between the real 

and set temperatures, is emitted in the form of 

a signal with different pulse and rest conditions. 

The total of the signal and rest times is always 10 

minutes. In the event of large differences in tem-

perature, the thermostat is constantly coupled on 

or off.

Assembly of LK Room Thermostat Cq-n

Take apart the room thermostat by lifting the dial 

at the temperature scale upwards and loosening 

the screws which are visible. Unfold the upper 

piece towards the left until it loosens. Install in 

place according to the installation drawing.

To ensure proper functionality of the room ther-

mostat, the following points should be observed:

• 

Install the thermostat on an inner wall with 

free ventilation, approximately 1.5 metres 

above the floor. 

• 

Avoid exposing the thermostat to direct sun-

light or other heat sources. 

• 

Do not install the thermostat close to a radio, 

TV or other senders. 

• 

Installation of the thermostat in the vicinity 

of metal doors, metal cabinets or similar is 

unsuitable. 

LK Receiver Unit Cq 1

LK Receiver Unit Cq 1 can address 1 LK room 

thermostat Cq-n. 

It is possible to connect two controlling devices 

directly to Cq 1. With the help of an outer termi-

nal, a total of eight devices can be connected. 

Models

LK Wireless Room Temperature Controller Cq 

NC 1 consists of a LK Room Thermostat Cq 

(transmitter) and a LK Receiver Unit Cq 1 (a re-

ceiver device for one channel).

Also included in the wireless assortment is a re-

ceiving device for eight channels; for more infor-

mation see separate instructions for LK Receiver 

Unit Cq 8. 

The LK Repeater Cq HW (signal repeater) is avai-

lable as an accessory for difficult sending condi-

tions; see more about this in separate instructions 

for the LK Repeater-HW.

Functional description

The LK Room thermostat Cq-n regulates the tem-

perature of the room via transmission of radio 

signals to the LK Receiver Unit Cq 1. The recei-

ver unit transforms the radio signals into control 

signals which activate the LK Controlling Device. 

Since the communication between the LK Re-

ceiver Unit Cq 1 and the LK Controlling Device 

occurs via cable, it is most suitable to place the 

receiver unit in direct connection to the circuit 

distributor.

LK Room Thermostat Cq-n

LK Room Thermostat Cq-n is available in two 

different models: polar white or silver grey.

The LK Room Thermostat Cq-n regulates the 

temperature of the room via transmission of radio 

signals to the LK Receiver Unit Cq 1. Regulation 

occurs via pulse width modulated (PBM) regula-

tion which is especially adapted to thermoelectric  

LK Receiver Unit Cq 1 (NC)

EN.33.C.74(NC).

Assembly instructions | LK Receiver Unit Cq 1 (NC)

Содержание Cq 1 NC

Страница 1: ... termi nal a total of eight devices can be connected Models LK Wireless Room Temperature Controller Cq NC 1 consists of a LK Room Thermostat Cq transmitter and a LK Receiver Unit Cq 1 a re ceiver device for one channel Also included in the wireless assortment is a re ceiving device for eight channels for more infor mation see separate instructions for LK Receiver Unit Cq 8 The LK Repeater Cq HW si...

Страница 2: ...ly The controlling device moves once a day in order to prevent valves from sticking in a closed posi tion If no valve movement is wanted the function can be disconnected by removing jumper 1 on the thermostat Remove the dial of the thermostat loosen the screws and remove the cover Remove jumper 1 marked BR1 on the circuit board Installation A 230 Volt wall outlet should be available nearby the rec...

Страница 3: ...Confirm by pres sing once on the upper black button of the ther mostat C The LED on the thermostat shuts off and the diode on the receiver unit will flash a few times The programming is now complete Functional control Test the connection by turning the knob of the thermostat up down When the thermostat is at the maximum position the indication light on Cq1 should be on and when the thermostat is a...

Страница 4: ... mm Weight 0 144 kg Capping class IP 40 Max no controlling devices Max 8 pcs Article name LK Room Thermostat Cq n Article no 241 88 50 Polar white 241 88 51 Silver grey Setting area 5 30 C Power supply 2 x 1 5 V 3 V alkaline bat teries LR03 Battery life Approx 2 years Control function PBM optional 2 point Cycle period Approx 10 minutes total on off time Measurement interval Approx 10 minutes Type ...