Page 3 

 

SE-330AU Neutral-Earthing-Resistor Monitor

 

Rev. 4-I-101817 

 
 

 

 

 

 

 

FIGURE 1.  Configuration Switches. 

 

2.1.4.3  S

ENSING

-R

ESISTOR

 

S

ELECTION

 

(S5)

 

  Set switch S5 to the resistance of the sensing resistor.  For 
the ER-600VC, ER-5KV, and ER-5WP select 20 k

W

.  For 

the  ER-15KV,  ER-25KV,  and  ER-35KV,  select  100 k

W

.  

Switch  S5  sets  the  V

N

  TRIP  LEVEL  range.    See  

Section 2.1.3. 

 
2.1.4.4  F

REQUENCY

 

(S6)

 

  Set switch S6 to 50 or 60 Hz to tune the digital filter to 
the line frequency of the monitored system.

 

 

2.1.4.5  U

PGRADE

 M

ODE

 

(S8)

 

  The  microSD™  card  is  used  for  firmware  upgrades.  
See Section 4.1.2 for upgrade instructions. 

N

OTE

:  An  upgrade  causes  an  SE-330AU  restart  and  this 

may cycle the output relays.   
 

2.1.5  R

ESISTOR-

F

AULT 

T

RIP 

T

IME

 

  The  resistor-fault  trip  time  can  be  adjusted  from  12 
(default) to 60 seconds using the SE-MON330 software or 
via network communications. 
 

2.1.6  R

ESISTOR-

F

AULT 

T

RIP 

L

EVEL

 

  The  resistor-fault  trip  level  can  be  adjusted  using  the 
SE-MON330  software  or  via  network  communications.  
See Section 6.1. 
 

2.1.7  G

EO-

M

AGNETIC 

F

ILTER

 

  A  low-frequency  earth  current  can  be  caused  by  the 
Earth’s  magnetic  field  and  from  charged  clouds  passing 
overhead during a thunderstorm.  In some rare conditions, 
this can cause a false resistor-fault trip.  Enabling the geo-
magnetic  filter  and  increasing  the  resistor-fault  trip  time 
can help counteract these effects. 
  A  trip  time  of  30  seconds  is  recommended  when  the 
geo-magnetic filter is enabled. 

  The  geo-magnetic  filter  is  disabled  by  default,  but  can 
be  enabled  using  the  SE-MON330  software  or  via 
network communications. 
 

2.2  C

ALIBRATION

 

  The  SE-330AU  measures  the  resistance  change  of  the 
NER  relative  to  the  NER-resistance  value  determined  at 
the  time  of  calibration.    When  the  resistance  change  is 
greater  than  a  threshold  amount  (500 

  for  20-k

 

systems, 2,500 

 for 100-k

 systems), a resistor-fault trip 

occurs.  Calibrate  the  SE-330AU  on  new  installations,  if 
the NER is changed, or if the sensing resistor is changed. 
  The  CALIBRATION  button  is  located  behind  the 
access  cover  on  the  front  panel,  and  it  is  recessed  to 
prevent inadvertent activation. 
 

N

OTE

:

    Calibration  must  be  performed  with  the  

SE-330AU connected to the sensing resistor and NER of 
the installed system. 

 
N

OTE

:

    Where  used,  coupling  components  for  lockout 

earth-fault  protection  devices  must  be  disconnected  from 
the supply during calibration. 

 

  To calibrate, press and hold the CALIBRATION button 
until the green CALIBRATED LED turns off and returns 
to on  (if the LED is already off, press and hold until the 
LED  turns  on).    Calibration  takes  approximately  two 
seconds.    If  calibration  is  not  successful,  a  resistor-fault 
trip  occurs,  the  RESISTOR  FAULT  TRIP  LED  will  be 
on,  the  CALIBRATED  LED  will  be  off,  and  the 
DIAGNOSTIC LED will flash the calibration-error code.  
See Section 2.8. 
  The  SE-330AU  may  be  calibrated  remotely  using  
the  SE-MON330  software  with  the  USB  interface  or  the 
communications options. 
  If  latching  resistor  fault  (switch  S4)  is  selected,  the 
calibration-error  code  flashes  until  RESET  is  pressed 
even if the CALIBRATED LED is on. 
  The calibration value is stored in non-volatile memory. 

 
2.3  CT D

ETECTION 

  The  SE-330AU  monitors  the  continuity  of  the  CT 
circuit.    When  an  open  CT  circuit  is  detected  for  two 
seconds,  the  SE-330AU  will  trip  on  earth  fault  and  the 
diagnostic  LED  will  flash  the  CT-Detection-Error  code.  
See  Section  2.8.    The  CT-Detection-Error  code  remains 
until  CT-circuit  continuity  is  detected  and  RESET  is 
pressed.    If  supply  voltage  is  cycled,  earth-fault  trip 
indication  is  not  reset  but  the  CT-Detection-Error 
indication  is  reset.    CT-Detection-Error  indication  will 
resume  after  two  seconds  if  CT-circuit  continuity  is  not 
detected. 
 

 

Содержание SE-330AU

Страница 1: ...il techline littelfuse com www littelfuse com SE 330AU SE 330AU MANUAL NEUTRAL EARTHING RESISTOR MONITOR Revision 4 I 101817 Copyright 2017 Littelfuse Startco All rights reserved Document Number PM 12...

Страница 2: ...Page i SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 This page intentionally left blank...

Страница 3: ...Calibration and Open Test 33 9 1 2 Voltage Test 33 9 2 Sensing Resistor Test 33 9 3 Analog Output Test 33 9 4 Earth Fault Performance Test 34 Appendix A SE 330AU Revision History 35 LIST OF FIGURES F...

Страница 4: ...Page iii SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 This page intentionally left blank...

Страница 5: ...resistor monitor that detects NER failures and earth faults in resistance earthed systems The SE 330AU measures NER resistance NER current and transformer or generator neutral to earth voltage The co...

Страница 6: ...This parameter must be set using a PC running the SE MON330 software connected to the USB interface The setting range is 2 to 100 of CT primary rating in 1 increments For example if the MEM parameter...

Страница 7: ...ge is greater than a threshold amount 500 for 20 k systems 2 500 for 100 k systems a resistor fault trip occurs Calibrate the SE 330AU on new installations if the NER is changed or if the sensing resi...

Страница 8: ...afe operation using the SE MON330 software or network communications The default mode is non fail safe In non fail safe mode relays energize on fault Network enabled SE 330AU s can be remotely tripped...

Страница 9: ...0 5 1 60 ER 5KV 20 kW 1 050 605 5 121 0 5 1 100 ER 5KV 20 kW 1 100 635 5 127 0 5 1 100 ER 5KV 20 kW 1 140 658 5 132 0 5 1 100 ER 5KV 20 kW 3 300 1 905 5 381 0 5 1 200 ER 5KV 20 kW 6 600 3 810 5 762 0...

Страница 10: ...n ER 5WP in applications in which it might be exposed to moisture The ER 15KV ER 25KV and ER 35KV include moisture resistant terminal covers Use suitable water tight fittings Connect terminal G to ear...

Страница 11: ...Page 7 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 3 SE 330AU Connection Diagram...

Страница 12: ...Page 8 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 4 SE 330AU Outline and Panel Mounting Details...

Страница 13: ...Page 9 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 5 SE 330AU Outline and Surface Mounting Details...

Страница 14: ...Page 10 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 6 SE IP65CVR G Weatherproof Cover Outline...

Страница 15: ...Page 11 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 7 SE IP65CVR G Weatherproof Cover Installation...

Страница 16: ...Page 12 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 8 ER 600VC Sensing Resistor...

Страница 17: ...Page 13 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 9 SE MRE 600 Moisture Resistant Enclosure...

Страница 18: ...Page 14 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 10 ER 600VC Installed in SE MRE 600...

Страница 19: ...Page 15 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 11 ER 5KV Sensing Resistor...

Страница 20: ...Page 16 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 12 ER 5WP Sensing Resistor...

Страница 21: ...Page 17 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 13 ER 15KV Sensing Resistor...

Страница 22: ...Page 18 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 14 ER 25KV Sensing Resistor...

Страница 23: ...Page 19 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 15 ER 35KV Sensing Resistor...

Страница 24: ...Page 20 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 16 EFCT 1 Earth Fault Current Sensor...

Страница 25: ...Page 21 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 17 SE CS30 70 Earth Fault Current Sensor...

Страница 26: ...Page 22 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 18 EFCT 26 and SE CS30 26 Earth Fault Current Sensors...

Страница 27: ...Page 23 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 FIGURE 19 RK 332 Remote Indication and Reset FIGURE 20 PGA 0520 Analog Percent Current Meter...

Страница 28: ...rom station earth and precautions must be taken with the power supply and the trip contacts See Technical Note RG 1 NGR Monitoring with Isolated Ground Beds at www littelfuse com relayscontrols A conf...

Страница 29: ...the firmware upgrade process The red DIAGNOSTIC LED blinks rapidly while the firmware upgrade is running and the SE 330AU may reset multiple times during the upgrade process Do not remove the SD card...

Страница 30: ...Littelfuse Startco Critical diagnostic code EF LED 2 No Change RF LED 2 ON K1 Trip SD Card DIAGNOSTIC LED flash code 1 L 5 S 1 L SD Card is full or a write error occurred Delete files or use a differ...

Страница 31: ...stic code EF LED 2 No Change RF LED 2 No Change K1 No Change DIAGNOSTIC LED Solid Red SE 330AU processor failed to start Cycle supply If problem persists consult Littelfuse Startco K1 De energized Pre...

Страница 32: ...1 2 3 4 5 A SE CS30 x 0 75 1 5 1 8 2 4 3 0 6 0 12 0 18 0 24 0 30 0 A Trip Time 0 10 0 12 0 14 0 16 0 18 0 20 0 25 0 30 0 35 0 40 0 50 s Trip Level Accuracy 0 20 of setting Trip Time Accuracy 0 20 of s...

Страница 33: ...ognized Mounting Configurations Panel Mount and Optional Surface Mount Dimensions Height 213 mm 8 4 Width 99 mm 3 9 Depth 132 mm 5 2 Shipping Weight 2 0 kg 4 4 lb Environment Operating Temperature 40...

Страница 34: ...600VC Maximum Voltage 600 Vac Maximum Current 30 mA Resistance 20 kW Thermal 420 Vac Continuous 600 Vac 6 minutes on 60 minutes off Shipping Weight 300 g 0 7 lb ER 5KV Maximum Voltage 2 500 Vac Maxim...

Страница 35: ...ow Diameter 70 mm 2 7 Shipping Weight 1 2 kg 2 5 lb Certifications CSA UL CE Compliance RoHS IEC 60044 1 7 ORDERING INFORMATION NOTE Please refer to the SE 330 Product Change Notice PCN document for u...

Страница 36: ...nd Ethernet IP protocols 3 Includes IEC 61850 and Modbus TCP protocols 4 Available at www littelfuse com relayscontrols 8 WARRANTY The SE 330AU Neutral Earthing Resistor Monitor is warranted to be fre...

Страница 37: ...will damage the SE 330AU and the ER sensing resistor The VN TRIP LEVEL is the trip voltage at terminal N not terminal R Procedure Connect the ER sensing resistor connection to the SE 330AU and calibr...

Страница 38: ...fy proper reaction of the circuit interrupting device in response to a simulated or controlled earth fault current To simulate earth fault current use CT primary current injection does not apply for b...

Страница 39: ...ed in Section 2 8 SECTION 3 Updated installation instructions SECTION 4 SD Card note added SECTION 5 Troubleshooting information added SECTION 7 Ordering information updated REVISION 4 H 120716 APPEND...

Страница 40: ...agnostic LED error removed SECTION 6 Earth Fault Circuit Trip Level updated USB Communications specifications added SECTION 7 Ordering information updated HARDWARE REVISION HISTORY HARDWARE REVISION 1...

Страница 41: ...filter Added support for 12 to 60 s resistor fault trip time Improved log file descriptions IEC 61850 GOOSE network input support now always enabled Improved compatibility for Modbus TCP Web page disa...

Страница 42: ...Page 38 SE 330AU Neutral Earthing Resistor Monitor Rev 4 I 101817 This page intentionally left blank...

Отзывы: