LXC31X0/LXC93X0 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC31X0/LXC39X0 User Manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
:
T:+86 769-23162896
:
F:+86 769-23166296
:
www.lixise.com
Page 6 of 28
Programmable Relay Output 5
5A AC250V voltage-free output
Overall Dimensions
143mm x 115mm x41mm
Panel Cutout
110mm x 90mm
CT Secondary Current
5A (rated)
Working Condition
Temperature: (-25~70)ºC;
Humidity: (20~93)%RH
Storage Condition
Temperature: (-25~70)ºC
Protection Level
IP55:When waterproof rubber seal installed between the controller
and panel fascia.
IP42:When waterproof rubber seal is not installed between the
controller and panel fascia.
Insulation Intensity
Object: input/output/power
Quote standard: IEC688-1992
Test way: AC1.5kV/1min leakage current:3mA
Weight
330g
4. Operation
4.1. Push buttons
Stop/ Reset
Stop running generator in Auto/Manual mode;
In case of alarm condition, pressing the button will reset alarm;
During stopping process, press this button again to stop generator
immediately;
In Standby mode, pressing and holding the button for 3 seconds will test
indicator lights (lamp test).
Start
Start genset in Manual/Test mode.
Manual
Pressing this key will set the module into manual mode.
Automatic
Pressing this key will set the module into auto mode.
Set/Confirm
Pressing this key will enter into Main Menu;
In setting parameter status, press this key will shift cursor or confirm
setting value.
Up/Increase
Scrolls the screen up;
Shift the cursor up or increase the set value in parameter setting menu.
Down/Decrease Scrolls the screen down;
Shift the cursor down or decrease the set value in parameter setting menu.