LXC31X0/LXC93X0 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC31X0/LXC39X0 User Manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
:
T:+86 769-23162896
:
F:+86 769-23166296
:
www.lixise.com
Page 23 of 28
If the generator without magnetoelectric sensor and Oil pressure sensor,the“Charger D+”is optional
as a starter motor separation conditions.It is recommended to select“Oil P Charger D+”for
safety.
7.9. Sensor select
When reselect sensors, the sensor curve will be transferred into the standard value.
When there is difference between standard sensor curves and the using sensor, user can adjust it in
“curve type
” via PC. After the adjustment is completed, the data will be saved to the "custom
resistance curve" option.Using a custom sensor when choosing the sensor options "Custom
resistance curve."
In the control panel, the same can customize the sensor curve, such as setting the project is "85.
Custom sensor curve."
The specific operation as follows:
1
Switch to
【
85 custom sensor curve
】
interface.
2
Press
key to enter the sensor type selected, press
to switch type.
3
Select Custom sensor curve type, pass
button to enter the data setting interface.
4
After setting, press
button to return to the previous menu.
If select sensor type as “None”, sensor curve is not working and LCD display “---” for the sensor
information.
If there is no oil pressure sensor, but there is low oil pressure alarm switch, user must set the oil
pressure sensor as “None”, otherwise, maybe low oil pressure shutdown occurs.