Littlefuse Startco SE-134C Скачать руководство пользователя страница 4

 

 

Page 2 

 

SE-134C Ground-Fault Ground-Check Monitor

 Rev. 

 
 

Pub. SE-134C-M, December 16, 2009. 

  If the SE-134C is used in a ground-fault-only 
application, an SE-TA6A must be connected to the 
ground-check and cable-ground terminals to validate the 
ground-check circuit.  See Fig. 1. 
 

2.3  R

ESET

 

  All ground-fault trips are latching and ground-check 
trips can be latching or non-latching.  To reset ground-
fault trips or latching ground-check trips, press the 
RESET switch or short the RESET terminals 9 and 10.  
See Fig. 1.   
  Cycling the supply voltage will also reset ground-fault 
trips; however, if the ground-check circuit is configured 
for latching fail-safe operation, the ground-check circuit 
will trip when supply voltage is applied.   
  The single-shot reset circuit responds only to a 
momentary closure; a jammed or shorted switch will not 
maintain a reset signal. 
 

2.4  T

RIP

 R

ELAY

 

  Isolated, normally open (Trip A, terminals 24 and 25) 
and normally closed (Trip B, terminals 22 and 23) 
contacts are provided for use in a contactor- or breaker-
control circuit.  With no connection between terminals 12 
and 13, the SE-134C trip relay operates in the fail-safe 
mode.  This mode is used with undervoltage devices 
where the trip relay energizes and its normally open 
contact closes if the ground-fault and ground-check 
circuits are not tripped.  This mode is recommended 
because: 
  — Undervoltage devices release if supply voltage 

fails. 

  —  Undervoltage ground-check circuits do not allow 

the power circuit and open cable couplers to be 
energized until the ground-check loop is verified. 

  The fail-safe mode of operation of the SE-134C trip 
relay can be used for shunt-trip circuits with a stored-
energy trip source.  In this case, the normally closed trip 
contact is used—the contact opens when the SE-134C is 
energized and the ground-fault and ground-check circuits 
are not tripped.  Care must be taken to ensure safe and 
correct operation during power up and power down. 
  Connect terminals 12 and 13 for non-fail-safe trip relay 
operation with shunt-trip devices.  In this mode, the 
normally open trip contact is used—the trip contact is 
closed when a ground-fault or ground-check trip occurs. 
  Shunt-trip circuits are not fail-safe and are not 
recommended because: 
  —  Shunt-trip devices do not operate if supply voltage 

fails. 

  —  Shunt-trip ground-check circuits allow the power 

circuit and open cable couplers to be energized for 
a short interval after supply voltage is applied. 

 

C

AUTION:

  The SE-134C is not a lock-out device.  Follow 

lock-out procedures for maintenance. 
 

3.  I

NDICATION

 

3.1  G

ROUND

 F

AULT

 

  A red LED indicates a ground-fault trip and the 
remote-indication relay GF is energized when the ground-
fault circuit is not tripped (fail-safe indication-contact 
operation).  A green LED indicates a current sensor is 
correctly connected.  If the SE-CS10-series current sensor 
is disconnected or shorted, the green LED will go out and 
the ground-fault circuit will trip.  If the sensor fault is 
intermittent, the ground-fault circuit will trip and the 
green LED will flash to indicate that the trip was initiated 
by a sensor fault. 
 

3.2  G

ROUND

 C

HECK

 

  A red LED indicates a ground-check trip.  A green 
LED indicates a valid ground-check loop and the remote-
indication relay GC is energized when the ground-check 
loop is valid (fail-safe indication-contact operation).  Two 
yellow LED’s indicate the status of an invalid ground-
check loop.  OPEN indicates the loop resistance exceeds 
the trip resistance and SHORT indicates the ground-check 
conductor is shorted to the ground conductor.  A flashing 
yellow LED indicates the corrected cause of a latched 
ground-check trip. 
 

3.3  P

OWER

 

  The green POWER LED indicates that the internal 
power supply is on. 
 

3.4  D

IAGNOSTIC

 E

RROR

 

  The red DIAGNOSTIC ERROR LED indicates that an 
internal error caused the SE-134C to trip.  Return the  
SE-134C to the factory if a reset does not clear the trip. 
  Induced ac current in the ground-check loop can cause 
the LED to flicker.  This is a normal condition and does 
not indicate a diagnostic error; the ground-check 
monitoring circuit is not affected. 
 

4.

  

I

NSTALLATION 

4.1  G

ENERAL

 

  This ground-fault ground-check monitoring system 
consists of an SE-134C Monitor, an SE-CS10-series 
Current Sensor, and an SE-TA6A-series Termination 
Assembly connected as shown in Fig. 1.   Select 
applications can use a combination of SE-TA12A and 
SE-TA12B Termination Assemblies.  See Technical Note 
GC-11.  If required, remote indication and reset can be 
with standard pilot devices, or with an RK-132 Remote-
Indication-and-Reset Kit. 

 

Содержание SE-134C

Страница 1: ...F TRIP LEVEL A GF TRIP TIME S POWER DIAGNOSTIC ERROR 10 50 20 75 30 1 0 40 1 5 50 2 0 70 2 5 1 0 1 3 5 0 1 6 7 5 2 0 10 0 2 5 12 5 G C T E S T R E S E T SHORT OPEN VALID TRIP GROUND CHECK SENSOR TRIP GROUND FAULT 3 0 SHORT OPEN VALID TRIP GROUND CHECK 5 A N G R 5 A N G R 15 R A NG 15 R A NG 25 A NGR 25 A NGR S E 1 3 4 C Copyright 2009 by Littelfuse Startco All rights reserved Publication SE 134C M...

Страница 2: ...est 14 8 1 2 Non Latching Ground Check Trip Test 14 8 2 Trip Relay Fail Safe Mode Test 14 8 3 Current Sensor Verification Test 14 8 4 SE TA6A Series Termination Assembly Tests 15 8 5 Ground Fault Performance Test 15 LIST OF FIGURES FIGURE PAGE 1 SE 134C Typical Application 4 2 SE 134C Outline and Panel Mounting Details 5 3 SE 134C Outline and Surface Mounting Details 6 4 SE CS10 Current Sensors 7 ...

Страница 3: ...ristic that will satisfy the ground check circuit s multi level drive allow induced currents to circulate in the ground check loop survive a phase to ground check fault and clamp the ground check voltage during the fault Although a standard 5 6 volt Zener diode may engage the SE 134C s ground check circuit only an SE TA6A series termination assembly has the compensation required to meet system spe...

Страница 4: ...ip circuits are not fail safe and are not recommended because Shunt trip devices do not operate if supply voltage fails Shunt trip ground check circuits allow the power circuit and open cable couplers to be energized for a short interval after supply voltage is applied CAUTION The SE 134C is not a lock out device Follow lock out procedures for maintenance 3 INDICATION 3 1 GROUND FAULT A red LED in...

Страница 5: ... Outline dimensions and mounting details for the SE CS10 series current sensors are shown in Fig 4 Pass only phase conductors through the sensor window as shown in Fig 1 If a shield ground or ground check conductor enters the sensor window it must be returned through the window before it is terminated Connect the current sensor to terminals 16 and 17 Ground terminal 17 Current sensor primary and s...

Страница 6: ...CT 17 18 TO DISABLE SENSOR VERIFICATION CABLE GROUND GC INDICATOR GF INDICATOR GC G SE TA6A GC G SE TA6A 13 14 15 CONNECT 12 13 FOR NON FAIL SAFE OPERATION OF THE TRIP RELAY CONNECT 14 15 FOR LATCHING GROUND CHECK NFS GROUND CHECK LATCH DISABLE SENSOR VERIFICATION R G NOTES 1 RELAY CONTACTS SHOWN WITH SE 134C DE ENERGIZED TERMINALS 3 4 5 6 AND 7 8 ARE INTERNALLY CONNECTED THE RK 132 REMOTE INDICAT...

Страница 7: ... 8 CABLE GROUND 9 10 1 1 12 13 14 15 16 17 18 RESET GC TEST NFS GC LATCH CURRENT SENSOR DISABLE SENSOR VERIFICATION 1 9 20 2 1 22 23 24 25 26 27 28 GF GC TRIP B TRIP A FUSE F1 1 5 A 500 VAC TIME DELAY F1 FRONT VIEW 98 3 3 87 212 6 8 37 G R O U N D F A U L T G R O U N D C H E C K M O N I T O R GF TRIP LEVEL A GF TRIP TIME S POWER DIAGNOSTIC ERROR 10 50 20 75 30 1 0 40 1 5 50 2 0 70 2 5 1 0 1 3 5 0 ...

Страница 8: ...O U N D F A U L T G R O U N D C H E C K M O N I T O R GF TRIP LEVEL A GF TRIP TIME S POWER DIAGNOSTIC ERROR 10 50 20 75 30 1 0 40 1 5 50 2 0 70 2 5 1 0 1 3 5 0 1 6 7 5 2 0 10 0 2 5 12 5 G C T E S T R E S E T SHORT OPEN VALID TRIP GROUND CHECK SENSOR TRIP GROUND FAULT 3 0 SHORT OPEN VALID TRIP GROUND CHECK 5 A N G R 5 A N G R 15 R A NG 15 R A NG 25 A NGR 25 A NGR 98 3 152 0 114 3 8 0 3 87 5 98 4 50...

Страница 9: ... 0 9 00 279 4 11 00 169 9 6 69 215 9 8 50 266 7 10 50 77 2 3 04 101 6 4 00 108 7 4 28 32 5 1 28 31 8 1 25 38 9 1 53 123 7 4 87 165 0 6 50 225 0 8 86 60 5 2 38 73 2 2 88 80 0 3 15 M4 8 32 M10 0 375 M10 0 375 H1 X1 TERMINAL LOCATION MAY VARY SE CS10 2 5 63 5 2 50 135 1 5 32 124 0 4 88 72 6 2 86 27 9 1 10 69 9 2 75 54 4 2 14 M4 8 32 I 138 2 5 44 171 5 6 75 200 7 7 90 88 9 3 50 J 138 2 5 44 171 5 6 75...

Страница 10: ... 800 TEC FUSE 1 800 832 3873 Made in Saskatoon Canada Rating 5 6 Vdc 105 mA 50 W Max Use with Ground Fault Ground Check Monitor Models SE 134 and SE 134C R 8 0 0 31 LR 53428 US C R Revision SE TA6A WL TERMINATION ASSEMBLY Serial Number 00 00000000 1 800 TEC FUSE 1 800 832 3873 Made in Saskatoon Canada Rating 5 6 Vdc 105 mA 50 W Max Use with Ground Fault Ground Check Monitor Models SE 134 and SE 13...

Страница 11: ...1 800 TEC FUSE 1 800 832 3873 Made in Saskatoon Canada TERMINATION ASSEMBLY FIGURE 6 SE TA6ASF WL Small Format Termination Assembly NOTES 1 ONE RED AND ONE GREEN LED LIGHT 24 120 VAC DC NOT POLARITY SENSITIVE 2 YELLOW PUSH BUTTON 3 A 240 VAC A600 0 5 A 125 VDC Q600 3 DIMENSIONS IN MILLIMETRES INCHES 4 INDICATES CLEARANCE REQUIRED 5 PANEL THICKNESS 1 0 TO 6 0 0 04 TO 0 24 6 NEMA 4X LEGEND PLATE 30 ...

Страница 12: ...Page 10 SE 134C Ground Fault Ground Check Monitor Rev 2 Pub SE 134C M December 16 2009 FIGURE 8 PPI 600V Parallel Path Isolator ...

Страница 13: ...HE FLANGE IS ISOLATED FROM THE GROUND PIN AND USE A MATING PLUG WITH A NON METALLIC HOUSING OR ISOLATE THE FLANGE FROM THE CHASSIS IF THE MATING PLUG HAS A METALLIC HOUSING 3 CABLE PLUGS AND RECEPTACLES WITH GROUNDED METAL HOUSINGS MUST BE ISOLATED FROM EARTH TO PREVENT PARALLEL GROUND PATHS OUTGOING OUTGOING GROUND CHECK GROUND GC G PPI 600V CHASSIS GROUND BUS CABLE GROUND G GROUND CHECK GC GROUN...

Страница 14: ...ng Mode Latching or Non Latching Trip Relay CSA UL Contact Rating 8 A Resistive 250 Vac 5 A 30 Vdc HP B300 Pilot Duty Supplemental Contact Ratings Make Carry 0 2 s 30 A Break dc 75 W Resistive 35 W Inductive L R 0 04 Break ac 2 000 VA Resistive 1 500 VA Inductive PF 0 4 Subject to maximums of 8 A and 250 V ac or dc Contact Configuration Isolated N O and N C Contacts Operating Mode Fail Safe or Non...

Страница 15: ...m 14 Dimensions 105 x 40 x 22 2 mm 4 13 x 1 57 x 0 87 Shipping Weight 300 g 0 7 lb SE TA6ASF WL Characteristic 5 6 V Zener Temperature Compensated Power Rating 12 W Wire Leads 18 AWG 300 mm 11 8 Dimensions 58 8 x 19 x 12 7 mm 2 32 x 0 75 x 0 5 Shipping Weight 45 g 0 1 lb Certification CSA Canada and USA LR 53428 US C R 6 ORDERING INFORMATION SE 134C Future Options Power Supply 0 Universal ac dc Su...

Страница 16: ...nd the SHORT LED will be flashing The TRIP contacts terminals 22 23 and 24 25 will remain latched and ground check indication contacts terminals 26 27 and 26 28 will change state Reset the monitor 8 1 2 NON LATCHING GROUND CHECK TRIP TEST Connect the monitor current sensor and termination device as shown in Fig 10 With supply voltage applied the POWER SENSOR and VALID LED s will be on Open the gro...

Страница 17: ...uipment manufacturer s detailed instructions b Verify proper location of the ground fault current transformer Ensure the cables pass through the ground fault current transformer window This check can be done visually with knowledge of the circuit The connection of the current transformer secondary to the SE 134C is not polarity sensitive c Verify that the system is correctly grounded and that alte...

Страница 18: ...R GROUND FAULT RELAY TEST UNIT SE 100T or SE 400 NOTES 1 MOMENTARILY CONNECT 9 10 TO PERFORM REMOTE RESET 2 MOMENTARILY CONNECT 11 12 TO PERFORM REMOTE GROUND CHECK TEST 3 CONNECT 12 13 FOR NON FAIL SAFE OPERATION OF THE TRIP RELAY 4 CONNECT 14 15 FOR LATCHING GROUND CHECK TRIP 5 CONNECT 17 18 TO DISABLE CURRENT SENSOR VERIFICATION 6 CONTACTS SHOWN DE ENERGIZED 7 REMOVE TERMINAL 3 CONNECTION WHEN ...

Отзывы: