INSTALLATION:ROUGH-IN SECTION END MOUNT

(Requires End Mount Panel Assembly)

(Ref:  Fig. 1 and 4)

Remove bar hanger bracket screws 

c

 and relocate bar

hanger brackets 

b

 with bar hangers 

g

  to alternate mounting

holes 

f

 (on ends of cover can) and secure using same

screws.  Bar hangers are adjustable from 14 

1

/

2

" to 24".

Break along bar hanger score lines to reduce spacing to  12".
Rough-in section may be off-centered if necessary, but bar
hangers should be secured together with bar hanger locking
screws 

e

.  Position the rough-in section with the side flanges

l

 of the cover can 

a

  flush with the inner (stud side) surface

of wall material.

WOOD STUDS:

Adjust bar hangers to fit against studs.  Secure by tightening
the locking screws 

e

.  Drive nailer tabs into wood.

METAL STUDS:

Installation is the same as for wood studs except that sheet
metal screws (not provided) should be used to fasten the
ends of the bar hanger to the studs.  These screws should
have a minimum pullout rating of 30 pounds.

CLOSE-IN:

DRY WALL:

Cutout hole in wall material should not exceed 4  1/2"  x  13 3/
4" (max.). Note: The top of the cover can 

a

 may be used as a

template to trace cutout onto wall material. Install trim ring
halves 

j

 and secure with trim ring mounting screws 

i

.

WET  WALL:

Do not plaster inside the plaster ring opening. Install trim ring
halves 

j

 and secure with trim ring mounting screws 

i

.

PAGE 3

EMCSA00679

   REV B

FIGURE 4

EMERGENCY LIGHTING SYSTEMS

TEL: 800-334-8694 Fax: 770-981-8141 www.lithonia.com

Содержание PreCise ELA LCRIS Series

Страница 1: ...wiring to power supply turn off electricity at fuse or circuit breaker 3 Disconnect A C power before servicing 4 All servicing should be performed by qualified personnel 5 Consult your local building code for approved wiring and installation 6 Do not use outdoors 7 Do not mount near gas or electric heater 8 Fixture must be grounded to avoid potential electric shock 9 Equipment should be mounted in...

Страница 2: ...tion with the side flanges l of the cover can a flush with the inner stud side surface of wall material WOOD STUDS Adjust bar hangers to fit against studs Secure by tightening the locking screws e Drive nailer tabs into wood METAL STUDS Installation is the same as for wood studs except that sheet metal screws not provided should be used to fasten the ends of the bar hanger to the studs These screw...

Страница 3: ...UDS Adjust bar hangers to fit against studs Secure by tightening the locking screws e Drive nailer tabs into wood METAL STUDS Installation is the same as for wood studs except that sheet metal screws not provided should be used to fasten the ends of the bar hanger to the studs These screws should have a minimum pullout rating of 30 pounds CLOSE IN DRY WALL Cutout hole in wall material should not e...

Страница 4: ... d un radiateur électrique ou au gaz 8 L appareil doit être mis à la terre afin d éviter toute possibilité de choc électrique 9 L appareil doit être installé dans un endroit et à une hauteur qui empêcheront tout accès du personnel non autorisé 10 L usage d équipement auxiliaire non recommandé par le fabricant peut présenter des dangers 11 N utiliser cet appareil que pour l usage auquel il est dest...

Страница 5: ...upports g sont ajustables de 14 1 2 po à 24 po Positionner le boîtier de manière à ce que le collet l du couvercle a soit affleuré avec l intérieur côté montant du mur MONTANTS DE BOIS Ajuster les supports aux montants du mur Fixer en vissant les vis de blocage e Clouer les pattes de clouage MONTANTS DE MÉTAL Même installation que pour le bois sauf utiliser des vis à métal non fournies pour sécuri...

Страница 6: ...t affleuré avec l intérieur côté montant du mur MONTANTS DE BOIS Ajuster les supports tout près des montants Fixer à l aide des vis de blocage e Clouer les pattes de clouage MONTANTS DE MÉTAL Même installation que pour le bois sauf utiliser des vis à métal non fournies pour sécuriser les supports aux montants Ces vis doivent être calibrées pour au moins 30 livres FERMETURE DU MUR MUR DE GYPSE L ou...

Отзывы: