3
Specifications
General specifications
Item
Specifications
Ambient temperature
range
0 to +55
°
C during operation, storage temperature: -20~70
°
C
Ambient humidity
35 to 85 % RH during operation (Dew condensation shall not be allowed.)
Noise resistance
Noise voltage 1,000 Vp-p, noise width 1
μ
s.
Withstand voltage
500 V AC for 1 min
(between analog input terminal and each terminal of PLC main unit)
Insulation resistance DC500V / 5 M
Ω
Operating
atmosphere
Corrosive gas and many dusts shall not be detected.
Power supply specifications
Item
Specifications
Interface driving
power supply
24 V DC
±
10%, 100 mA, supplied via terminal from outside
CPU driving power
supply
5 V DC, 50mA, supplied via extension cable from PLC main unit
Performance specifications
Item
Specifications
Conversion speed
When only voltage input and current input are used 500
μ
s x Number of used channels
Insulation method
Photocoupler insulates analog input area from PLC.
DC/DC converter insulates power supply from analog I/O.
Number of occupied
I/O points
Don’t occupy any I/O points
Applicable PLC
Ex1n, Ex2n Series PLC, V1.40 or more