SELF-DIAGNOSTICS SYSTEM OPERATION 

(EMERGENCY OPERATION UNITS ONLY) 

 

Normal Power-Up Sequence

  

 

At power-up, the red and green LED indicators will alternately flash for one to two seconds.  Next, the unit will 
go through a “Power-Up Quick Test” with the green LED flashing quickly.  If no power-up faults were 
detected, the green LED will then flash slowly for up to 36 hours to indicate that the battery is charging.  If any 
faults were detected during the “Power-Up Quick Test”, these will be indicated by a flashing red LED indicator 
(see below for interpretation of flashing sequences).  The red LED may be accompanied by a buzzer.  This 
buzzer may be disabled by a short press of the test switch or by the “SILENCE ALARM” button on the remote 
tester and will remain disabled for a period of 196 hours.  After the fault has been corrected, the red LED flash 
and buzzer will be cleared automatically and the unit will return to normal operation except in the case of lamp 
failure.  Once relamping has been completed, perform a manual test to clear the fault. 

 

Emergency Operation

  

 

Emergency operation occurs when AC power fails.  The unit remains in this mode until AC power is restored.  
During emergency operation, both red and green LED indicators are disabled.  Upon restoration of AC power, 
the green LED will flash for up to 36 hours to indicate that the unit is in battery charging mode. Allow 72 hours 
for the battery to fully charge. 

 

User Interface 

 

Green LED Indicator 

 

Steady On – AC power is present and battery is fully charged 

 

Slow Flash – Battery charging 

 

Fast Flash – Unit is performing an automatic or manually initiated self-test 

 

Red LED Indicator 

 

Single Flash – Battery fault 

 

Double Flash – Lamp failure 

 

Triple Flash – Charger fault 

 

Quad Flash – Emergency transfer failure  

(If more than one fault condition is present simultaneously, the red LED will flash each fault pattern in 
sequence, and then repeat) 

 

Red and Green LED Indicators Together 

 

Slow flashing red and green – Low line voltage 

 

Fast flashing red and green – High line voltage 

 

Pushbutton Test Switch 

 

Long Press (over 0.5 seconds) – Transfers unit to emergency (battery) operation as long as button is 
depressed 

 

Short Press – Initiates various self tests 

o

 

One Press – Cancel any self-test currently running 

o

 

Two Presses – Start 1 minute self-test 

o

 

Three Presses – Start 90 minute self-test 

o

 

Seven presses – Forces a complete system reset 

(The unit will allow up to seven 1 minute tests during the first 24 hours of operation.  Allow at least 24 
hours for battery charging before performing any extended amount of testing) 

 

Buzzer – Sounds in unison with the flashing red LED if a fault is detected.  May be disabled for up to 196 hours 
by a short press of the test switch. 

 

IR receiver – Used with the optional hand-held IR remote tester to initiate or cancel manual testing. 


 
 

Содержание LZ Series

Страница 1: ...lacement parts In Class I Division 2 areas install equipment in accordance with appropriate NEC articles plus any other applicable codes To avoid static discharge do not attach any ungrounded metal hardware to the enclosure Do not use this equipment outdoors CLASS I DIV 2 HAZARDOUS LOCATION GROUPS A B C AND D ZONE 2 GROUPS IIC IIB AND IIA CLASS II DIV 2 GROUPS F AND G AND CLASS III DIV 1 AND 2 INS...

Страница 2: ... See Figures 1 and 2 4 Connect conduit supply to hub on unit 5 Hookup AC service to the connector assembly as follows Enclosure Cover Screws 2 Lens Screws 4 Hub Vent Test Switch Figure 1 Figure 2 AC Charge IR Receiver Status Indicator 120 VAC OPERATION 277 VAC OPERATION Black Wire 120V Line Blue Wire 277V Line White Wire Common White Wire Common Green Wire Ground Green Wire Ground Unused primary w...

Страница 3: ... adhesive backing are supplied Apply label s to exit lens as necessary 7 Remount exit lens using lens screws Close cover and secure with cover screws INSTRUCTIONS OPERATION 1 Energize AC power to exit Unit will initiate normal power up sequence See page 4 ...

Страница 4: ...ll flash for up to 36 hours to indicate that the unit is in battery charging mode Allow 72 hours for the battery to fully charge User Interface Green LED Indicator Steady On AC power is present and battery is fully charged Slow Flash Battery charging Fast Flash Unit is performing an automatic or manually initiated self test Red LED Indicator Single Flash Battery fault Double Flash Lamp failure Tri...

Страница 5: ...9140053441 Rev 1 5 ...

Отзывы: