GAS SUPPLY
Inlet Standing Pressure
Set Up Pressure
NATURAL GAS
2.0 kPa
HIGH 1.0 kPa
LOW 0.5 kPa
U/LPG – PROPANE
3.0 kPa
HIGH 2.5 kPa
LOW 1.5 kPa
Maximum Inlet Pressure 6.0 kPa
If inlet pressure exceeds 6.0 kPa, then damage will occur and may result in a hazardous
condition.
TEST PRESSURES
Both the gas inlet and outlet test nipples are located on the electronic gas control valve.
Values are shown in section 11.
TESTING
The fire outlet pressures have been preset in the factory. To adjust:
Turn off the fire and loosen the test nipple screw;
Fit 6mm tube and test gauge securely;
Turn on the fire, check pressure settings on high and low;
Adjust control valve setting where required (refer to the Rating Plate for correct adjustment
and settings);
Turn off the fire, remove the gauge and tube. Secure the test nipple screw and replace the
cover.
In transit items of the burner or fire may become loose or pipe work may move, it is important
to check all joints are gas tight and that all parts are located and operating correctly
Final test with gas detector
Содержание Eastside Euro
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 27: ......
Страница 28: ......
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......