Page 16
SE-134C Ground-Fault Ground-Check Monitor
Rev.
0
Pub. SE-134C-M, December 16, 2009.
SE-134C
G
GC
SE-TA6A-SERIES
TERMINATION
ASSEMBLY
26
19
22
24
25
23
20
21
27
28
TRIP A
TRIP B
GF
GF
GC
GC
NOTE 6
OHMS
CURRENT
SENSOR
DISABLE
SENSOR
VERIFICATION
17
16
18
SUPPLY
VOLTAGE
L
N
NOTE 1
NOTE 5
RESET
L1
L2/N
NOTE 2
NOTE 3
SUPPLY
VOLTAGE
L
N
NFS
GC
TEST
NOTE 4
GROUND-
CHECK
LATCH
3
4
SPG
5
6
7
8
GROUND
CHECK
CABLE
GROUND
NOTE 7
1
2
9
10
11
12
13
14
15
OUTPUT
SE-CS10
CURRENT
SENSOR
GROUND-FAULT RELAY
TEST UNIT
(SE-100T or SE-400)
NOTES:
1. MOMENTARILY CONNECT 9 & 10 TO
PERFORM REMOTE RESET.
2. MOMENTARILY CONNECT 11 & 12 TO
PERFORM REMOTE GROUND-CHECK
TEST.
3. CONNECT 12 & 13 FOR NON-FAIL-SAFE
OPERATION OF THE TRIP RELAY.
4. CONNECT 14 & 15 FOR LATCHING
GROUND-CHECK TRIP.
5. CONNECT 17 & 18 TO DISABLE CURRENT-
SENSOR VERIFICATION.
6. CONTACTS SHOWN DE-ENERGIZED.
7. REMOVE TERMINAL 3 CONNECTION
WHEN PERFORMING DIELECTRIC TESTS.
FIGURE 10. Ground-Fault-Test Circuit.
REVERSE-BIASED TEST
FORWARD-BIASED TEST
100
5 W
W,
-
+
15 Vdc
VOLTS
+
-
15 Vdc
G
GC
SE-TA6A-SERIES
TERMINATION
ASSEMBLY
G
GC
SE-TA6A-SERIES
TERMINATION
ASSEMBLY
VOLTS
100
5 W
W,
FIGURE 11. Termination-Assembly-Test Circuits.